Table 8: FX-PCV accessories (order separately)
Product code number
Description
AP-TBK4SA-0
Replacement MS/TP SA Bus Terminal, 4-Position Connector, Brown (Bulk
Pack of 10)
AP-TBK4FC-0
Replacement MS/TP FC Bus Terminal, 4-Position Connector, Blue (Bulk
Pack of 10)
AP-TBK3PW-0
Replacement Power Terminal, 3-Position Connector, Gray (Bulk Pack of
10)
TL-BRTRP-0
BACnet IP to MS/TP Router for Connecting a Computer with CCT to MS/
TP Field Controllers
FX-BTCVTCBL-700
Cable Replacement Set for the FX-BTCVT-1 or the FX-ATV7003-0; Includes
One 5 ft (1.5 m) Retractable Cable
NS Series Sensors
NS Series Network Sensors: Refer to the
NS Series Network Sensors
Product Bulletin (LIT-12011574)
for specific sensor model descriptions
Technical specifications
Table 9: FX-PCV16 Controllers
Product Code
Numbers
FX-PCV1610-0U
: 1 UI FX-PCV (Cooling Only)
FX-PCV1610-1U
: 1 UI FX-PCV (Cooling Only)
FX-PCV1620-0U
: 1 UI, 3 BO, 2 CO FX-PCV (Cooling with Reheat and Fan
Control)
Note:
FX-PCV1620-1U
: 1 UI, 3 BO, 2 CO FX-PCV (Cooling with
Reheat and Fan Control)Only -xU models of these controllers are
available. These models are for smoke control applications only.
If your application is not for a UL 864 UUKL 10th Edition smoke
control application, please review the product selection before
installation.
Supply Voltage
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power
supply Class 2 (North America), Safety Extra-Low Voltage (SELV) (Europe)
Power Consumption
10 VA typical, 14 VA maximum
Note:
VA rating does
not
include any power supplied to the
peripheral devices connected to Binary Outputs (BOs) or
Configurable Outputs (COs), which can consume up to 12 VA for
each BO or CO for a possible total consumption of an additional 60
VA (maximum).
Ambient Conditions
Operating:
0°C to 50°C (32°F to 122°F)
Storage:
-40°C to 70°C (-40°F to 158°F)
Terminations
Inputs/Outputs: 6.3 mm (1/4 in.) spade lugs
FC Bus, SA Bus, and Supply Power: 4-Wire and 3-Wire Pluggable Screw
Terminal Blocks
Sensor Port: RJ-12 6-Pin Modular Jacks