©2016 Johnson Controls   |   The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local           

                                                Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

© 2016 AirFixture, LLC

2

FlexSys

 Control Box

CB2

Model:

Installation / Operation Manual

V160811

HEATING

DEMAND

AIR VALVES

(DAMPERS)

PROPORTIONAL

WATER VALVE

(10-0V / NORMALLY OPEN / 

REVERSE ACTING)

2-POSITION

WATER VALVE

(ON-OFF / NORMALLY OPEN)

2-POSITION

WATER VALVE

(ON-OFF / NORMALLY CLOSED)

0% – 17%

CLOSED 

1

CLOSED (10V)

CLOSED (24VAC)

CLOSED (0VAC)

ON

OFF

OFF

OFF

10% – 28%

CLOSED 

1

OPEN 20% (8V)

OPEN (0VAC)

OPEN (24VAC)

ON

1

OFF

OFF

21% – 41%

CLOSED 

1

OPEN 40% (6V)

OPEN (0VAC)

OPEN (24VAC)

ON

2

OFF

OFF

34% – 54%

CLOSED 

1

OPEN 60% (4V)

OPEN (0VAC)

OPEN (24VAC)

ON

3

OFF

OFF

47% – 67%

CLOSED 

1

OPEN 80% (2V)

OPEN (0VAC)

OPEN (24VAC)

ON

4

OFF

OFF

60% – 80%

CLOSED 

1

OPEN 100% (0V)

OPEN (0VAC)

OPEN (24VAC)

ON

ON

OFF

OFF

73% – 100%

OPEN 

2

OPEN 100% (0V)

OPEN (0VAC)

OPEN (24VAC)

ON

ON

OFF

ON

COOLING

DEMAND

0%

CLOSED 

1

CLOSED (0V)

CLOSED (24VAC)

CLOSED (0VAC)

ON

OFF

OFF

OFF

0% – 100%

0 – 100% OPEN

CLOSED (0V)

CLOSED (24VAC)

CLOSED (0VAC)

ON

OFF

ON

OFF

100%

OPEN

CLOSED (0V)

CLOSED (24VAC)

CLOSED (0VAC)

ON

OFF

ON

ON

POWER LED

HEA
T LED

COOL

 LED

FAN LED

NOTES:

•  Air Valve Min% Modulation (1) set by Adj2 Pot (R4 on right)
   - Range: 0% (CCW) to 50% (CW)
   - Factory set to 0% (Full CCW)
•  Air Valve Heat% Modulation (2) set by Adj1 Pot (R8 on left)
   - Range: Min% (CCW) to 100% (CW)
   - Factory set to 100% (Full CW)
•  There is a 7% Deadband in the Heating Demand input, which

   gives the appearance of overlap in the ranges.
•  Cool LED turns On when Cooling Demand exceeds 17%
•  Fan LED turns On when Air Valve modulation exceeds 35%
•  Heat LED blinks during lower Heat Demand until WV is fully open

STANDARD SEQUENCE OF OPERATION: