background image

 

P/N IM-520/MH Rev. E 

1

 

*CWSI-IM-520MHE*

 

© 2017 Johnson Controls. All rights reserved. All specifications and other information 
shown were current as of document revision date and are subject to change without notice. 

 

 

 

 

 

Low Frequency Sounder Model 520(R)(W) 

Mini Horn Sounder Model MH(R)(W) 

 
Description: 

The Model 520 and MH are self-contained wireless audible notification devices which comply 
with UL464 and NFPA 72 when installed in accordance with this manual. The sounders are 
designed for use in sleeping areas as well as common areas within protected premises. The 
model 520 is a low frequency sounder capable of annunciating temporal 3 or 4 pattern and 
the MH is a piezo type sounder which produces the temporal 3 pattern. The 520/MH are fully 
supervised for tamper, low battery, output driver fault and RF signal integrity. The individual 
models can also be synchronized by interconnecting them.  The sounders are powered by 
3.6 volt lithium batteries as listed under the specifications section of this manual and the label 
on  the  product.  The  Models  520  and  MH  are  intended  to  be  used  with  CWSI  Fire  Alarm 
Control Panels. Refer to the control panel manual for compatibility details.  
 

Installation: 
The Model 520/MH must be installed and maintained in accordance with the National 
Fire Protection Association’s Standards (NFPA), the National Electrical Code and all 
local fire and electrical requirements. The 520/MH is to be installed in an indoor dry 
location. Exposure to weather or corrosive conditions may damage the unit. 

Locate  a  few  accessible  locations  that  are  not  prone  to  tampering  or  accidental  damage. 
Sound db output level, reliable RF signal, repeater depth and mounting method are important 
factors  when  deciding  on  an  installation  location.  Refer  to  the  individual  sections  in  this 
manual to perform the sound level and signal survey testing. 

Sound output level and RF 

signal survey tests must be conducted prior to and after mounting the product. 

Once 

successful sound and signal survey tests have been completed

 

the 520/MH can be mounted. 

Mounting options include single gang, dual gang, 

4” conduit box or surface mount directly to 

the  wall. When mounting directly to the  wall the  mounting surface should be relatively flat 
and  be  capable  of  accepting  screws  or  anchors.  Always  install  the  product  vertically 
observing the UP and arrow in the back box as shown in figure 1. Any other mounting position 
will result in tamper troubles on the control panel. Mount the product in the desired location 
then place the control panel in enrollment mode and install the batteries as shown in figure 
2. Refer to the control panel manual for enrollment procedures. Observe polarities marked 
on the battery holders. There is one battery for the RF circuitry and two for the sounder driver 
circuitry. The RF battery is p/n ER34615 and has a black line around the outside of the battery 
at the + terminal. The sounder driver batteries are p/n ER34615M and have a gold line around 
the outside of the battery at the + terminal. 

Warning: Always install a new battery of one 

of the approved types as listed in the Specifications section of this manual and the 
product label. 

Two short beeps will be emitted

 

from the sounder along with a power up reset 

trouble  showing  the  product  serial  number  at  the  control  panel  indicating  successful 
enrollment. Attach the front of the 520/MH to the back box by inserting the tabs on the bottom 
of the front into the slots on the back box then hinge the front closed and secure it with the 
two supplied screws (figure 3). Perform sound, RF signal and alarm tests as specified in this 
manual after installation is complete. 

Содержание 520

Страница 1: ...on an installation location Refer to the individual sections in this manual to perform the sound level and signal survey testing Sound output level and RF signal survey tests must be conducted prior to and after mounting the product Once successful sound and signal survey tests have been completed the 520 MH can be mounted Mounting options include single gang dual gang 4 conduit box or surface mou...

Страница 2: ... test will produce the temporal 3 pattern for 5 seconds to allow a db sound output measurement to be obtained at the desired location This test can be performed without the unit being enrolled into a panel or in a network making for a good tool for pre installation testing Loud Norm jumper 520 only The model 520 has an optional loud setting of the sound level output The J8 jumper can be selected f...

Страница 3: ...one or two beeps One beep indicates an unacceptable location and two beeps indicate an acceptable location If only one beep is heard then relocate the model 520 MH mounting position closer to the nearest repeater or control panel and perform the test again Continue this procedure until 2 beeps are achieved Do not mount the appliance detector unless 2 beeps are heard when performing 5 consecutive s...

Страница 4: ...thin one room Note Interconnection of models 520 and MH is not recommended as synchronization is not guaranteed between different models When connected together the sounders will synchronize their temporal 3 and 4 520 only patterns when multiple sounders are activated To achieve synchronization the sounders must be both correctly configured as master and slave s and wired together Master and slave...

Страница 5: ...and terminal 2 on the master should go to terminal 3 on the slave To connect more than one slave continue to wire from output to input slave to slave until the last one is connected Refer to figure 4 for the wiring diagram of interconnected sounders Problems with wiring or improper jumper settings will cause an EOL Config trouble at the control panel Check the wiring and jumper settings and correc...

Страница 6: ...y 90 seconds The RF and sounder batteries send two uniquely identified low battery troubles If the RF battery is low a low battery trouble will be present on the panel If the sounder driver batteries are low a low battery2 trouble signal will be present on the control panel If more than one type of trouble exists all will be repeated in increments of 90 seconds Always replace the low battery with ...

Страница 7: ...r The 520 MH contains a built in tilt switch that will cause a Tamper signal to be transmitted if the front cover of the sounder is removed A tamper signal is transmitted and repeated every 90 seconds until the front cover is put back into position Where more than one type of trouble exists all will be repeated in increments of 90 seconds Note The tamper trouble is self restoring on CP 3500D or ne...

Страница 8: ...l and NFPA 72 or local requirements Transmission In compliance with FCC part 15 Test Transmission Every 90 seconds Overall dimensions 8 25 x 5 5 x 2 5 Weight 19 2 oz without battery FCC Statement Important Any changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment This device complies with part 15 of the FCC ...

Отзывы: