IOM4710 Input/Output Module Installation Instructions

4

3.

Tighten the cover screw to secure the cover to the
base.

Wiring   

Refer to the 

MS/TP Communications Bus Technical 

Bulletin (LIT-12011034) 

for more information on 

MS/TP

 

devices.

To wire the IOM controller:

1.

Terminate wiring per engineering drawings.

2.

If the IOM is connected to the FC Bus of a Network
Automation Engine (NAE) or Network Control
Engine (NCE), wire the FC Bus in a daisy chain
(Figure 6).

3.

If the IOM is connected to the SA Bus of an NCE or
FEC, wire the SA Bus in a daisy chain (Figure 7).

Note:

The SA/FC Bus Port (RJ-12, 6-pin, modular 

connector) provides 15 VDC on two of its pins, 
which is used to power the MS-BTCVT (Figure 8).

Note:

If the IOM controller is at one end of the SA 

Bus daisy chain, set the End-of-Line (EOL) switch 
to ON.

4.

Connect power to the IOM controller.

5.

Download and commission the IOM controller. See
the 

Commissioning

 section.

SA/FC Bus Port

The SA/FC Bus port on the front of the IOM is an 
RJ-12, 6-position modular jack that provides a 
connection for the Wireless Commissioning Converter.  
See Table 1 for more information. The SA/FC Bus Port 
pin assignment is shown in (Figure 8).   

IMPORTANT:

Do not connect 24 VAC supply 

power to the IOM controller before finishing wiring 
and checking all wiring connections. Short circuits or 
improperly connected wires may result in permanent 
damage to the equipment.

IMPORTANT:

User copper conductors only. Make 

all wiring in accordance with local, national, and 
regional regulations. The IOM controller is a 
low-voltage (<30 VAC) device. Do not exceed the 
IOM controller electrical ratings.

IMPORTANT:

Prevent any static electric discharge 

to the IOM controller. Static electric discharge can 
damage the IOM controller and void any warranties.

Figure 5: Attaching the Cover

SA BUS

STAT

C

O

M

+

+

1

5

V

O

U

T

 8

O

C

O

M

 8

O

U

T

 9

O

C

O

M

 9

O

U

T

 4

O

C

O

M

 4

O

U

T

 5

O

C

O

M

 5

O

U

T

 6

O

C

O

M

 6

O

U

T

 7

O

C

O

M

 7

UNIVERSAL

F

IG

:I

O

M

_

cv

r_

a

tt

ch

Hinge 

Slots

Hinge

Tabs

Cover

Screw

Figure 6: FC Bus Terminal Block Wiring

Stranded 3-Wire Twisted Shielded Cable

Isolated Shield

Connection

Terminal

+

_

CO

M

SH

L

D

To Next

Device on

the FC Bus

Segment

FC Bus

Terminal

Block Plugs

F

IG

: f

c_

bus

_t

er

m

s

+

_

CO

M

SH

L

D

Terminating Device

on FC Bus Segment

To Next

Device on

the FC Bus

Segment

Daisy Chained Device 

on FC Bus Segment

Stranded, 4-Wire (2 Twisted Pair) Shielded Cable

(One twisted pair is the   and  leads. 

The second pair is COM and SA PWR.) 

+

 

-

Cable Shield

Connection

To Next

Device on

the SA Bus

F

IG

:s

a_b

us

_

te

rm

s

SA Bus

Terminal

Block Plugs

Terminating Device

on SA Bus

Daisy Chained Device 

on SA Bus

To Next

Device on

the SA Bus

+

CO

M

SA

 PW

R

+

CO

M

SA

 PW

R

Figure 7: SA Bus Terminal Block Wiring

Содержание IOM4710

Страница 1: ...dels that are UL Listed UUKL 864 Listed Smoke Control Equipment See Repair Information on page 10 for UUKL 864 Listed IOM4710 models For Metasys system smoke control applications you must refer to the...

Страница 2: ...the enclosure wall or the transformer does not obstruct ventilation of or radiate heat into the IOM controller housing Wall Mount Applications Use the holes in the mounting clips for wall mount applic...

Страница 3: ...hinge tabs cover onto the top of the hinge slots base See Figure 5 Note Do not fully insert the tabs into the slots If the tabs are fully inserted into the slots the cover hinge may not allow the cov...

Страница 4: ...troller before finishing wiring and checking all wiring connections Short circuits or improperly connected wires may result in permanent damage to the equipment IMPORTANT User copper conductors only M...

Страница 5: ...4 20 mA input signal Internal 100 ohm load Impedence enabled disabled by jumper B Analog Input Resistive Mode Accepts 0 600k ohm input signal Internal 12 V 15k ohm Pullup RTD 1k Nickel Johnson Contro...

Страница 6: ...n activated 30 VAC maximum output voltage 40 mA minimum load current 0 5 A maximum output current or 1 3 A at 25 duty cycle or Maximum 6 cycles per hour with M9220 BGx 3 C OCOM n The signal common for...

Страница 7: ...on network RJ 12 6 position modular connector 30 5 m 100 ft maximum length phone cord SA Bus1 2 COM Provides SA Bus communication network Daisy chained 366 m 1 200 ft maximum length 0 6 to 1 5 mm 18 t...

Страница 8: ...ons Table 2 Wire Gauge and Length Guidelines Guideline Cable Size Maximum Length Assumptions A 1 5 mm 18 AWG 457 2 m 1 500 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 297 2 m 975 ft 0 6 mm 22 AWG 182...

Страница 9: ...the Binary Outputs and power must come from one or more external sources Do not wire the load directly to the OUTx and COMx terminals Wire one side of the load to the source and the other side of the...

Страница 10: ...Steady Power is supplied by primary voltage Fault Red Off Steady Blink 2 Hz Download or startup in progress not ready for normal operation Off Steady No faults On Steady Device fault or no application...

Страница 11: ...olution and 200 mV in 0 10 VDC applications Mounting On flat surface with screws on three mounting clips or a single 35 mm DIN rail Dimensions Height x Width x Depth 180 x 127 x 58 7 1 16 x 5 x 2 1 4...

Страница 12: ...odule Installation Instructions 12 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2010 Johnson Controls...

Отзывы: