Water regulating valve kit
Optional Water Regulating Valve Kit modulates the condenser water flow in order to control the
condensing pressure in each refrigeration circuit. Valves open and close in response to rise and fall
of the condensing pressure as sensed by the capillary tube, which is connected to the liquid line
access fittings of the respective refrigerant circuits.
When the valves are properly installed and adjusted, water flow will automatically decrease as
the discharge pressure falls and will increase as the discharge pressure rises. Refer to the
Water
Regulating Valve Kit for CSV096B-300B Installation manual (Form 145.15-N1)
for more information on
installation and operation.
WARNING
UNAUTHORIZED CUSTOMER MODIFICATIONS TO CERTIFIED PRODUCTS ARE PROHIBITED. The
manufacturer has certified the product as being compliant with applicable government and/or
industry standards.
Note:
Product certification is designated either on the product itself or in the product
literature. The certification mark identifies the applicable standards as well as the Nationally
Recognized Test Lab (NRTL) or other testing facility that conducted the testing, where
applicable. If changes are made to the product, an engineering review will be needed to
assess the impact to the product certification. In some instances, the changes may be such
that the NRTL or testing facility will need to review and potentially reapprove of the product
by means of a field or site inspection and certification. Any person or entity making changes
to the product is responsible for obtaining any necessary engineering review and reapproval.
Unauthorized customer modifications to certified products are prohibited for the following
reasons:
1. Modifications may create hazards that could result in death, serious injury, or
equipment damage.
2. Modifications will void product warranties.
3. Modifications may invalidate product certifications.
4. Modifications may violate country standards. Country standards may require that only
certified products be used in certain applications, and modifications that result in the
loss of product certification may violate those standards.
15
C-Series Vertical (CSV) Water-Cooled Self-Contained Units, B Generation, R-410A Installation, Operation, and
Maintenance Manual