background image

Setup and adjustments

Configuring N2 communications

N2-capable controllers support the full range of

possible N2 device addresses provided by the N2

protocol standard (1-254).
To configure a controller to communicate using the N2

protocol, complete the following steps:
1. Disconnect the 240 VAC supply from the

controller.

2. Set the address switches to the desired N2

address. For details about setting a device

address, see 

Setting the device address

.

3. Reconnect the 240 VAC supply to the controller.

4. Using an SA bus connection, download the

firmware and controller application file configured

for N2 to the controller.

Switching the Communications Protocol

from N2 to MS/TP

For N2 sites that are converting to BACnet MS/TP,

you can switch the communications protocol of N2-

configured MS/TP controllers back to BACnet MS/TP.
To switch the ATC operating in N2 mode back into

BACnet MS/TP mode, complete the following steps:
1. Disconnect the 240 VAC supply from the

controller.

2. Set the address switches to the desired BACnet

MS/TP address. For details about setting a device

address, see 

Setting the device address

.

3. Reconnect the 240 VAC supply to the controller.

4. Using an SA Bus connection, download a

controller application file configured for BACnet

MS/TP to the controller.

Setting the device address

Equipment controllers are master devices on MS/TP

(FC or SA) buses. Before you operate controllers on a

bus, you 

must

 set a valid and unique device address

for each controller on the bus. You set the ATC device

address by setting the positions of the Device Address

switch on the front of the controller.
The 

Technical Specifications

 table describes the valid

device addresses for communications bus applications.

The device address must match the device address

defined in the Controller Configuration Tool (CCT)

under 

Define Hardware > Network Settings

.

To set the device addresses on the ATCs, complete the

following steps:
1. Set a unique and sequential device address for

each of the equipment controllers connected on

the FC or SA Bus.

2. To ensure the best bus performance, set

sequential device addresses with no gaps in the

device address range (4, 5, 6, 7, 8, 9, and so on).

The equipment controllers do not need to be

physically connected on the bus in their numerical

device address order.

Setting up a local display

ATC models do not have an integral display, but can be

connected to a DIS1710 Local Controller Display. For

detailed information about setting up and operating

a remotely connected DIS1710 display, refer to the

DIS1710 Local Controller Display Technical Bulletin

(LIT-12011270) .

Input/Output Wiring Validation

The ATCs ship with a default state that can assist in

validating the wiring of the input and output terminals

prior to download of an application file. When the

controller is powered on in this state, the Fault LED will

flash in a pattern of two quick blinks and then a long

pause (see Table 6).
To make use of this feature, make sure that you set

the device address and wire the input and output

terminals. Apply power to the ATC and connect to the

device with either a MAP Gateway or MS-DIS1710-0

Local Display to view the points in the controller. The

ATC reports an Operational status even though there

is no true application loaded. CCT will not be able to

commission or upload the device as a result until a

true application is downloaded. The application name

displayed will be the address of the controller followed

by the model of the controller and “Default State”.
For example, an ATC with device address set to 8 would

have the default state application name of “8-ATC

Default State”.
The default state creates I/O points for all connections

on the input and output terminals. It assumes all

Universal Inputs (UIs) are Nickel temperature sensors.

All Configurable Outputs (COs) are treated as Binary

Outputs (BOs) with an initial value of 0. The default

state also takes input from a Network Sensor at

address 199. If there is no connected Network Sensor,

the startup of this default state will be delayed by

ATC1510 Advanced Terminal Unit Controller Installation Guide

13

Содержание ATC1510

Страница 1: ...dio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area ma...

Страница 2: ...the back of the controller extend the two mounting clips as illustrated 3 Position the controller so that the two extended mounting clips are facing downwards and place the controller on the DIN rail...

Страница 3: ...fa on incor recte risquent d endommager irr m diablement l quipement 1 Wire the FC Bus Terminal Block The ATC features a blue removable 4 terminal FC Bus block that fits into a board mounted jack Wire...

Страница 4: ...450 ft and the wire cross sectional area is 1 5 mm 2 16 AWG to 0 5 mm 2 22 AWG Input and Output wiring guidelines Table 2 and Table 3 provide information and guidelines about the functions ratings an...

Страница 5: ...Accumulator Mode 0 01 second minimum pulse width 50 Hz at 50 duty cycle Internal 18 V 3k ohm pull up BINARY Inputs ICOMn Binary Input Common for all Binary Input IN terminals Note All Binary ICOMn ter...

Страница 6: ...240 VAC 0 66FLA 4LRA 50k cycles BINARY RELAY 5A Output OCOMn Binary Relay Output Common for OUTn terminal Note Each Binary Relay Output Common terminal OCOMn is isolated from all other commons includi...

Страница 7: ...wire 137 m 450 ft twisted wire 0 5 mm 2 22 AWG stranded copper 183 m 600 ft twisted wire 91 m 300 ft twisted wire B 0 25 mm 2 24 AWG stranded copper 107 m 350 ft twisted wire 61 m 200 ft twisted wire...

Страница 8: ...s COM Signal Reference Common for Bus communications FC BUS 2 SHIELD Isolated terminal optional shield drain connection 0 5 mm 2 22 AWG stranded 3 wire twisted shielded cable recommended SA Bus Commun...

Страница 9: ...le termination diagrams Table 5 Termination diagrams Type of Field Device Type of Input Output Termination Diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Self Powered UI...

Страница 10: ...t Output CO 24 VAC Triac Output Switch Low External Source CO Incremental Control to Actuator Switch Low Externally Sourced Triac Jumpers where applicable BO 24 VAC Binary Output Switch Low Externally...

Страница 11: ...he TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection Network Stat with Terminals Addressable SA Bus Network Stat with Terminals Fixed Address 199 SA Bus The following...

Страница 12: ...rs Accessory Kit all wiring must be secured to the stress brackets as illustrated below The following procedure describes how to install the IP20 Covers Accessory Kit to the ATC 1 Attach the IP20 cove...

Страница 13: ...ential device address for each of the equipment controllers connected on the FC or SA Bus 2 To ensure the best bus performance set sequential device addresses with no gaps in the device address range...

Страница 14: ...commission the controller but you cannot use the Bluetooth connection to Transfer to Device Download The MAP Gateway serves as a replacement for the BTCVT which is no longer available for purchase but...

Страница 15: ...d required if controller is in Boot mode Blink 2 Hz Download or Startup in progress not ready for normal operation Rapid blink SA Bus communications issue SA BUS Green Blink 2 Hz Blink 2 Hz Data Trans...

Страница 16: ...ical Features The following section describes the physical features of the ATC Figure 6 Advanced Terminal Unit Controller Physical Features ATC1510 Advanced Terminal Unit Controller Installation Guide...

Страница 17: ...outputs C 24 VAC out D 5 A relay outputs E DIN clips F Triac outputs G 10 A relay output H 240 VAC power input I FC Bus J FC Bus EOL switch K SA Bus L SA Bus RJ12 M USB N Universal inputs O Binary inp...

Страница 18: ...and not valid field controller addresses N2 Valid field controller device addresses 1 to 254 Device address 255 is reserved for the broadcast address and not a valid field controller address Communica...

Страница 19: ...d common terminal between all 5A ROs Binary Output Triac BO 24 VAC or 240 VAC 500 mA Resistive Externally powered Shared common terminal between all BO Triacs 10 A Relay Output 10A RO K8 Single Pole S...

Страница 20: ...E VOLTAGE 4000 V Ball Pressure temperature 90 C BINARY RELAY Outputs Reference all relay commons to the same pole of the supply circuit BINARY Triacs Outputs Reference all triac commons to the same po...

Отзывы: