Automatic Clock Adjust
This value adds or subtracts seconds from the system clock at the end of each day to compensate
for inaccuracies. To determine the adjustment value, monitor the time lost or gained by the alarm
system over a period of time and calculate the average gains or loses.
Example #1: The clock loses an average of 9 seconds per day. Program the alarm controller to
adjust the clock by 51 seconds for the last minute of each day. This speeds up the alarm controller’s
clock by 9 seconds, correcting the problem.
Example #2: The clock gains an average of 11 seconds per day. Program the alarm controller
to adjust the clock by 71 seconds for the last minute of each day. This slows down the alarm
controller’s clock by 11 seconds, correcting the problem.
If the Auto-arm time is set for 23:59, any change to the Clock Adjust option will directly affect the
Auto-arm pre-alert time.
[001]-[008] Partition 1-8 Timers
The following timers can be applied to each partition.
Note:
For UL installations, the Entry Delay plus the Communications Delay must not exceed 60
seconds.
Entry Delay 1:
This value determines the entry delay time for delay 1 type zones. Valid entries are 001 to 255
seconds.
Entry Delay 2:
This value determines the entry delay time for delay 2 type zones. Valid entries are 001 to 255
seconds.
Note:
The system follows the entry timer that activates first.
Exit Delay:
This value determines the exit delay time when arming the system. During exit delay, both the
Ready and Armed LEDs are on. When the exit delay expires, both LEDs turn off.
Note:
European products will only activate the armed LED at the end of exit delay.
Settle Delay:
This timer enables a programmable, short duration bypass of all zones on the partition at the time
of arming. It allows motion detectors to restore when the system is armed to help prevent false
alarms.
The typical value for this timer is 5 seconds, but can be increased if false alarms persist. Program
000 for no settle delay.
The settle delay duration is programmed in seconds. Valid entries are 000 to 010 seconds.
[900] – Bell Delay Partition Mask
This option enables or disables the Bell Delay feature for individual partitions. When the option is
enabled, Bell Delay is applied to the selected partition during alarm conditions. When the option is
disabled, Bell Delay is not applied. The default setting is (Y): enabled.
[901]/[902] – Daylight Savings Begin/End
Daylight Begin [001] and Daylight End [002]:
Set the date and time daylight savings starts and ends.