Figure 6: Pin number assignments for sensor, SA bus

and FC bus ports on expansion modules

Supply power terminal block

The 24 VAC supply power terminal block is a gray,

removable, 3-terminal plug that fits into a board-mounted

jack on the top right of the expansion module.
Wire the 24 VAC supply power wires from the transformer

to the HOT and COM terminals on the terminal plug as

shown in Figure 7. The middle terminal on the supply

power terminal block is not used.

Figure 7: 24 VAC supply power terminal block wiring

Note: 

The supply power wire colors may be different

on transformers from other manufacturers. Refer to

the transformer manufacturer’s instructions and the

project installation drawings for wiring details.

Important: 

Connect 24 VAC supply power to the

expansion module and all other network devices

so that transformer phasing is uniform across the

network devices. Powering network devices with

uniform 24 VAC supply power phasing reduces

noise, interference, and ground loop problems. The

expansion module does not require an earth ground

connection.

Wireless network applications

About this task:

The expansion module can also be installed in a wireless

application using a ZFR/ZFR Pro Wireless Field Bus Router.

To configure an expansion module for use with the ZFR/

ZFR Pro Series Wireless Field Bus system:

Note: 

IOMs can communicate wirelessly on the FC

bus only.

1. Connect the ZFR181x or ZFR182x Wireless

Field Bus Router to the FC bus port (RJ-12

modular jack) on the front of the expansion

module.

2. Ensure that the expansion module's device

address DIP switches are set to the correct

device address. See .

3. Set DIP switch 128 to ON, which enables

wireless operation on the expansion module.

Result:

For more information on the ZFR Pro Wireless Field Bus

system, refer to the 

WNC1800/ZFR182x Pro Series Wireless

Field Bus System Product Bulletin (LIT-12012320)

.

For more information on the ZFR 1800 Wireless Field

Bus system, refer to the 

ZFR1800 Series Wireless Field Bus

System Product Bulletin (LIT-12011336)

.

Terminal Wiring Guidelines,

Functions, Ratings, and

Requirements

Input and output wiring guidelines

Table 2 provides information and guidelines about the

functions, ratings, and requirements for the expansion

module input and output terminals, and references

guidelines for determining proper wire sizes and cable

lengths.
In addition to the wiring guidelines in Table 2, observe

the following guidelines when wiring expansion module

inputs and outputs:
• Run 

all

 low-voltage wiring and cables separate from

high-voltage wiring.

• All input and output cables, regardless of wire size or

number of wires, should consist of stranded, insulated,

and twisted copper wires.

• Shielded cable is not required for input or output

cables.

• Shielded cable is recommended for input and output

cables that are exposed to high electromagnetic or

radio frequency noise.

• Inputs/outputs with cables less than 30 m (100 ft)

typically do not require an offset in the software setup.

Cable-runs over 30 m (100 ft) may require an offset in

the input/output software setup.

IOM2721 Input/Output Module Installation Guide

5

Содержание IOM2721

Страница 1: ...equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operatio...

Страница 2: ...applications Use shims or washers to mount the expansion module securely and evenly on the mounting surface Mount the expansion module in an area free of corrosive vapors and observe the Ambient Cond...

Страница 3: ...or surface in a proper mount position and mark the hole locations through the mounting clips 3 Drill holes in the wall or surface at the marked locations and insert appropriate wall anchors in the ho...

Страница 4: ...terminal blocks are mounted on the top of the expansion module SA FC bus terminal block An IOM can be connected to a Sensor Actuator SA bus or a Field Controller FC bus but not to both buses simultan...

Страница 5: ...us port RJ 12 modular jack on the front of the expansion module 2 Ensure that the expansion module s device address DIP switches are set to the correct device address See 3 Set DIP switch 128 to ON wh...

Страница 6: ...inum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10k Type L 10k JCI Type II 2 252k Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1...

Страница 7: ...re See Figure 8 to determine cable length Use twisted wire cable N A Maximum cable length versus load current Use the following figure to estimate the maximum cable length relative to the wire size an...

Страница 8: ...upply 15 VDC The SA bus supervisor supplies 15 VDC to devices on the SA bus requiring power FC Bus 0 6 mm 22 AWG stranded 3 wire twisted shielded cable required SA Bus 0 6 mm 22 AWG stranded 4 wire 2...

Страница 9: ...applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Interna...

Страница 10: ...grams Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI Dry Contact Binary Input UI 0 10 VDC Output to Actuator External Source AO 0 10 VDC Out...

Страница 11: ...pansion module on the bus You set an expansion module s device address by setting the positions of the switches on the DIP switch block at the top of the expansion module Device addresses 4 through 12...

Страница 12: ...e on Descriptions 0 Switch 128 Off Reserved for FC Bus Supervisory Controller not for use on controllers or expansion modules 1 3 Switch 128 Off Reserved for peripheral devices not for use on controll...

Страница 13: ...er to the expansion module is interrupted or off Figure 12 Current loop jumper positions Setting the current loop jumper to the Enabled position Figure 12 connects an internal 100 ohm resistor across...

Страница 14: ...tartup in progress not ready for normal operation SA FC BUS Green Blink 2 Hz Blink 2 Hz Data Transmission normal communication Off Steady No Data Transmission N A auto baud not supported On Steady Com...

Страница 15: ...k of 10 Note These terminal blocks can be used as replacement parts if keeping consistent terminal block colors is important AP TBK3PW 0 Replacement Power Terminal Blocks 3 Position Gray Bulk Pack of...

Страница 16: ...w Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting clips on expansion module Housing Enclosure material ABS and...

Страница 17: ...C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 5...

Страница 18: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Отзывы: