Installation
Observe these guidelines when installing a field controller:
•
Transport the controller in the original container to
minimize vibration and shock damage.
•
Verify that all parts shipped with the controller.
•
Do not drop the controller or subject it to physical
shock.
Parts Included
•
one field controller with removable terminal blocks
(Power, SA bus, and FC bus are removable)
•
one installation instructions sheet
Materials and Special Tools Needed
•
three fasteners appropriate for the mounting surface
(M4 screws or #8 screws)
•
one 20 cm (8 in.) or longer piece of 35 mm DIN rail
and appropriate hardware for DIN rail mount (only)
•
small straight-blade screwdriver for securing wires in
the terminal blocks
Mounting
Observe these guidelines when mounting a field
controller:
•
Ensure the mounting surface can support the
controller, DIN rail, and any user-supplied enclosure.
•
Mount the controller horizontally on 35 mm DIN rail
whenever possible.
•
Mount the controller in the proper mounting position.
•
Mount the controller on a hard, even surface
whenever possible in wall-mount applications.
•
Use shims or washers to mount the controller securely
and evenly on the mounting surface.
•
Mount the controller in an area free of corrosive
vapors and observe the Ambient Conditions
requirements in .
•
Provide for sufficient space around the controller for
cable and wire connections for easy cover removal
and good ventilation through the controller (50 mm
[2 in.] minimum on the top, bottom, and front of the
controller).
•
Do not mount the controller on surfaces prone to
vibration, such as duct work.
•
Do not mount the controller in areas where
electromagnetic emissions from other devices or
wiring can interfere with controller communication.
Observe these additional guidelines when mounting a
field controller in a panel or enclosure:
•
Mount the controller so that the enclosure walls do
not obstruct cover removal or ventilation through the
controller.
•
Mount the controller so that the power transformer
and other devices do not radiate excessive heat to
the controller.
•
Do not install the controller in an airtight enclosure.
Figure 1: Field Controller Mounting Positions
DIN Rail Mount Applications
Mounting the field controller horizontal on 35 mm DIN rail
is the preferred mounting method.
To mount a controller on 35 mm DIN rail:
1. Securely mount a 20 cm (8 in.) or longer section of
35 mm DIN rail horizontal and centered in the desired
space so that the controller mounts in the horizontal
position shown in .
2. Pull the two bottom mounting clips outward from the
controller to the extended position ().
2
FEC26Field Equipment Controllers Installation Instructions