070.250-IOM (APR 11)

Page 6

408 MM ROTARY SCREW COMPRESSOR

INSTALLATION - OPERATION - MAINTENANCE

compressor  Vi.  Both  are  hydraulically  controlled  through 
the  solenoid  valves  located  on  the  compressor  cylinder 
housing.

Proper operation of the 408 mm compressor slide valve and 
slide stop require the use of a pump to boost oil pressure 
above discharge pressure.

Oil from the pump is piped to the SC-13 port located on the 
solenoid block which is mounted on the compressor cylinder 
housing.  The  cylinder  oil  booster  pump  pressure  shall  be 
regulated to maintain a minimum 40 PSID oil pressure boost 
above discharge pressure.

Refer  to  CES  6606  for  basic  oil  pump  requirements  and 
basic piping diagrams. Actual system operating conditions 
may  necessitate  the  need  for  piping  systems  other  than 
those addressed by CES 6606. Contact Johnson Controls-
FRICk Service for assistance. 

DEMAND OIL PUMP

A demand oil pump is required for low differential pressure 
applications (CoolWare

 will provide a warning when the oil 

differential  pressure  is  too  low).  Oil  being  supplied  to  the 
compressor  from  the  oil  separator  is  at  system  discharge 
pressure.  Within  the  compressor,  oil  porting  to  all  parts  of 
the  compressor  is  vented  back  to  a  location  in  the 
compressor’s  body  that  is  at  a  pressure  lower  than 
compressor  discharge  pressure.  All  oil  entering  the 
compressor  is  moved  by  the  compressor  rotors  out  the 
compressor outlet and back to the system oil separator. 

 

CONSTRUCTION DETAILS

HOUSING: 

All  408  mm  screw  compressor  castings  are 

ductile  iron  to  ensure  structural  integrity  and  mechanical 
and  thermal  stability  under  all  operating  conditions.  Steel 
housings are also available for special applications. Contact 
Johnson Controls–Frick Sales for additional information.

ROTORS: 

The rotors are machined from AISI-1141 steel to 

the exacting tolerances of the latest Frick profile. The five-
lobed  male  rotor  is  directly  connected  to  the  driver.  The 
seven-lobed female rotor is driven by the male on a thin oil 
film.

BEARINGS: 

Antifriction  bearings  are  used  for  reduced 

frictional  horsepower  and  superior  rotor  positioning, 
resulting  in  reduced  power  consumption,  particularly  at 
higher  pressure  ratios.  Cylindrical  roller  bearings  are 
provided to handle the radial loads and the thrust loads are 
absorbed  by  angular  contact  bearings.  In  addition,  thrust 
balance pistons are provided to reduce the thrust load and 
improve bearing life.

SHAFT  SEAL: 

The  compressor  shaft  seal  is  a  single-face 

type with a spring-loaded carbon stationary surface riding 

against a stainless steel rotating seat. The seal is capable of 
withstanding  static  pressure  up  to  600  psig.  During 
operation it is vented to low pressure to provide extended 
life.

VOLUMIZER  VARIABLE  VOLUME  RATIO  CONTROL: 

The 

Frick compressor includes a method of varying the internal 
volume ratio to match the system pressure ratio. Control of 
the  internal  volume  ratio  eliminates  the  power  penalty 
associated with over- or under-compression. Volume ratio 
control  is  achieved  by  the  use  of  a  slide  stop  which  is  a 
movable portion of the rotor housing that moves axially with 
the rotors to control discharge port location. The slide stop 
is moved by hydraulic actuation of a control piston. 

STEPLESS  CAPACITY  CONTROL: 

Capacity  control  is 

achieved by use of a movable slide valve. The slide valve 
moves axially under the rotors to provide fully modulated 
capacity  control  from  100%  to  minimum  load  capacity. 
Minimum  load  capacity  varies  slightly  with  compressor 
model, pressure ratio,  discharge pressure level, and rotor 
speed. 

The slide valve is positioned by hydraulic movement of its 

Содержание Frick 408L

Страница 1: ... COMPRESSOR MODELS 408S 408L 408XL THIS MANUAL CONTAINS RIGGING ASSEMBLY START UP AND MAINTENANCE INSTRUCTIONS READ THOROUGHLY BEFORE BEGINNING INSTALLATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN PERSONAL INJURY OR DEATH DAMAGE TO THE UNIT OR IMPROPER OPERATION Please check www jci com frick for the latest version of this publication ...

Страница 2: ...UP INSTRUCTIONS 16 COMPRESSOR HYDRAULIC SYSTEM 16 VOLUMIZER VOLUME RATIO CONTROL 16 LOW AMBIENT OPERATION 16 INITIAL START UP 16 INITIAL START UP PROCEDURE 17 NORMAL START UP PROCEDURE 17 MAINTENANCE GENERAL INFORMATION 18 NORMAL MAINTENANCE OPERATIONS 18 GENERAL MAINTENANCE 18 CHANGING OIL 18 RECOMMENDED MAINTENANCE PROGRAM 18 VIBRATION ANALYSIS 18 OIL QUALITY and ANALYSIS 19 OPERATING LOG 19 TRO...

Страница 3: ...ion of any moisture in the compressor and oil separator DESIGN LIMITATIONS Frick 408 mm compressors are designed for operation within the pressure and temperature limits which are specified by Johnson Controls Frick and our COOLWARE selection software They are primarily used for compressing refrigerant gas and most hydrocarbon gasses If your application is for sour gas there are special requiremen...

Страница 4: ...ermstorageofequipmentmayleadtothedeterioration of components over the period of time Synthetic components in the compressor may deteriorate over time even if they are kept flooded with oil A warm and dry environment is essential to minimize environmental and corrosion damage Long term storage of the affected equipment at a customer s site may involve additional requirements and interested parties ...

Страница 5: ...ing is designed to maintain operating pressure on seal well below discharge pressure for increased seal life 9 Oil injected into the rotors to maintain good volumetric and adiabatic efficiency even at very high compression ratios 10 Shaft rotation clockwise facing compressor suitable for all types of drives SEE FOLLOWING WARNING WARNING Compressor rotation is clockwise when facing the compressor d...

Страница 6: ...son Controls Frick Sales for additional information Rotors The rotors are machined from AISI 1141 steel to the exacting tolerances of the latest Frick profile The five lobed male rotor is directly connected to the driver The seven lobed female rotor is driven by the male on a thin oil film Bearings Antifriction bearings are used for reduced frictional horsepower and superior rotor positioning resu...

Страница 7: ...e models is provided below Please see CoolWare to determine the limits for a specific application The rotor and bearing design set limitations of the 408 mm compressors must not be exceeded See CoolWare Refer to Johnson Controls Frick Compressor Control Panel instruction 090 040 O for additional information on setpoint limits OUTLINE DIMENSIONS Drawings for reference only can be found on the follo...

Страница 8: ...070 250 IOM APR 11 Page 8 408 MM ROTARY SCREW COMPRESSOR INSTALLATION COMPRESSOR PORT LOCATIONS 408 MM A B A C C B SC 1 SC 3 SC 5 SC 7 SM 1 SC 9 SV 1 SC 9 ST 2 SC 6 ST 1 SC 10 SC 11 VIEW C C ...

Страница 9: ...500 B C MODEL PSI MAX P A B PSI MAX T V Hz Amps Hydraulic Valve Division Elyria Ohio 44036 2026 USA MODEL PSI MAX P A B PSI MAX T V Hz Hydraulic Valve Division Elyria Ohio 44036 2026 USA CAUTION REFER TO INSTALLATION OPERATION AND MAINTENANCE MANUAL FOR ADDITIONAL INFORMATION THIS EQUIPMENT HAS BEEN PRESSURIZED WITH NITROGEN GAS TEMPORARY VALVES AND GAUGES HAVE BEEN INSTALLED ESCAPING GAS MAY CAUS...

Страница 10: ...R 11 Page 10 408 MM ROTARY SCREW COMPRESSOR INSTALLATION COMPRESSOR PORT LOCATIONS 408 MM SL 2 SL 1 SC 3 SC 2 SC 14 SC 13 VIEW D D DISCHARGE 12 300 ANSI FLANGE 1 7 UNC 2B x 3 00 DP 16X ON 17 750 B C D D SC 4 SC 2 BP ...

Страница 11: ...M 12 UN 2B STRAIGHT THREAD 980A0012K72 CLOSED THREAD PRESSURE SC 10 1B 12 UN 2B STRAIGHT THREAD 980A0012K71 SLIDE VALVE TOOL DISCH PRESSURE SC 11 1B 12 UN 2B STRAIGHT THREAD 980A0012K71 DRAIN DISCHARGE PRESSURE SC 12 3 4 16 UNF 2B STRAIGHT THREAD 980A0012K62 DRAIN SUCTION PRESSURE SC 13 3 4 16 UNF 2B STRAIGHT THREAD 980A0012K62 CYLINDER OIL PRESSURE SC 14 3 4 16 UNF 2B STRAIGHT THREAD 980A0012K62 ...

Страница 12: ...roper spacing for servicing see Dimensional Outline Drawing The first requirement of the compressor foundation is that it must be able to support the weight 408S 13 960 lb 408L 15 580 lb 408XL 16 615 lb NOTICE Weights are for standard compressor in Ductile Iron Contact factory for weights of optional models Screw compressors are capable of converting large quantities of shaft power into gas compre...

Страница 13: ... MOTOR COUPLING REQUIREMENTS Frick 408 mm compressors are arranged for direct motor drive and require a flexible drive coupling to connect the compressor to the motor If you are using the Johnson Controls Frick motor mount the mount is machined to ensure that motor to compressor alignment is in specification see the above MOTOR MOUNTING section for mounting details With a foot mounted motor it is ...

Страница 14: ...Valve off the vacuum pump and hold vacuum for one hour Pass Vacuum cannot rise more than 500 microns during one hour hold period Fail Vacuum rise is more than 500 microns during one hour hold period Identify and repair any system leaks Repeat vacuum test until requirements are met ELECTRICAL INSTALLATION SLIDE STOP TRANSMITTER The slide stop transmitter Figure 5 measures the position of the slide ...

Страница 15: ...irectional control valves Solenoids YY1 YY2 YY3 and YY4 must be wired to give the correct function A description of their function is given in the OPERATION chapter For control system information refer to Frick Compressor Control Panel 090 020 O See wiring diagram in Figure 9 Figure 9 Directional Control Valve Wiring Diagram ...

Страница 16: ... energized and oil flows from the oil manifold through valve ports P and A to cylinder port SC1 and enters the unload side of the cylinder Simultaneously gas on the load side of the cylinder is vented through port SC2 and valve BP to compressor suction NOTICE To control the rate of loading and unloading throttle the needle valve at SC1 port DOUBLE ACTING MODE Booster low differential Open valve at...

Страница 17: ...1 to 3 hours of operation adjust oil cooling system 3 Pull and clean suction strainer after 24 hours of operation If it is excessively dirty repeat every 24 hours until system is clean Otherwise follow the normal maintenance schedule 4 Perform vibration analysis if equipment is available Figure 11 Hydraulic Schematic SC4 BP SC2 SC3 SC1 SC3 2 SC4 SC3 SC13 1 2 SC2 SC1 2 SC2 1 1 2 A B 1 P T BP B A T ...

Страница 18: ...or is used to avoid dumping liquid into compressor suction 5 Protect the compressor during long periods of shutdown If the compressor will be sitting for long periods without running it is advisable to evacuate to low pressure and charge with dry nitrogen or oil This is particularly true on systems known to contain water vapor 6 Preventive maintenance inspection is recommended any time a compresso...

Страница 19: ...recording of gauge pressures temperatures and other pertinent information enables the observer and serviceman to be constantly familiar with the operation of the system and to recognize immediately any deviations from normal operating conditions It is recommended that readings be taken at least daily TROUBLESHOOTING GUIDE Successful problem solving requires an organized approach to define the prob...

Страница 20: ...13 Volumizer Transmitter The linear transmitter with hermetic enclosure is based on the inductive measuring principle It features removable electronics from the sensor well eliminating the need to evacuate the compressor for replacement This type of transmitter is dedicated to volume ratio control and has no user adjustments 1 Shut off control power 2 Remove DIN connector plug from transmitter 3 L...

Страница 21: ...ere is power to the coil Check coil Solenoid may be actuated mechanically by inserting a piece of 3 16 rod against armature pin and pushing spool to opposite end Push A side to confirm unload capability If valve works problem is electrical SLIDE VALVE WILL LOAD BUT WILL NOT UNLOAD A side solenoid coil may be burned out Replace Dirt inside solenoid valve preventing valve from operating both ways Cl...

Страница 22: ...out Repair or replace OIL PRESSURE RAPIDLY DROPS OFF WHEN COMPRESSOR STARTS Main oil injection throttling valve too wide open or oil pressure regulating valve improperly adjusted Readjust both valves NOISE and VIBRATION Pump strainer blocked Clean Pump worn out Repair or replace OIL PRESSURE DROPS AS HEAD PRESSURE INCREASES Normal behavior Set main oil injection and oil pressure for maximum head p...

Страница 23: ...ompressor Motor Magnetic Center Checked Marked N A Compressor Coupling Hub Runout____________ Motor Coupling Hub Runout_ ____________ Initial Cold Alignment Initial Hot Alignment Final Hot Alignment Operating Log Sheet Date Time Hour Meter Reading Equip Room Temp Suction Pressure Suction Temperature Suction Superheat Discharge Pressure Discharge Temperature Corresponding Temperature Oil Pressure O...

Страница 24: ...__________________________ Motor Serial Number _ ________________________________ RPM _________ Frame Size ____________ H P ___________ Refrigerant Ambient Room Temperature _ ____________ F Operating Conditions VIBRATION DATA SHEET Final Hot Alignment SUCTION DISCHARGE OIL SEPARATOR Slide Valve Position Press Press Press Temp F Vi Ratio Temp F Temp F Temp F F L A Total Thickness of Shims Added Fac...

Страница 25: ... female rotor 6 Foundation 12 G gaskets 20 gas load 19 H hermetic enclosur 20 hermetic enclosure 20 Holding Charge 12 hydraulic cylinder 5 16 hydrocarbon gasses 3 I identification data plate 3 Installation 7 insulated 16 L lifting rings 12 linear transmitter 20 load surges 3 Long term storage 4 lubrication system 5 M maintenance 18 Maintenance Maintenance Schedule 19 male rotor 6 male rotor shaft ...

Страница 26: ...r 17 18 system piping 19 T thermal stability 6 transmitter unit 20 traps 3 troubleshooting 18 Troubleshooting 21 Filter cartridges 22 hydraulic control valve 21 Oil Pressure 22 Oil pressure regulator 22 Piston Seals 21 pressure regulating valve 22 Pump 22 Pump strainer 22 service valves 22 Slide Stop 21 Slide stop indicator rod 21 Slide Valve 21 Solenoid coils 21 Solenoid spool 21 Strainer 22 Unlo...

Страница 27: ...070 250 IOM APR 11 Page 27 408 MM ROTARY SCREW COMPRESSOR INSTALLATION OPERATION MAINTENANCE ...

Страница 28: ...ION MAINTENANCE Johnson Controls 100 CV Avenue Waynesboro PA 17268 1206 USA Phone 717 762 2121 FAX 717 762 8624 www jci com frick Form 070 250 IOM 2011 04 Supersedes NOTHING Subject to change without notice Published in USA 0714 PDF 2014 Johnson Controls Inc ALL RIGHTS RESERVED ...

Отзывы: