5808011-JIM-A-0320
Johnson Controls Ducted Systems
33
J10
(10)
208-3-60 16.2 110
25
3.03
9.6
5.5
20
None
-
-
-
67.9
73.4
80
80
E18
13.5
2
37.5
71.4
78.3
80
80
E24
18
2
50
87
93.9
90
100
E36
25.5
2
70.8
113
119.9
125
125
E54
40.6
2
112.7
165.4
172.3
175
175
230-3-60 16.2 110
25
3.03
9.6
5.5
20
None
-
-
-
67.9
73.4
80
80
E18
18
2
43.3
78.6
85.5
80
90
E24
24
2
57.7
96.6
103.5
100
110
E36
34
2
81.8
126.8
133.6
150
150
E54
54
2
129.9
154.4
161.3
175
175
460-3-60
7.6
52
12
1.6
4.7
2.2
20
None
-
-
-
32.7
34.9
40
40
E18
18
2
21.7
39.3
42
40
45
E24
24
2
28.9
48.3
51
50
60
E36
34
2
40.9
63.3
66
70
70
E54
54
2
65
77.1
79.9
90
90
575-3-60
5.1 43.8
8
1.35
3.2
1.8
20
None
-
-
-
21.4
23.2
25
25
E18
18
2
17.3
30.6
32.9
35
35
E24
24
2
23.1
37.9
40.1
40
45
E36
34
2
32.7
49.9
52.1
50
60
E54
54
2
52
61
63.3
70
70
J12
(12.5)
208-3-60 18.6 149
29
2.1
14
5.5
20
None
-
-
-
79
84.5
100
100
E18
13.5
2
37.5
79
84.5
100
100
E24
18
2
50
92.5
99.4
100
100
E36
25.5
2
70.8
118.5
125.4
125
150
E54
40.6
2
112.7
170.9
177.8
175
200
230-3-60 18.6 149
29
2.1
14
5.5
20
None
-
-
-
79
84.5
100
100
E18
18
2
43.3
84.1
91
100
100
E24
24
2
57.7
102.1
109
110
110
E36
34
2
81.8
132.3
139.1
150
150
E54
54
2
129.9
159.9
166.8
175
175
460-3-60
9
60.9
14
1.26
6.6
2.2
20
None
-
-
-
38.9
41.1
45
50
E18
18
2
21.7
41.6
44.4
45
50
E24
24
2
28.9
50.6
53.4
60
60
E36
34
2
40.9
65.6
68.4
70
70
E54
54
2
65
79.5
82.3
90
90
575-3-60
7.1
56
11
0.66
5.2
1.8
20
None
-
-
-
28.5
30.3
35
35
E18
18
2
17.3
33.1
35.4
35
40
E24
24
2
23.1
40.4
42.6
45
45
E36
34
2
32.7
52.4
54.6
60
60
E54
54
2
52
63.5
65.8
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Electric heat multipliers
Voltage
kW capacity multipliers
1
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.
Nominal
Applied
240
208
0.75
230
0.92
480
460
0.92
600
575
0.92
J06-12ZB High Static Indoor Blower - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
MCA
1
w/Pwr
Exh
(Amps)
Max fuse
2
/
breaker
3
size
(amps)
Max Fuse
2
/
Breaker
3
Size w/
Pwr Exh
(Amps)
RLA LRA MCC
FLA
FLA
FLA
FLA
Model kW Stages Amps