P5417055
21
5.9 Comfort Setting
5.9.1 Setting of “Control Cool Air” (Cold Draft Control during Cooling Operation)
NOTICE
● The "Control Cool Air" function may not have much effect depending on the operating conditions of the outdoor
unit.
● In case one outdoor unit is connected to multiple indoor units and the rate of these indoor units which are
equipped with the "Control Cool Air" function is low, this function may not have much of an effect.
● When this function is set, it may take a few minutes to cool the entire room.
● While this function is activated, “Cold draft rest.” is displayed on the LCD control panel of the wired
controller.
(1) Function
This function controls the overcooling airflow to prevent of cold draft.
(2) Setting Items
* OFF : This function is not available.
* LOW : The over-cooling airflow temperature is controlled low degree.
* MID : The over-cooling airflow temperature is controlled medium degree.
* HIGH : The over-cooling airflow temperature is controlled high degree.
(The default setting is “OFF”)
(3) Supplement of Function
• The discharge air temperature is elevated higher in “HIGH” > “MID” > “LOW” order.
• The recommended discharge air temperature setting is “LOW”. (When feeling cold at "LOW", change
the setting to “MID” or “HIGH”.)
* This function also reduces the formation of dew condensation on the decorative panel when the
discharge air temperature is lower than the inlet air temperature in a very humid room.
(The recommended discharge air temperature setting is “LOW”.)
(1) Function
This function automatically activates the louver under
the setting of “Avoid Air” or “Receive” when the motion
sensor detects human activity.
The “Avoid Air” setting is the reduction of airflow set
by the wired controller.
The "Receive" setting allows airflow set by the wired
controller.
Each Detection Area:
A
to
D
,corresponds to each
area
a
to
d
as shown on the right.
5.9.2 Setting of Avoid Air and Receive
Detecting Area of Motion Sensor
c
A
B
C
D
d
b
a
Motion Sensor
• NORMAL: The function is not activated.
(The louvers are situated in the setting directions on the main menu.)
• AVOID AIR: The louver angle is automatically adjusted to the highest angle if human activity is
detected by the motion sensor.
• RECEIVE: The louver operation is automatically changed to “AUTO” (Auto-Swing) mode if
human activity is detected by the motion sensor.
(The default setting is “NORMAL”.)
(2) Descriptions for Setting Items
Louver in COOL (Louver Activation at Cooling Operation)
Louver in HEAT (Louver Activation at Heating Operation)