[9.2.2] Alarm Tests
[9.2.2.1] M02-04-00 Magnet Test

1.  Place the painted surface of the magnet onto the TEST locator on the 

bottom of the detector housing (Figure 14).

2.  Verify system control panel alarm status and control panel execution 

of all intended auxiliary functions (i.e. fan shutdown, damper control, 
etc.)  

3.  The detector is self-restoring when the magnet is removed. Verify that 

the system control panel has reset; the panel may have to be reset.  

[9.2.2.2] RTS451/RTS451KEY Remote Station Test

The  RTS451/RTS451KEY  Remote  Test  Station  facilitates  test  of  the 
alarm capability of the duct smoke detector. These accessories provide 
the stimulus to initiate an alarm condition at the detector. The detector is 
self-restoring when the accessory test stimulus is removed. Verify that the 
system control panel has reset; the panel may have to be reset.   

[9.2.3] Sensitivity Tests

Notify  the  proper  authorities  that  the  smoke  detector  system  is  under-
going  maintenance,  and  that  the  system  will  temporarily  be  out  of  ser-
vice.  Disable  the  device  or  system  undergoing  maintenance  to  prevent 
unwanted alarms and possible dispatch of the fire department.

[9.3] Maintenance of Duct Smoke Detectors
[9.3.1] Air Filters

1.  Turn off power to the system.
2.  Remove and inspect sampling tube filters.
3.  If filters are heavily coated with dirt, replace them with new filters (p/n 

F36-09-11). If they are not heavily coated, use a vacuum cleaner or 
compressed air nozzle to remove dust, then reinstall the filters. 

5 7

PA400

5 = Alarm Signal
7 = Aux. Power (–)

Figure 12.  Detector with optional PA400

Figure 13. Insulator card for DH300RPL

H0132-00

H0133-00

H0130-00

Figure 14. Testing detector alarm:

Figure 10. Wiring Diagram for DH300RPL Duct Smoke 
Detector with optional RA400Z

5 7

RA400Z

5 = Alarm Signal
7 = Aux. Power (–)

DO NOT BREAK TAB ON RA400Z

H0135-00

Figure 11. System Wiring Diagram 
for DH300RPL Duct Smoke 
Detector with RTS451/RTS451KEY

ALARM SIGNAL

AUX. POWER (–)

TEST +

TEST –

ALARM SIGNAL

NOT USED

NOT USED

CIRCUIT

REFERENCE

TEST

SWITCH

FOR RTS451, TERMINAL 3 IS NOT 

USED. (RTS451 DOES NOT HAVE 

A TERMINAL 6.) FOR RTS451KEY, 

TERMINALS 3 AND 6 ARE NOT USED.

RTS 451/RTS451KEY

5

7

4

3

1

3

6

2

4

5

Содержание DH300RPL

Страница 1: ... it can isolate toxic smoke and fire gases throughout the areas served by the duct system Two LEDs on each detector may illuminate if programmed by the system control panel to provide a local alarm indication There is also a remote alarm output for use with auxiliary devices The DH300RPL has remote test capability with the RTS451 RTS451KEY Remote Test Station The DH300RPL incorporates a cover tamp...

Страница 2: ...Installation for ducts more than 8 feet wide 4 Step 5 Install the filters 4 Step 6 Field wiring 4 Step 7 Perform detector check 5 Step 8 Install the cover 5 Step 9 Detector Maintenance and Test Procedures 5 1 Verify Duct Air Flow Direction And Velocity The DH300RPL duct smoke detector is designed to be used in air handling systems having air velocities of 100 to 4000 feet per minute Be sure to che...

Страница 3: ...opposite the duct smoke detector 2 Slide the tube into the housing bushing that meets the air flow first Position the tube so that the arrow points into the air flow as shown in Figure 4 3 Secure the tube flange to the housing bushing with two 6 self tapping screws 4 For tubes longer than the width of the air duct the tube should extend out of the opposite side of the duct If there are more than 2...

Страница 4: ... where the flange will be used 5 Install The Filters To install the sampling tube filters simply push the filters into the sampling and exhaust tube holes as shown in Figure 6 If a metal sampling tube is used install the filters over the tube end Figure 6 Sampling tube filter installation 6 Field Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical...

Страница 5: ...in duct smoke detectors as recommended in NFPA 72 The tests contained in this manual were devised to assist maintenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the device or system under test to prevent unwanted alarms 9 1 Smoke Entry Tests 9 1 1 Air...

Страница 6: ...ces to determine whether the filters should be replaced because only a high percentage of contamination affects performance If further testing is required compare differ ential pressure readings with and without the filters installed If the difference exceeds 10 replace the filters In no case should the pressure differential fall below 0 0015 inches of water 9 2 Standby Alarm And Sensitivity Tests...

Страница 7: ...and that the system will temporarily be out of ser vice Disable the device or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 9 3 Maintenance of Duct Smoke Detectors 9 3 1 Air Filters 1 Turn off power to the system 2 Remove and inspect sampling tube filters 3 If filters are heavily coated with dirt replace them with new filters p n F36 09 11 If...

Страница 8: ...different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help To keep your equipment in excellent working order ongoing maintenance is required per the manufacturer s recommendations and UL and NFPA standards At a minimum the requirements of Chapter 7 of NFPA 72 the National Fire Alarm Code shall be followed A preventative maintenance agre...

Отзывы: