• Temporal three fire signal (if enabled)
• All audible burglary and fire alarms by partition
• Bell cut-off time
• Bell squawk conditions
• Audible exit fault
This output activates when the alarm output is active and turns off when the alarm output is
silenced. The siren pattern matches the programmed cadence for the zone that went into alarm.
Cadence priority is as follows:
• fire alarm cadence
• CO alarm cadence
• other alarm cadences
The main siren still activates for all alarms.
102 - Delayed Fire and Burglary
This output type operates the same as the Burglary and Fire Bell Follower (PGM type 01), but does
not activate until the transmission delay time expires.
When a zone with transmission delay enabled is tripped, the Bell, Regular Fire and Burglary PGMs
activate. At the end of the transmission delay, the delayed Fire and Burglary output activates.
This PGM is usually used to control outdoor sirens. If a false alarm occurs, the user has time to
disarm the system before the external sirens activate.
Note:
If a zone alarm occurs but does not follow transmission delay, this PGM activates
immediately, even if transmission delay is active for a different zone alarm.
This output activates for audible exit fault and does not interfere with the operation of any other
programmable output.
103 - Sensor Reset [*][7][2]
This output is normally active and deactivates for 5 seconds when a [*][7][2] fire reset command
is entered or when an auto verified fire alarm is detected. This option is used to reset power for
latching smoke detectors. The keypad buzzer does not sound for the 5-second period.
for instructions on wiring smoke detectors.
104 - 2-Wire Smoke
When this PGM is programmed, the onboard PGM functions as an input instead of an output. 2-
wire smoke detectors can be connected to this input, which means that a zone input does not need
to be used.
The PGM is also supervised, and a trouble condition is generated if a 2.2KΩ resistor is not present
between the PGM terminal and Aux+.
The 2-wire smoke detector input creates an instant and latching alarm.
109 - Courtesy Pulse
Courtesy pulse causes an output to activate for the entry and exit times, plus 2 minutes. This option
is typically used to activate a courtesy light near the exit door for the duration of the entry/exit
times.
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual
94