Technical specifications

Table 2: DIS1710 Local Controller display

Product Code Number

MS-DIS1710-0 Local Controller Display for Field Equipment Controllers

Power Requirement

Nominal 15 volts provided by controller over SA Bus.

Power Consumption

2 VA maximum

Ambient Operating

Temperature

0°C–50°C (32°F–122°F)

Ambient Operating

Conditions

10%–90% RH, 30°C (86°F) maximum dew point

Ambient Storage

Temperature

-40°C–70°C (-40°F–158°F)

Ambient Storage

Conditions

5%–95% RH, 30°C (86°F) maximum dew point

Terminations

RJ-12 6-pin jack at Service Port (covered by removable cap-plug) SA Bus connection on back of unit

Processor

Renesas

®

 H8S-2398 16-bit microprocessor

Memory

256 KB Flash Memory 8 KB Random Access Memory (RAM)

Operating System

RTOS-H8S

Network and Serial

Interfaces

Communication to controller over SA Bus

Graphic Display

Resolution

240 x 64 pixels with white LED backlighting (adjustable)

Dimensions (Height x

Width x Depth)

85.9 mm x 238 mm x 25.8 mm (3.4 in. x 9.37 in. x 1.0 in.)

Housing

Plastic housing material: ABS + polycarbonate
Protection: IP20 (IEC60529)

Mounting (Height x

Width)

Mount to the outside of the enclosure 70.5 mm x 216.5 mm (2.78 in. x 8.525 in.)

Shipping Weight

0.14 kg (0.3 lb)

United States:

 UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment; FCC Compliant

to CFR47, Part 15, Subpart B, Class A

Canada:

 UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal Equipment; Industry Canada

Compliant, ICES-003

Europe:

 CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential

requirements and other relevant provisions of the EMC Directive.

Compliance

Australia and New Zealand:

 RCM Mark, Australia/NZ Emissions Compliant

The performance specifications are nominal and conform to acceptable industry standards. For application at

conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be

liable for damages resulting from misapplication or misuse of its products.

Product warranty

This product is covered by a limited

warranty, details of which can be found at

www.johnsoncontrols.com/buildingswarranty.

Single point of contact

APAC

Europe

NA/SA

JOHNSON CONTROLS
C/O CONTROLS PRODUCT
MANAGEMENT
NO. 32 CHANGJIJANG RD NEW
DISTRICT
WUXI JIANGSU PROVINCE 214028
CHINA

JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY

JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA

For more contact information, refer to

www.johnsoncontrols.com/locations.

© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and

are subject to change without notice.

www.johnsoncontrols.com

Содержание DIS1710

Страница 1: ...ed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in which case the users will be required to correct the interference at their own expense Canada This Class A digital apparatus meets all the requirements of the Canadian Interference Causing Equipment Regulati...

Страница 2: ...nel Door with Cutout for display Mounting Location considerations The display is mounted onto the front panel door of an enclosure Mounting dimensions and physical features Refer to the following illustrations for the mounting dimensions and physical features of the display Figure 1 DIS1710 Mounting Dimensions mm in Figure 2 DIS1710 physical features Preparing the panel The display is mounted onto...

Страница 3: ... 4 Insert the display into the front access hole on the panel door Hold in place 5 Carefully insert the back plate to the other side of the access hole inside of the panel door and secure it to the cutout by hand tightening the two thumbscrews You may need to tilt the back plate to slide it onto the two bottom retaining tabs Figure 4 Attaching the display into panel cutout 6 Using the screwdriver ...

Страница 4: ...een the SA Bus connector on the back of the display and the SA Bus jack on the front of the controller Figure 6 The coiled cable is 91 cm 3 ft in length and can be stretched to a maximum length of 152 cm 5 ft Figure 6 Connecting the SA bus cable If the SA Bus jack on the controller is in use you can wire the display s communication cable to the SA Bus terminal block Splice one end of the communica...

Страница 5: ...not require commissioning Cable connection between the DIS1710 Local Controller Display and a commissioned field controller allows for immediate display function Ensure that the communication cable is connected between the display and the controller For more information on commissioning refer to the Controller Tool Help LIT 12011147 Troubleshooting Refer to the DIS1710 Local Controller Display Tec...

Страница 6: ...CN PAZX UL 916 Energy Management Equipment FCC Compliant to CFR47 Part 15 Subpart B Class A Canada UL Listed File E107041 CCN PAZX7 CAN CSA C22 2 No 205 Signal Equipment Industry Canada Compliant ICES 003 Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive Compliance Australia and New Zea...

Отзывы: