AD-1252 Thermal Dispersion Probe Airflow Measuring System Installation Instructions
14
UNITS
This option submenu sets the displayed velocity and
temperature unit. To access this submenu, press
ENTER. The LCD screen states UNIT SYSTEM. Use
UP and DOWN to select SI or IU unit systems.
•
Select SI for FPM or CFM with temperature in
degrees Fahrenheit.
•
Select UI for M/S or L/S with temperature in
degrees Celsius.
Use UP and DOWN to scroll through the available
units. Press ENTER to select the desired unit.
If CFM or L/S is selected, the area is requested on the
LCD screen. Use UP and DOWN to adjust the area
calculation. Press ENTER to accept the area value.
See Figure 19.
Figure 19: Units Submenu
ENTER
UNIT SYSTEM
:S.I.
UNIT SYSTEM
:I.U.
VELOCITY UNIT
:M/S
AREA VALUE
:1.00 sq.M.
AREA VALUE
:1.00 sq.ft.
VELOCITY UNIT
:FPM
VELOCITY UNIT
:L/S
VELOCITY UNIT
:CFM