Do not mount the controller on surfaces prone to
vibration, such as duct work.

Do not mount the controller in areas where
electromagnetic emissions from other devices or
wiring can interfere with controller communication.

Observe these additional guidelines when mounting an
FX-PCX47 controller in a panel or enclosure:

Mount the controller so that the enclosure walls do
not obstruct cover removal or ventilation through the
controller.

Mount the controller so that the power transformer
and other devices do not radiate excessive heat to
the controller.

Do not install the controller in an airtight enclosure.

Figure 1: Controller Mounting Positions

DIN Rail Mount Applications

Mounting the controller horizontal on 35 mm DIN rail is
the preferred mounting method.

To mount an FX-PCX47 controller on 35 mm DIN rail:

1. Securely mount a 20 cm (8 in.) or longer section of

35 mm DIN rail horizontal and centered in the desired
space so that the controller mounts in the horizontal
position shown in

Figure 1

.

2. Pull the two bottom mounting clips outward from the

controller to the extended position (

Figure 2

).

3. Hang the controller on the DIN rail by the hooks at

the top of the (DIN rail) channel on the back of the
controller (

Figure 2

), and position the controller snugly

against the DIN rail.

4. Push the bottom mounting clips inward (up) to secure

the controller on the DIN rail.

To remove the controller from the DIN rail, pull the
bottom mounting clips out to the extended position
and carefully lift the controller off the DIN rail.

Wall Mount Applications

To mount a controller directly on a wall or other flat
vertical surface:

1. Pull the two bottom mounting clips outward and

ensure they are locked in the extended position as
shown in

Figure 2

.

2. Mark the mounting hole locations on the wall using

the dimensions in

Figure 2

and one of the mount

positions shown in

Figure 1

Or, hold the controller

up to the wall or surface in a proper mount position
and mark the hole locations through the mounting
clips.

3. Drill holes in the wall or surface at the marked

locations, and insert appropriate wall anchors in the
holes (if necessary).

4. Hold the controller in place, and insert the screws

through the mounting clips and into the holes (or
anchors). Carefully tighten all of the screws.

Important:

Do not overtighten the mounting screws.
Overtightening the screws may damage
the mounting clips.

Figure 2: Back of Controller Showing Extended

Mounting Clips, DIN Rail Channel, and Mounting

Dimensions, mm (in.)

2

FX-PCX47 Expansion Input/Output Module Installation Instructions

Содержание FX-PCX47

Страница 1: ...nstalled and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in w...

Страница 2: ...rail channel on the back of the controller Figure 2 and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To remov...

Страница 3: ...le 5 6 Cover Lift Tab One of Two See Removing the Controller Cover 7 Sensor Actuator SA Bus or Field Controller FC Bus Terminal Block See Table 5 8 Binary Input BI Terminal Block 2 Binary Inputs See T...

Страница 4: ...figuring and wiring an MS TP Bus FC bus and SA bus refer to the FX PC Series Controllers MS TP Communications Bus Technical Bulletin LIT 12011670 or MS TP Communications Bus for BCM System Technical B...

Страница 5: ...on the top right of the controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in Figure 7 The middle terminal on the supply powe...

Страница 6: ...o the FX ZFR1811 Wireless Field Bus Router Installation Instructions Part No 24 10325 29 Termination Details A set of Johnson Controls termination diagrams provides details for wiring inputs and outpu...

Страница 7: ...rrent Input Internal Source 2 wire UI Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI or BI Dry Contact Binary Input CO or AO 0 20 VDC Output...

Страница 8: ...CO or AO 0 10 VDC Output to Actuator Internal Source CO or AO 4 20 mA Output to Actuator CO or AO 4 20 mA Output to Actuator AO Voltage Analog Output AO Analog Output Current CO 24 VAC Triac Output Sw...

Страница 9: ...24 VAC Triac Output Switch High Externally Sourced CO Incremental Control to Actuator Switch High Externally Sourced BO Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary...

Страница 10: ...e BO Incremental Control to Actuator Switch High Externally Sourced SA Bus Network Stat with Phone Jack Fixed Address 199 SA Bus Network Stat with Terminals Addressable SA Bus Network Stat with Termin...

Страница 11: ...rminal Label Terminal Block Label Same as Universal INn Note Use 3 wire cable for devices that source power from the 15V terminal 15 VDC Power Source for active 3 wire input devices connected to the U...

Страница 12: ...greater than 1 000 ohm Devices that drop below 1 000 ohm may not operate as intended for Voltage Mode applications OUTn ANALOG Outputs Analog Output Current Mode 4 20 mA Requires and external load be...

Страница 13: ...imum output voltage 10 mA maximum output current Required an external load of 1 000 ohm or more OUTn CONFIGURABLE Outputs See Guideline C in Table 4 Binary Output 24 VAC Triac External Power Source on...

Страница 14: ...per 100 mV maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or output point 229 m 750 ft twisted wi...

Страница 15: ...cable recommended Note On the SA Bus the and wire are one twisted pair and the COM and SA PWR are the second twisted pair of wires FC or SA Bus Communications FC BUS 2 or SA BUS 2 Signal Reference Co...

Страница 16: ...itch 4 ON followed by switch 1 16 4 1 21 See Figure 9 3 Set switch 128 to ON only for controllers on an FX ZFR Series Wireless Field Bus application For all hard wired SA and FC bus applications ensur...

Страница 17: ...under the two cover lift tabs Figure 3 on the sides of the housing cover and gently pry the top of the cover away from the base to release the cover from the two upper latches 2 Pivot the top of the...

Страница 18: ...Jumpers The current loop fail safe jumpers are on the circuit board under the controller cover near the UI terminals Figure 10 When a UI is defined in the system software as a 4 20 mA Analog Input and...

Страница 19: ...For a replacement controller contact your Johnson Controls representative Accessories See Table 9 for controller accessories ordering information Table 9 Accessories Ordering Information Description...

Страница 20: ...FX PCG FX PCA FX PCX and FX PCV field controllers Also allows use of the FX ZFR Checkout Tool FX ZCT in FX PCT Note The ZFR USBHA 0 replaces the IA OEM DAUBI_2400 ZigBee USB dongle For additional inf...

Страница 21: ...28 KB Random Access Memory RAM Memory 6 Universal Inputs Defined as 0 10 VDC 4 20 mA 0 600k ohm or Binary Dry Contact 2 Binary Inputs Defined as Dry Contact Maintained or Pulse Counter Accumulator Mod...

Страница 22: ...erformance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls I...

Отзывы: