SMOKE DETECTORS
- (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
•
COIL GUARD
- Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
•
STAINLESS STEEL HEAT EXCHANGER
- For applica-
tions in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.
•
STAINLESS STEEL DRAIN PAN -
An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
•
PHASE MONITORS
- Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
•
HIGH STATIC DRIVE
- Includes a belt and blower pulley
upgrade to enhance blower performance.
•
DIRTY FILTER SWITCH
- This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
•
HINGED FILTER DOOR/”TOOL FREE” BLOWER AND
ACCESS PANELS (not hinged)
- This option allows for
easy access and maintenance.
NOTE:
Knobs are shipped separately within the unit to
prevent shipping damage. These must be field
installed for tool free operation.
•
HINGED/"TOOL FREE" BLOWER, BLOWER MOTOR,
FILTER AND ELECTRIC ACCESS PANELS -
This
option allows for complete hinged and tool free access to
the unit's blower, blower motor, filters and electrical panel
sections.
CONTROL OPTIONS
•
Johnson Light Commercial System (LCCS)
- Provides
rooftop system integration for LCCS single zone,
change-over bypass and VAV systems.
•
Johnson UNT 1126 Rooftop Controller
- N2 protocol
with air proving and dirty filter sensors. Hardware con-
tains generic application logic; field engineering and/or
modification may be required.
FIELD-INSTALLED ACCESSORIES
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS
- Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER
-
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
ROOF CURBS
- Fourteen-inch high roof curbs provide a
water-tight seal between the unit and the finished roof.
These full perimeter curbs meet the requirements of the
National Roofing Contractors Association (NRCA) and
are shipped knocked-down for field assembly.
They're designed to fit inside the base rails of the unit
and include both a wood nailing strip and duct hanger
supports.
•
HIGH ALTITUDE NATURAL GAS
- Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
•
PROPANE
- Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
•
HIGH ALTITUDE PROPANE
- Burner orifices and pilot
orifices are provided for proper furnace operation at alti-
tudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
•
SIDE DUCT FLANGES
- One-inch flanges replace the
supply and return air panels on the rear of the unit to
accommodate horizontal duct connections. These
flanges can also be used individually for bottom supply/
horizontal return or horizontal supply/bottom return. They
cannot be used on units with power exhaust.
•
BAROMETRIC RELIEF DAMPER
- This damper acces-
sory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
Factory installed smoke detectors in the return air
may be subjected to freezing temperatures during
“off” times due to outside air infiltration. These
smoke detectors have an operation limit of 32°F to
131°F. Smoke detectors installed in areas that
could be outside those limitations will have to be
moved to prevent having false alarms.