background image

5396713-BIM-C-0319

Johnson Controls Ducted Systems

5

INSTALLATION OF SCREW ATTACHMENT DUCT 

CONNECTOR (7990 SERIES)

1.

Make floor cut out as shown in Figure 6.

2.

Determine the depth of the floor cavity from the surface of the floor
to the top of the supply air duct and select the appropriate duct
connector from the chart.

3.

Place locating bracket (supplied with the duct connector) to the
back edge of the floor opening. See Figure 7.

4.

Apply a water based duct sealant to the 1/2” supply duct attach-
ment flange of the duct connector.

5.

Determine which of the four positions the duct connector best cen-
ters over the supply duct and insert it through the floor cutout.

6.

When properly aligned with the supply duct, secure the duct con-
nector to the floor with nails, flat head screws or staples.

7.

Use screws as required to secure duct connector to supply duct.

8.

Cut out the opening to the supply duct. If sealant was not used, the
installer should tape the mating flanges to provide a good air seal.

INSTALLATION OF TAB ATTACHMENT DUCT 

CONNECTOR (7990 SERIES)

1.

Make floor cut out as shown in Figure 6.

2.

Determine the depth of the floor cavity from the surface of the floor
to the top of the supply air duct and select the appropriate duct
connector from the chart.

3.

Place locating bracket (supplied with the duct connector) to the
rear of the floor area for the furnace. See Figure 8.

4.

Determine which of the four positions the duct connector best cen-
ters over the supply duct and insert it through the floor cutout.

5.

Mark cut-out location on the supply duct and remove the duct con-
nector.

6.

Cut out the opening to the supply duct.

7.

Bend tabs down through and back up under the supply duct.

8.

Secure the duct connector to the floor with nails, flat head screws
or staples.

The duct connector is designed for use on ducts down to 12" in width.
When using the connector on smaller width ducts, there is not sufficient
clearance to bend the tabs on two sides of the duct connector. 

In such cases the tabs may be attached to the sides of the duct by
using sheet metal screws or other suitable fasteners. Holes for sheet
metal screws are provided in three (3) tabs on each side of the duct
connector. If more than 3 tabs need to be used to provide a more
secure and air tight connection, the remaining tabs can also be fas-
tened to the duct with screws after drilling the required screw holes.

INSTALLATION OF THE FURNACE

1.

Remove the front panels and set the furnace onto the duct con-
nector. Slide it back until the rear of the unit engages the locator
bracket.

2.

Secure the front of the furnace with two screws at the provided
mounting holes. See Figure 9.

3.

Secure the top of the furnace to a structural member using screw
through the strap at the top of the furnace. Strap may be moved to
any of the holes located along the top back of the furnace. Installer
may provide an equivalent method, such as screws through the
casing side.

 FIGURE 7:  

Duct Connector Screw Attachment (7990 Series)

NOTICE

Duct sealant and tape must be classified as meeting HUD Standard
3280.715, U.L. Standard 181A.

 FIGURE 8:  

Duct Connector Tab Attachment (7990 Series)

LOCATOR BRACKET

NAILS, FLAT HEAD SCREWS,
OR STAPLES

SCREWS

FLOOR

SUPPLY DUCT

A0872-001

LOCATOR BRACKET

NAILS, FLAT HEAD SCREWS,
OR STAPLES

(Bend tabs under duct
opening to secure to the
supply duct.)

FLOOR

SUPPLY DUCT

A0873-001

 FIGURE 9:  

Installation of Furnace

Furnace Seated
Against the
Locator Bracket

Secure Furnace
to Floor with Two
Nails or Screws
(Not Provided).

A0874-001

.

Содержание EBE Series

Страница 1: ...furnace and its packaging inclusions 1 Furnace is rated at 240 volts 60 Hz single phase 2 Filters are furnished with EBE model and are the same for all EBE models 16 x 20 x 1 in top and 20 x 20 x 1 i...

Страница 2: ...8 Installing and servicing heating cooling equipment can be hazard ous due to the electrical components Only trained and qualified personnel should install repair or service heating cooling equip ment...

Страница 3: ...led below furnace The return air opening can be located in a closet front door or a side wall above the furnace casing or in a louvered door on the furnace If opening for the return air is located in...

Страница 4: ...rnace to an under the floor supply duct system The furnace may be installed on combustible flooring without a separate sub base TABLE 1 Duct Connector for Electric Furnaces FLOOR TO DUCT DIMENSIONS FI...

Страница 5: ...ough and back up under the supply duct 8 Secure the duct connector to the floor with nails flat head screws or staples The duct connector is designed for use on ducts down to 12 in width When using th...

Страница 6: ...reaker panel General wire and breaker sizes are shown in Table 2 If sheathed cable is used refer to National Electrical Code Canadian Electrical Code and local codes for additional requirements concer...

Страница 7: ...other applicable codes 2 Does Not require a Jumper 3 Approved for Single Branch Circuit Service Only 4 Jumper provided for Single Branch Circuit Only 5 Requires Jumper Bars P N 3500 378P WARNING For p...

Страница 8: ...n 19 1 2 no wider than 18 1 4 and no deeper than 20 1 2 EUE Furnace Models No extension cabinet and coil shelf are needed for the EUE upflow fur nace The coil shelf is already installed in the EUE mod...

Страница 9: ...OCK SERVICE CONNECTION COVER MUST BE INSTALLED IF FILTERS ARE USED CLEAN REPLACE EACH SEASON OR MORE OFTEN AS NEEDED CAUTION IMPORTANT HIGH VOLTAGE WARNING 5395383 UWD B 1017 LINE LOAD XFMR 3A FUSE RE...

Страница 10: ...ER MUST BE INSTALLED IF FILTERS ARE USED CLEAN REPLACE EACH SEASON OR MORE OFTEN AS NEEDED CAUTION IMPORTANT HIGH VOLTAGE WARNING 5395384 UWD B 1017 LINE LOAD XFMR 3A FUSE RED 8 RED 9 Y G W HEAT COOL...

Страница 11: ...ED CAUTION IMPORTANT HIGH VOLTAGE WARNING 5395385 UWD B 1017 60 AMP CIRCUIT 1 BREAKER 60 AMP 240 VAC 60Hz 1 PHASE CIRCUIT 2 BREAKER GND LUG SINGLE BRANCH CIRCUIT SERVICE 240 VAC 60 Hz 1 PHASE REQUIRES...

Страница 12: ...OR OTHER PROPER INSTRUMENT HAZARD OF ELECTRICAL SHOCK SERVICE CONNECTION COVER MUST BE INSTALLED IF FILTERS ARE USED CLEAN REPLACE EACH SEASON OR MORE OFTEN AS NEEDED CAUTION IMPORTANT HIGH VOLTAGE W...

Страница 13: ...REPLACE EACH SEASON OR MORE OFTEN AS NEEDED CAUTION IMPORTANT HIGH VOLTAGE WARNING 5395388 UWD A 0717 LINE LOAD XFMR 3A FUSE RED 8 RED 9 Y G W HEAT COOL T STAT BLK 1 M3 M1 M2 H2 M5 M6 H4 H3 WHT BLK S...

Страница 14: ...CH CIRCUIT SERVICE GND ECM ELECTRIC FURNACE 23kW CONDENSING UNIT CONTACTOR 240 VAC 60 Hz 1 PHASE REQUIRES JUMPER BARS P N 3500 378 YEL 13 WHT 11 M4 H1 RED SHOCK HAZARD THIS FURNACE MAY BE CONNECTED TO...

Отзывы: