Figure 1: G670 Intermittent Pilot Ignition Control
The G670 is a Non-100% Lockout Intermittent Pilot Ignition (IPI) control
that replaces the G67AG and G67BG ignition controls. The G670 is used to
automatically light a pilot burner and energize the main burner gas valve in
response to a call for heat from the system thermostat. When the call for heat
is satisfied, the thermostat opens and the G670 de-energizes the pilot and
main burner gas valves.
Following are the application requirements of the G670 control.
•
The G670 can be used with equipment with a maximum firing rate of
117 kW (400,000 Btu/hr). Any application greater than 117 kW
(400,000 Btu/hr) must have written approval in advance from the
Heating Products Engineering Department.
•
All G670 applications must use a redundant gas valve system with the
main valve seats in series.