Table 6: SA/FC Bus Device Address Descriptions

Use on Description

Device
Address

Reserved addresses for wired slave devices
(not for use on controllers).

Note:

FX-PCX controllers ship with switch 128

ON and the remaining address switches off
rendering the controllers wired slave devices,
which do not operate on MS/TP buses.

0 to 3

(Switch
128 ON)

Valid for MS/TP Master controllers on

wireless

FC Buses only

.

Note:

Do

not

connect a controller with switch

128 ON to an active (

hard-wired

) SA or FC

Bus. When a controller with switch 128 ON
and a device address from 4 to 127 is
connected to a wired field bus, the entire field
bus is rendered inoperable until the controller
is disconnected or switch 128 is set to Off.

4 to 127

(Switch
128 ON)

Removing the Controller Cover

Important:

Electrostatic discharge can damage
controller components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.

Important:

Disconnect all power sources to the
controller before removing cover and
changing the position of any jumper or the
EOL switch on the controller. Failure to
disconnect power before changing a jumper
or EOL switch position can result in damage
to the controller and void any warranties.

The controller cover is held in place by four plastic latches
that extend from the base and snap into slots on the
inside of the housing cover.

To remove the controller cover:

1. Place your fingernails under the two cover lift tabs

(

Figure 3

on the sides of the housing cover and

gently pry the top of the cover away from the base to
release the cover from the two upper latches.

2. Pivot the top of the cover further to release it from the

lower two latches.

3. Replace the cover by placing it squarely over the

base, and then gently and evenly push the cover on
to the latches until they snap into the latched position.

Figure 10: FX-PCX47 with Cover Removed Showing

EOL Switch and Jumper Positions

Setting the End-of-Line (EOL) Switch

Each controller has an EOL switch, which, when set to
ON, sets the controller as a terminating device on the
bus. See

Figure 10

for the EOL switch location. The

default EOL switch position is Off.

Figure 11: End-of-Line Switch Positions

To set the EOL switch on a controller:

1. Determine the physical location of the controller on

the SA or FC bus.

2. Determine if the controller must be set as a

terminating device on the bus.

Note:

The EOL termination rules for SA buses and
FC buses are different. Refer to the

FX-PC

Series Controllers MS/TP Communications
Bus Technical Bulletin (LIT-12011670)

or

MS/TP Communications Bus for BCM System
Technical Bulletin (LIT-12011908)

for detailed

information regarding EOL termination rules
and EOL switch settings on SA and FC buses.

3. If the controller is a terminating device on the FC bus,

set the EOL switch to ON. If the controller is not a
terminating device on the bus, set the EOL switch to
Off.

When a controller is connected to power with its EOL
switch set to ON, the amber EOL LED on the
controller cover is lit.

17

FX-PCX47 Expansion Input/Output Module Installation Instructions

Содержание FX-PCX47

Страница 1: ...nstalled and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in w...

Страница 2: ...rail channel on the back of the controller Figure 2 and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To remov...

Страница 3: ...le 5 6 Cover Lift Tab One of Two See Removing the Controller Cover 7 Sensor Actuator SA Bus or Field Controller FC Bus Terminal Block See Table 5 8 Binary Input BI Terminal Block 2 Binary Inputs See T...

Страница 4: ...figuring and wiring an MS TP Bus FC bus and SA bus refer to the FX PC Series Controllers MS TP Communications Bus Technical Bulletin LIT 12011670 or MS TP Communications Bus for BCM System Technical B...

Страница 5: ...on the top right of the controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in Figure 7 The middle terminal on the supply powe...

Страница 6: ...o the FX ZFR1811 Wireless Field Bus Router Installation Instructions Part No 24 10325 29 Termination Details A set of Johnson Controls termination diagrams provides details for wiring inputs and outpu...

Страница 7: ...rrent Input Internal Source 2 wire UI Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI or BI Dry Contact Binary Input CO or AO 0 20 VDC Output...

Страница 8: ...CO or AO 0 10 VDC Output to Actuator Internal Source CO or AO 4 20 mA Output to Actuator CO or AO 4 20 mA Output to Actuator AO Voltage Analog Output AO Analog Output Current CO 24 VAC Triac Output Sw...

Страница 9: ...24 VAC Triac Output Switch High Externally Sourced CO Incremental Control to Actuator Switch High Externally Sourced BO Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary...

Страница 10: ...e BO Incremental Control to Actuator Switch High Externally Sourced SA Bus Network Stat with Phone Jack Fixed Address 199 SA Bus Network Stat with Terminals Addressable SA Bus Network Stat with Termin...

Страница 11: ...rminal Label Terminal Block Label Same as Universal INn Note Use 3 wire cable for devices that source power from the 15V terminal 15 VDC Power Source for active 3 wire input devices connected to the U...

Страница 12: ...greater than 1 000 ohm Devices that drop below 1 000 ohm may not operate as intended for Voltage Mode applications OUTn ANALOG Outputs Analog Output Current Mode 4 20 mA Requires and external load be...

Страница 13: ...imum output voltage 10 mA maximum output current Required an external load of 1 000 ohm or more OUTn CONFIGURABLE Outputs See Guideline C in Table 4 Binary Output 24 VAC Triac External Power Source on...

Страница 14: ...per 100 mV maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or output point 229 m 750 ft twisted wi...

Страница 15: ...cable recommended Note On the SA Bus the and wire are one twisted pair and the COM and SA PWR are the second twisted pair of wires FC or SA Bus Communications FC BUS 2 or SA BUS 2 Signal Reference Co...

Страница 16: ...itch 4 ON followed by switch 1 16 4 1 21 See Figure 9 3 Set switch 128 to ON only for controllers on an FX ZFR Series Wireless Field Bus application For all hard wired SA and FC bus applications ensur...

Страница 17: ...under the two cover lift tabs Figure 3 on the sides of the housing cover and gently pry the top of the cover away from the base to release the cover from the two upper latches 2 Pivot the top of the...

Страница 18: ...Jumpers The current loop fail safe jumpers are on the circuit board under the controller cover near the UI terminals Figure 10 When a UI is defined in the system software as a 4 20 mA Analog Input and...

Страница 19: ...For a replacement controller contact your Johnson Controls representative Accessories See Table 9 for controller accessories ordering information Table 9 Accessories Ordering Information Description...

Страница 20: ...FX PCG FX PCA FX PCX and FX PCV field controllers Also allows use of the FX ZFR Checkout Tool FX ZCT in FX PCT Note The ZFR USBHA 0 replaces the IA OEM DAUBI_2400 ZigBee USB dongle For additional inf...

Страница 21: ...28 KB Random Access Memory RAM Memory 6 Universal Inputs Defined as 0 10 VDC 4 20 mA 0 600k ohm or Binary Dry Contact 2 Binary Inputs Defined as Dry Contact Maintained or Pulse Counter Accumulator Mod...

Страница 22: ...erformance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls I...

Отзывы: