line slaves synchronized to it. If the original master resumes control then the pseudo
master will resort back to slave mode.
Alarm Testing
The 520/MH sounders must be tested after installation, programming, battery replacement
and following any maintenance.
NOTE: Before testing, notify the proper authorities that
maintenance is being performed and the system will be temporarily out of service
.
A basic sounder test can be accomplished by performing the sound test described in this
manual. This test
does not
check for proper programming of zones to the sounder or
functionality of all circuitry. A full system test to activate the sounders via zones is mandatory
to test full functionality of the sounder.
To test the sounder perform the following:
1.
Activate an alarm from a device whose zone matches a zone programmed into the
sounder.
2.
Verify activation of the sounder and measure db output at the desired location.
3.
Verify the sounder operates for a minimum of 60 seconds.
4.
Verify no troubles are received from the sounder during the alarm test.
5.
Reset the control panel and verify the sounder silences.
6.
Verify no troubles are received from the sounder after the alarm test.
7.
Repeat the above for each sounder.
A failure of any sounder to successfully complete the alarm test should be checked and
repaired or replaced.
Low battery/Low battery2:
The model 520/MH periodically tests both the sounder driver and RF batteries for a low
battery condition. If a low battery is detected a trouble condition is transmitted and repeated
every 90 seconds. The RF and sounder batteries send two uniquely identified low battery
troubles. If the RF battery is low a low battery trouble will be present on the panel. If the
sounder driver batteries are low a low battery2 trouble signal will be present on the control
panel. If more than one type of trouble exists, all will be repeated in increments of 90 seconds.
Always replace the low battery with a new one. Refer to the Battery Installation and
Replacement section for instructions on battery replacement.
Battery Installation and Replacement:
Warning: Always install new battery/batteries of one of the approved types as listed in
the Specifications section of this manual and the product label. The RF and sounder
driver batteries are two different part numbers. Be sure to install the correct p/n battery
in the appropriate holder(s).
Observe correct polarity as marked in the battery holders.
To replace the battery:
1. Place the Control Panel in Test mode to prevent any unwanted alarms.
2. Remove the front of the 520/MH by removing the two closing screws then separate the
front and back starting at the top of the case. Lift off the front then remove the old battery/
batteries and dispose of properly.
3. To insure proper power down sequence, wait a minimum of 20 seconds before installing
a new battery.
4. Install new battery/batteries in the battery compartment following the polarity diagram
inside the compartment.
When replacing the sounder driver batteries always replace
both batteries with new ones.
A power up reset trouble signal should be indicated on the
Control Panel within 30 seconds. A tamper trouble will also be indicated if the front cover is
not attached to the base.
Note: When changing only the sounder driver batteries you must remove and reinstall
the RF battery after replacing the sounder driver batteries in order to reset the
lowbattery2 trouble signal from the memory of the 520/MH. The RF battery does not