FlexSys
Control Box
CB2
Model:
Installation / Operation Manual
V160811
HEATING
DEMAND
AIR VALVES
(DAMPERS)
PROPORTIONAL
WATER VALVE
(10-0V / NORMALLY OPEN /
REVERSE ACTING)
2-POSITION
WATER VALVE
(ON-OFF / NORMALLY OPEN)
2-POSITION
WATER VALVE
(ON-OFF / NORMALLY CLOSED)
0% – 17%
CLOSED
1
CLOSED (10V)
CLOSED (24VAC)
CLOSED (0VAC)
ON
OFF
OFF
OFF
10% – 28%
CLOSED
1
OPEN 20% (8V)
OPEN (0VAC)
OPEN (24VAC)
ON
1
OFF
OFF
21% – 41%
CLOSED
1
OPEN 40% (6V)
OPEN (0VAC)
OPEN (24VAC)
ON
2
OFF
OFF
34% – 54%
CLOSED
1
OPEN 60% (4V)
OPEN (0VAC)
OPEN (24VAC)
ON
3
OFF
OFF
47% – 67%
CLOSED
1
OPEN 80% (2V)
OPEN (0VAC)
OPEN (24VAC)
ON
4
OFF
OFF
60% – 80%
CLOSED
1
OPEN 100% (0V)
OPEN (0VAC)
OPEN (24VAC)
ON
ON
OFF
OFF
73% – 100%
OPEN
2
OPEN 100% (0V)
OPEN (0VAC)
OPEN (24VAC)
ON
ON
OFF
ON
COOLING
DEMAND
0%
CLOSED
1
CLOSED (0V)
CLOSED (24VAC)
CLOSED (0VAC)
ON
OFF
OFF
OFF
0% – 100%
0 – 100% OPEN
CLOSED (0V)
CLOSED (24VAC)
CLOSED (0VAC)
ON
OFF
ON
OFF
100%
OPEN
CLOSED (0V)
CLOSED (24VAC)
CLOSED (0VAC)
ON
OFF
ON
ON
POWER LED
HEA
T LED
COOL
LED
FAN LED
NOTES:
• Air Valve Min% Modulation (1) set by Adj2 Pot (R4 on right)
- Range: 0% (CCW) to 50% (CW)
- Factory set to 0% (Full CCW)
• Air Valve Heat% Modulation (2) set by Adj1 Pot (R8 on left)
- Range: Min% (CCW) to 100% (CW)
- Factory set to 100% (Full CW)
• There is a 7% Deadband in the Heating Demand input, which
gives the appearance of overlap in the ranges.
• Cool LED turns On when Cooling Demand exceeds 17%
• Fan LED turns On when Air Valve modulation exceeds 35%
• Heat LED blinks during lower Heat Demand until WV is fully open
STANDARD SEQUENCE OF OPERATION: