FMS-2000C
LIT-12013504
2
Risk of Personal Injury or Property Damage.
For use in a controlled environment only. Refer to installation instructions for environmental conditions.
Risk of Electric Shock.
Disconnect the power supply before making electrical connections. Contact with components carrying hazardous voltage can cause
electric shock and may result in severe personal injury or death.
Risk of Electric Shock.
Disconnect all electric power sources from the FMS-2000C Critical Environment Controller before removing the FMS-2000C controller
cover. Contact with internal components carrying hazardous voltage can cause electric shock and may result in severe personal injury
or death.
Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in
permanent damage to the equipment.
Risk of Property Damage.
Do not run low-voltage cable in the same conduit or wiring troughs with high-voltage wires. Running low- and high-voltage wires in the
same conduit or wiring troughs may damage the equipment or cause system malfunction.
Risk of Property Damage.
Ensure that the power source conforms to the requirements of the equipment. Failure to use a correct power source may result in
permanent damage to the equipment.
Risk of Property Damage.
Do not run network communication cables in the same conduit, raceway, or panel with any high-voltage (greater than 30 VAC) wiring.
Isolate all network wiring and all network devices from high-voltage wiring and equipment. Failure to isolate network wiring and
network devices from high-voltage wiring and equipment can result in damage to network devices or poor network performance.
Risk of Property Damage.
Label all wires prior to disconnecting the equipment. Failure to label the wires may cause improper equipment operation after
reconnecting the equipment.
Risk of Property Damage
Do not use a single transformer to power both the actuator and the controller. Use a 24 VAC 30 VA Class 2, Limited Energy, or LPS for
the controller, and a separate 24 VAC 20 VA Class 2, Limited Energy, or LPS for the actuator. Failure to follow the wiring diagrams may
result in damage to the actuator, the transformer, the controller, or all devices and could void your warranty.
IMPORTANT:
Do not install or use this FMS-2000C Critical Environment Controller in or near environments where corrosive substances
or vapors could be present. Exposure of the FMS-2000C Critical Environment Controller to corrosive environments may damage the
device’s internal components and will void the warranty.
IMPORTANT:
Do not install this FMS-2000C Critical Environment Controller in condensing, wet, or damp environments. Moisture may
cause damage to the FMS-2000C controller.
IMPORTANT:
Only qualified personnel should install or service Johnson Controls products. These instructions are a guide for such
personnel. Carefully follow all instructions in this document and all instructions for the FMS-2000C Critical Environment Controller.
Note:
The actuator is sold separately.