background image

FOAM

GASKETS

SAMPLING TUBE

SAMPLING TUBE

FILTERS

DETECTOR

COVER

DETECTOR BOARD

CONDUIT HOLES

DETECTOR

HOUSING

TERMINAL STRIP

POWER BOARD

COVER MOUNTING

SCREWS

J500-41-00 

I56-2199-003R

Johnson Controls, Inc., 507 E. Michigan St., Milwaukee, WI 53201

Before installing detectors, please thoroughly read the NEMA

 Guide for Proper Use of Smoke Detectors in Duct Applications, 

which provides detailed 

information  on  detector  spacing,  placement,  zoning,  wiring,  and  special  applications.  Copies  of  this  manual  are  available  from  NEMA  (National 
Electrical Manufacturers Association, 2101 L Street NW, Washington, DC 20037). NFPA Standards 72 and 90A should also be referenced for detailed  
information.

NOTICE:

 This manual shall be left with the owner/user of this equipment.

IMPORTANT:

 This detector must be tested and maintained regularly following NFPA 72 requirements. The detector should be cleaned at least once 

a year.

GENERAL DESCRIPTION

An HVAC system supplies conditioned air to virtually every area of a building. Smoke introduced into this air duct system is distributed to the entire 
building. Smoke detectors designed for use in air duct systems are used to sense the presence of smoke in the duct. 

The  DH300RPL  air  duct  smoke  detector  is  a  photoelectric  detector. This  smoke  detection  method  combines  with  an  efficient  housing  design  that 
samples air passing through a duct and allows detection of a developing hazardous condition. When sufficient smoke is sensed, an alarm signal is 
initiated at the fire control panel monitoring the detector, and appropriate action can be taken to shut off fans, blowers and change over air handling 
systems, etc. This can prevent the distribution or it can isolate toxic smoke and fire gases throughout the areas served by the duct system.

Two LEDs on each detector may illuminate, if programmed by the system control panel, to provide a local alarm indication. There is also a remote 
alarm  output  for  use  with  auxiliary  devices.  The  DH300RPL  has  remote  test  capability  with  the  RTS451/RTS451KEY  Remote  Test  Station.  The 
DH300RPL incorporates a cover tamper feature. When the cover is removed for more than 20 minutes, the unit loses communication at the panel, a 
trouble is indicated at the panel and the alarm relay switches states thereby shutting down fans, dampers and blowers. In the case when the sensor 
is removed or when there is no power to the unit, only a trouble is indicated at the panel (alarm relay does not work any longer).

CONTENTS OF THE DUCT SMOKE DETECTOR HOUSING KIT

The DH300RPL Duct Smoke Detector consists of the following items
(See Figure 1.):

DH300RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR

WITH EXTENDED AIR SPEED RANGE

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Figure 1. Exploded view of duct smoke detector components:

NOTE:

  For ducts over 1

1

⁄ 2

 feet, longer sampling tubes must be ordered to complete the installation. They must be the correct length for the width 

of the duct where they will be installed. See Table 1 on page 3 to determine the sampling tube required for different duct widths.

Contents Of The Duct Smoke 
Detector

1.  Complete duct smoke detector assembly with 

sensor

2.  Two #10 x 

1

/

4

 sheet metal mounting screws

3.  Two sampling tube filters
4.  One test magnet
5.  Drilling template
6.  Two foam gaskets
7.  Four #6-self tapping mounting screws for 

the sampling tube and optional exhaust tube 
extension

8.  One sampling tube end cap
9.  One plastic sampling tube
10.  One #8 self-tapping screw for plastic sampling 

tube   

NOTE:  A  detector  sensor  board  DOES  NOT 
need to be ordered separately.

H0129-00

Содержание DH300RPL

Страница 1: ... it can isolate toxic smoke and fire gases throughout the areas served by the duct system Two LEDs on each detector may illuminate if programmed by the system control panel to provide a local alarm indication There is also a remote alarm output for use with auxiliary devices The DH300RPL has remote test capability with the RTS451 RTS451KEY Remote Test Station The DH300RPL incorporates a cover tamp...

Страница 2: ...Installation for ducts more than 8 feet wide 4 Step 5 Install the filters 4 Step 6 Field wiring 4 Step 7 Perform detector check 5 Step 8 Install the cover 5 Step 9 Detector Maintenance and Test Procedures 5 1 Verify Duct Air Flow Direction And Velocity The DH300RPL duct smoke detector is designed to be used in air handling systems having air velocities of 100 to 4000 feet per minute Be sure to che...

Страница 3: ...opposite the duct smoke detector 2 Slide the tube into the housing bushing that meets the air flow first Position the tube so that the arrow points into the air flow as shown in Figure 4 3 Secure the tube flange to the housing bushing with two 6 self tapping screws 4 For tubes longer than the width of the air duct the tube should extend out of the opposite side of the duct If there are more than 2...

Страница 4: ... where the flange will be used 5 Install The Filters To install the sampling tube filters simply push the filters into the sampling and exhaust tube holes as shown in Figure 6 If a metal sampling tube is used install the filters over the tube end Figure 6 Sampling tube filter installation 6 Field Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical...

Страница 5: ...in duct smoke detectors as recommended in NFPA 72 The tests contained in this manual were devised to assist maintenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the device or system under test to prevent unwanted alarms 9 1 Smoke Entry Tests 9 1 1 Air...

Страница 6: ...ces to determine whether the filters should be replaced because only a high percentage of contamination affects performance If further testing is required compare differ ential pressure readings with and without the filters installed If the difference exceeds 10 replace the filters In no case should the pressure differential fall below 0 0015 inches of water 9 2 Standby Alarm And Sensitivity Tests...

Страница 7: ...and that the system will temporarily be out of ser vice Disable the device or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 9 3 Maintenance of Duct Smoke Detectors 9 3 1 Air Filters 1 Turn off power to the system 2 Remove and inspect sampling tube filters 3 If filters are heavily coated with dirt replace them with new filters p n F36 09 11 If...

Страница 8: ...different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help To keep your equipment in excellent working order ongoing maintenance is required per the manufacturer s recommendations and UL and NFPA standards At a minimum the requirements of Chapter 7 of NFPA 72 the National Fire Alarm Code shall be followed A preventative maintenance agre...

Отзывы: