368261-UIM-B-1008

8

Johnson Controls Unitary Products

FURNACE ASSEMBLY - MC & FC SERIES COILS

These coils are factory shipped for installation in either upflow or down-
flow applications with no conversion.

Position the coil casing over or under the furnace opening as shown in
Figure 8 after configuring coil flanges as required see “Coil Flange” sec-
tion below.

COIL FLANGE INSTALLATION

The coils include removable flanges to allow proper fit up with furnaces
having various inlet and outlet flange configurations. The two flanges
are attached to the top of the coil in the factory during production.  For
proper configuration of flanges refer to Figure 9.

FURNACE ASSEMBLY - MC SERIES COILS ONLY

MC coils are supplied ready to be installed in a horizontal position. A
horizontal pan is factory installed. MC coils should be installed in all hor-
izontal applications with the horizontal drain pan side down.

For horizontal left hand applications no conversion is required to an MC
coil when used with a downflow/horizontal furnace. A mounting plate,
supplied with every coil should always be installed on the side desig-
nated as top side. See Figures 10 & 11.

FURNACE ASSEMBLY - PC SERIES COILS

These upflow coils are designed for installation on top of upflow fur-
naces only.

If the coil is used with a furnace of a different size, use a 45° transition
to allow proper air distribution through the coil.

1.

Position the coil casing over the furnace opening as shown in Fig-
ure 12.

2.

Place the ductwork over the coil casing flange and secure.

3.

Check for air leakage between the furnace and coil casing and
seal appropriately.

NOTE: 

Dimension “C” should be at least 2/3 of dimension “D”. See Fig-

ure 12.

CRITICAL COIL PROJECTION

The coil assembly must be located in the duct such that a minimum dis-
tance is maintained between the top of the coil and the top of the duct.
Refer to Table 2.

COIL / FURNACE ASSEMBLY - HC SERIES COILS

These coils are supplied ready to be installed in a right hand position or
a left hand position. When used in conjunction with a horizontal furnace
(blow through) application, the coil should be oriented with the opening
of the “A” coil closest to the furnace. See Figure 13.

NOTE: 

Each coil is shipped with an external tie plate that should be

used to secure the coil to the furnace. It should be installed on the back
side of the coil using the dimpled pilot holes. See Figure 13.

 FIGURE 9:  

Coil Flange

 FIGURE 10:  

Horizontal Right Application (Typical)

 FIGURE 11:  

Horizontal Left Application

ALTERNATE
FLANGE LOCATION
(Used for downflow or
horizontal left
installations)

FACTORY

FLANGE

LOCATION

(Used for upflow

or horizontal

right installations)

Furnace

Mounting Plate

Furnace

Mounting Plate

Do not drill any holes or drive any screws into the front duct
flange on the coil in order to prevent damaging coil tubing. See
Figure 12.

 FIGURE 12:  

PC Series Upflow Coil Installation

Table 2: 

Coil Projection Dimensions - PC Series Coils

COIL SIZE

DIMENSION “C” INCH

PC18

3-1/2

PC24

4-1/2

PC30, PC32, PC35

4-1/2

PC42, PC43, PC36, PC37

5-1/2

PC48

6-1/2

PC60

9

 FIGURE 13:  

Horizontal Left or Right Application (Right Shown)

Flexible
Duct Collar

Do not drill
or Screw
this flange

Field
Fabricated
Ductwork

Upflow
Coil

Upflow
Furnace

Secondary

Drain

Primary

Drain

D

C

(Min)

Alternate

Drain Location

Use tie plate
supplied with coil

Air flow

Gas Furnace

Содержание CM8M*MP

Страница 1: ...Outside and Ambient Combustion Air 21 Gas Valve 25 Furnace Control Board 26 Wiring Diagram 30 LIST OF TABLES Unit Clearances to Combustibles 4 Coil Projection Dimensions PC Series Coils 8 Cabinet and...

Страница 2: ...ting point provided that the tubes are lifted at the front of the heat exchangers where attached to the vestibule panel Do not use the top return bend of the heat exchangers as lifting points as the t...

Страница 3: ...the National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 or for only the NFGC contact the American Gas Association 400 N Capital N W Washington DC 20001 or www NFPA org CANADA NS...

Страница 4: ...ng but not limited to decks and porches the following require ments shall be satisfied 1 INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall horizontal vented gas fu...

Страница 5: ...es are rotated down for shipment In order to use the flanges remove the screw holding an individual flange rotate the flange so it is in the upward position and reinstall the screw then repeat this fo...

Страница 6: ...igure 4 When moving or handling this furnace prior to installation always leave the doors on the furnace to provide support and to prevent damage or warping of the cabinet When lifting the furnace sup...

Страница 7: ...te the vent blower 90 left or right so that the vent pipe passes through the side of the furnace casing rather than the end See Figure 6 COIL INSTALLATION COIL FURNACE ASSEMBLY MC FC PC SERIES COILS F...

Страница 8: ...e furnace and coil casing and seal appropriately NOTE Dimension C should be at least 2 3 of dimension D See Fig ure 12 CRITICAL COIL PROJECTION The coil assembly must be located in the duct such that...

Страница 9: ...24 25 29 5 For Cladded door add appoximately an additional 75 28 5 Electrical Entry Gas Pipe Entry Thermostat Wiring FRONT 14 1 1 5 23 SUPPLY END C 24 38 20 5 B Gas Pipe Entry Thermostat Wiring 33 A...

Страница 10: ...as piping may be connected from either side of the furnace using any of the gas pipe entry on both sides of the furnace Refer to Figure 14 All filters and mounting provision must be field supplied All...

Страница 11: ...he input rate back up to approxi mately 76 000 BTU H which is what it should be for that furnace at 6 000 feet SECTION V ELECTRICAL POWER ELECTRICAL POWER CONNECTIONS Field wiring to the unit must be...

Страница 12: ...4 volt 40 VA transformer is sized for the furnace components only and should not be connected to power auxiliary devices such as humidifiers air cleaners etc The transformer may provide power for an a...

Страница 13: ...tric heat on thermostat is not necessary C 24 Volt Common Y Compressor SINGLE STAGE AIR CONDITIONER Y Compressor Contactor SINGLE STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 Single Stage C...

Страница 14: ...sed with batteries Thermostat Installer Setup 0170 System Type must be set to 8 2 Heat 2 Cool Multistage Conventional Connection of the C terminal 24 volt common is optional when used with batteries T...

Страница 15: ...t Y1 Single Stage Compressor MODULATING FURNACE CONTROL G Fan MODULATING FURNACE Y Y2 Second or Full Stage Compressor DHUM Dehumidification Open on Humidity Rise W Modulating Heat Part Numbers SAP Leg...

Страница 16: ...unction Light W Auxiliary Heat SINGLE STAGE HEAT PUMP 1 1 Part Number S1 2HU16700124 3 Y2 Second Stage Compressor Step 9 of Thermostat Installer Configuration Menu must be set to Pump OFF Step 1 of Th...

Страница 17: ...2 OUT Second Stage Heat Y2 OUT Second Stage Compressor Y1 Single Stage Compressor X L Malfunction Light Y2 Second Stage Compressor W Auxiliary Heat BS Bonnet Sensor BSG Bonnet Sensor YORKGUARD VI CONT...

Страница 18: ...at R 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR AUX Auxiliary Heat Step 1 of Thermostat Installer Configuration Menu must be set to HP2 Selection of GAS ELEC switch on thermostat not necessary The...

Страница 19: ...nal is removed 3 Hot Heat Pump The hot heat pump feature will work when the control is wired to a 2 stage thermostat and a 2 stage heat pump 4 Hot Heat Pump The hot heat pump feature will not work whe...

Страница 20: ...have no dimen sion smaller than 0 25 0 64 cm 3 A manually operated damper or manually adjustable louvers are not permitted for use 4 A automatically operated damper or automatically adjustable lou ve...

Страница 21: ...ional area as the free area of the air supply inlet opening to which it connects 4 The blocking effects of louvers grilles and screens must be given consideration in calculating free area If the free...

Страница 22: ...ollowing steps shall be followed for each appliance connected to the venting system being placed into operation while all other appliances connected to the venting system are not in operation 1 Inspec...

Страница 23: ...per input rate using natu ral gas with a heating value of 1030 BTU Ft3 38 4 MJ m3 If the heat ing value of your gas is significantly different it may be necessary to replace the orifices NOTE DO NOT s...

Страница 24: ...300 750 78 46 92 231 25 144 288 720 80 45 90 225 26 138 277 692 82 44 88 220 27 133 267 667 84 43 86 214 28 129 257 643 86 42 84 209 29 124 248 621 88 41 82 205 30 120 240 600 90 40 80 200 31 116 232...

Страница 25: ...urnace temperature rise Take temperature readings of both the return air and the heated air in the ducts about six feet away from the furnace where they will not be affected by radiant heat Increase o...

Страница 26: ...removed Electrical supply to this unit is dependent upon the panel that covers the blower compartment being in place and properly positioned ROLLOUT SWITCH CONTROLS These controls are mounted on the...

Страница 27: ...l senses that flame is present the circulating blower starts at low speed 5 The furnace fires at 70 of full rate for 30 45 seconds then drops to the minimum 50 firing rate 6 The firing rate is automat...

Страница 28: ...not connected properly check for loose plug or loose wires in plug Steady On Red Control fault has been detected or there is 24 volts present without 115 volts Check that there is 24 volts and 115 vol...

Страница 29: ...L Models Only MISCELLANEOUS ORIFICE BURNER Natural 45 SIGHT GLASS OVAL 2 Req d GASKET FOAM Door 1 5 ft req d GASKET INTAKE PAN PLUG VENT HOLE BRACKET DOOR WIRING HARNESS FERRULE 3 Req d GROMMET 3 Req...

Страница 30: ...nted in U S A 368261 UIM B 1008 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 368261 UIM A 0508 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 SECTION XI WIR...

Отзывы: