Note:
If temporary occupancy is required for the application on the TE-67xx and TE-68xx Series
Sensors, set the DIP switch positions on the back of the sensor to down, up, and down. This
setting only applies to single and no setpoint controller models (not dual setpoint controller
models).
Refer to the
NS Series Network Sensors Product Bulletin (LIT-12011574)
for a complete list of available
NS Series Network Sensors.
Note:
In each of the following procedures that include the use of the Commissioning
Converter (BTCVT), note the following: The Mobile Access Portal (MAP) Gateway serves as a
replacement for the BTCVT, which is no longer available for purchase, but continues to be
supported on select controllers. CCT auto-detects when BTCVT can be used or not, based on
the controller model and the corresponding CCT Release mode.
Replacing a TE-6xxx series sensor
To replace a TE-6xxx Series Sensor with a functionally equivalent NS Series Network Sensor,
complete the following instructions.
Note:
• Replacing a TE-6xxx Series Sensor is recommended over reusing the sensor.
• When replacing a TE-6xxx Series sensor with an NS Series sensor and dissimilar paint or wall
covering is visible outside of the new sensor, consider using the NS-WALLPLATE-0 for the new NS
sensor. See Table 8 for more information.
1. Remove the TE-6xxx Series Sensor from the wall and disconnect the 8-pin male jack from the
back of the sensor.
2. Plug the 8-pin male jack that was plugged into the back of the sensor into the 8-pin female
socket on the single-socket adapter (Figure 9) provided with the FX-PCV18 controller.
3. Plug the 6-pin male jack on the single socket adapter into the modular jack connection on the
NS Series Network Sensor.
4. Mount the NS Series Network Sensor in the same location the TE-6xxx Series Sensor was
previously mounted, concealing the adapter assembly in the existing wall opening behind the
sensor. Refer to the installation instructions for the applicable NS Series Sensor model.
5. Plug the BTCVT into the 6-pin socket on the NS Series Network Sensor.
Note:
When using an NS Series Network Sensor with screw terminal block terminations, see
the wiring diagram in the installation instructions for the applicable NS Series Sensor model.
Figure 9: Single-Socket Adapter
FX-PCV1826/1832 Programmable VAV Box Controller Installation Instructions
16