background image

System 350 A350E Electronic Cooling Control Product/Technical Bulletin

    5

Sensor Connection

Shielded cable is not generally required for sensor
wiring on runs of less than 50 ft (15.2 m), but is
recommended for lengths greater than 50 ft (15.2 m).
Connect the shield to the COM sensor terminal on the
A350E. (See Figure 2 for terminal location.) Sensor
A99BA-200, which includes a shielded cable, is
available if needed.

Note:

At the maximum cable lengths listed in
Table 2, no more than 1F° (0.6C°) error in the
sensed temperature will result due to wire
resistance.

Table 2: Recommended Maximum Sensor
Cable Lengths

Wire

Shielded Cable Length

*

Gauge

Feet

Meters

14 AWG

800

244

16 AWG

500

152

18 AWG

310

94

20 AWG

200

61

22 AWG

124

38

* Values provided are for 2-wire stranded cable.

A variety of A99B Series Temperature Sensors
and mounting hardware are available for use with
the A350E. Connect the sensor to the SEN
terminal and one of the COM terminals on the
four position terminal strip located at the top left of
the printed circuit board, as shown in Figure 6. The
sensor is not polarity sensitive.

The sensor must be mounted so that it can
accurately sense the temperature of the controlled
medium.

Table 3: Sensor Included With A350E
Controls

Control

Sensor Included

A350EA-4C

A99BB-25C; Range -40 to 212°F
(-40 to 100°C)
Lead length is 9-3/4 in. (0.25 m).

A350EB-1C

No Sensor Included

A350EB-1D

No Sensor Included

A350EB-2C

No Sensor Included

For more information regarding sensor options and
installation, refer to the

 A99B Series Temperature

Sensors Product/Technical Bulletin (LIT-125186).

Load

Load

Load

Load

Shield (Connect
to COM on A350E.)

Sensor

A350E

Y350R

S350A

D350

S350A

S350A

120 VAC

24V

COM

COM

SEN

NC

COM NO

Figure 6: Typical Wiring Diagram for an A350E Powered by a

Y350R Power Module    

Содержание A350E

Страница 1: ...esign provides easy plug together connections for quick installation and future expandability Figure 1 A350E Electronic Cooling Control Features and Benefits Modular Design Enables stage display and p...

Страница 2: ...ity of the installer to add devices safety limit controls that protect against or systems alarm supervisory systems that warn of control failure Setpoint Adjustment Setpoint is defined as the temperat...

Страница 3: ...echnical Bulletin LIT 930080 S350C Slave Stage Modules S350C Slave Stage Modules receive power and sensor input from the A350E control S350C Slave Stage Modules perform switching functions based upon...

Страница 4: ...as well as other control modules Refer to Figures 5 and 6 for proper arrangement Note When mounting any System 350 module to rigid conduit attach the hub to the conduit before securing the hub to the...

Страница 5: ...s Temperature Sensors and mounting hardware are available for use with the A350E Connect the sensor to the SEN terminal and one of the COM terminals on the four position terminal strip located at the...

Страница 6: ...ng connections are according to job specifications before applying power Refer to Figure 7 for a sample multistage application if needed 2 Make the necessary adjustments and electrical connections 3 P...

Страница 7: ...m as indicated in Table 4 replace the A350E Table 4 A350E Relay Troubleshooting LED N O Relay Status Setpoint Dial Setting On Closed Ts Differential Off Open Ts Ts is sensed temperature For example 70...

Страница 8: ...Range 10 to 65 F 12 to 18 C Differential Adjustment Range 1 to 30F 0 6 to 16 7C SPDT Relay Output 120V 208 to 240V Horsepower 1 2 1 2 Full Load 9 8A 4 9A Locked Rotor 58 8A 29 4A Non Inductive 10A at...