Hx-68P3 Series Outside Humidity and Temperature Transmitters Installation Instructions

6

6. Secure the cable to the wall using cable ties. 

Incorporate a drip loop below the cable gland to 
prevent water from running into the transmitter 
along the cable.

 Wiring

     

   

Calibration

There are no calibration adjustments to make for this 
device.

Troubleshooting

Analog Output Error State

The output channel is in a defined error level instead of 
the measured result in two situations.

The transmitter detects a measurement 
malfunction such as a damaged sensor or 
unfavorable environmental conditions.

The measured values are outside of the scaled 
output range. See 

Analog Output Overrange 

Behavior

.

The error level depends on the output type.

For a 0 to 10 V output, the error level is 11 V.

For a 4 to 20 mA output, the error level is 3.6 mA.

The transmitter resumes normal operation of the 
analog outputs when the cause of the error state is 
removed.

Analog Output Overrange Behavior

The Analog outputs have a defined behavior when the 
values measure by the transmitter are outside the 
scaled analog output range.

The output is clipped at the end of the range.

The output is set to the error state when the 
measured value is 5% outside of the scaled range.

The output resumes normal function when the 
measured value is back on the scaled range.

Repair Information

If the Hx-68P3 Series Outside Humidity and 
Temperature Transmitter fails to operate within its 
specifications, replace the unit. For a replacement 
transmitter, contact the nearest Johnson Controls® 
representative.

!

CAUTION: Risk of Electric Shock.

Disconnect the power supply before 
making electrical connections to avoid 
electric shock.

MISE EN GARDE : Risque de décharge 
électrique.

Débrancher l'alimentation avant de 
réaliser tout raccordement électrique afin 
d'éviter tout risque de décharge 
électrique.

Figure 9: Securing Cable on a Wall

FI

G

:Ca

bl

e W

a

ll

Figure 10: HT-68P3-0N000 Wiring

Two 4 to 20 mA outputs, 
temperature output scaling -40 
to 140°F (-40 to 60°C)

Alternate wiring with one 
power supply.

 
1
2
3
4

mA

mA

mA

mA

HUM+
HUM-
T+
T-

HUM+
HUM-
T+
T-

+

+

+

 
1
2
3
4

F

IG:

HT

-6

8

0

3

-0

N0

0

Figure 11: HE-68P3-0N000 Wiring

 
1
2
3
4
5

VDC+/AC
VDC-/AC
T+

T-/

HUM+

HUM-

+

+

V

 
1
2
3
4
5

 
1
2
3
4
5

 
1
2
3
4
5

V

V

V

VDC+/AC
VDC-/AC
T+

T-/

HUM+

HUM-

Two 0 to 10 V outputs, 
temperature output scaling 
-40 to 140°F (-40 to 60°C)

Terminals 2 and 5 are 
internally connected on the 
transmitter, so you can use 
a cable with four wires.

Содержание H -68P3 Series

Страница 1: ...dans des conditions normales de fonctionnement Lorsqu une d faillance ou un dysfonctionnement du humidity and temperature transmitter risque de provoquer des blessures ou d endommager l quipement con...

Страница 2: ...ation instructions Tools Needed medium Phillips screwdriver small slotted screwdriver wire cutters open ended wrench zip ties cable clips Figure 1 Hx 68P3 Series Outside Humidity and Temperature Trans...

Страница 3: ...d Temperature Transmitter Dimensions in mm 4 7 8 122 10 3 8 264 FIG Dimensions Cable Gland Suitable for 5 32 to 5 16 4 to 8 Cable Diameter 3 32 to 2 11 32 25 to 60 Diameter 7 32 6 Figure 3 DIP Switch...

Страница 4: ...sources such as cooling towers Install the transmitter at least 8 ft 2 5 m above the ground 1 Loosen the six captive screws that hold the transmitter cover in place 2 Be sure the DIP switches are set...

Страница 5: ...the cover screws See Figure 5 for plugging in the terminal block and attaching the cover 5 Secure the cable to the pole using cable ties Incorporate a drip loop below the cable gland to prevent water...

Страница 6: ...tput is clipped at the end of the range The output is set to the error state when the measured value is 5 outside of the scaled range The output resumes normal function when the measured value is back...

Страница 7: ...tability in typical HVAC app 2 RH over 2 years Temperature Measurement range 40 to 140 F 40 to 60 C Accuracy at 68 F 20 C 0 54 F 0 3 C Temperature dependance 0 01 C C Temperature sensor Pt1000 RTD Cla...

Страница 8: ...s in compliance with the essential requirements and other relevant provisions of the EMC Directive Australia and New Zealand RCM Mark Australia NZ Emissions Compliant The performance specifications ar...

Отзывы: