Johnson Controls, Inc. SLC Wiring Manual —
P/N 51870:G 04/23/2009
Control Modules
Connecting a Releasing Device to the Addressable Control Module
4.
Do not loop wiring under the screw terminals. Break the wire run to provide supervision of
connections.
5.
All applications using the M300CJ-REL are power-limited:
a.
Program the releasing circuit for Type Code REL CKT ULC or RELEASE CKT.
b.
Circuits are supervised against opens and shorts.
6.
Refer to your FACP’s
Programming Manual
for instructions on setting the Soak Timer.
The M300CJ-REL module must be programmed with the correct releasing type code listed in your
FACP’s
Programming Manual
.