835965-UIM-B-0413

4

Johnson Controls Unitary Products

The outdoor condensing unit must be connected to the indoor evapora-
tor coil using field supplied refrigerant grade copper tubing that is inter-
nally clean and dry. Units should be installed only with the tubing sizes
for approved system combinations as specified in tabular data sheet.
The charge given is applicable for total tubing lengths up to 15 feet. See
Application Data Part Number 247077 for installing tubing of longer
lengths and elevation differences.

PRECAUTIONS DURING LINE INSTALLATION

1. Install the lines with as few bends as possible. Care must be taken

not to damage the couplings or kink the tubing. Use clean hard
drawn copper tubing where no appreciable amount of bending
around obstruction is necessary. If soft copper must be used, care
must be taken to avoid sharp bends which may cause a restriction.

2. The lines should be installed so that they will not obstruct service

access to the coil, air handling system, or filter.

3. Care must also be taken to isolate the refrigerant lines to minimize

noise transmission from the equipment to the structure.

4. The vapor line must be insulated with a minimum of 1/2" foam rubber

insulation (Armaflex or equivalent). Liquid lines that will be exposed
to direct sunlight and/or high temperatures must also be insulated.

5. Tape and suspend the refrigerant lines as shown. DO NOT allow

tube metal-to-metal contact. See Figure 2 "Tubing Hanger".

6. Use PVC piping as a conduit for all underground installations as

shown in Figure 3 "Underground Installation". Buried lines should be
kept as short as possible to minimize the build up of liquid refrigerant
in the vapor line during long periods of shutdown

7. Pack fiberglass insulation and a sealing material such as permagum

around refrigerant lines where they penetrate a wall to reduce vibra-
tion and to retain some flexibility.

8. See application part number 247077 for additional piping informa-

tion.

PRECAUTIONS DURING BRAZING OF LINES

All outdoor unit and evaporator coil connections are copper-to-copper
and should be brazed with a phosphorous-copper alloy material such
as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units
have reusable service valves on both the liquid and vapor connections.
The total system refrigerant charge is retained within the outdoor unit
during shipping and installation. The reusable service valves are pro-
vided to evacuate and charge per this instruction.

Serious service problems can be avoided by taking adequate precau-
tions to ensure an internally clean and dry system.

PRECAUTIONS DURING BRAZING SERVICE VALVE

Precautions should be taken to prevent heat damage to service valves
by wrapping a wet rag around it as shown in Figure 4 "Heat Protection".
Also, protect all painted surfaces, insulation, and plastic base during
brazing. After brazing, cool joint with wet rag.

The valve can be opened by removing the plunger cap and fully insert-
ing a hex wrench into the stem and backing out counter-clockwise until
valve stem just touches the chamfered retaining wall.

Connect the refrigerant lines using the following procedure:

1. Refer to the Tabular Data Sheet for proper vapor and liquid line siz-

ing.

Using a larger than specified line size could result in oil return prob-
lems. Using too small a line will result in loss of capacity and other
problems caused by insufficient refrigerant flow. Slope horizontal
vapor lines at least 1" every 20 feet toward the outdoor unit to facili-
tate proper oil return.

 FIGURE 2:  

Tubing Hanger

NOTICE

LIQUID
LINE

INCORRECT

CORRECT

TAPE

SHEET METAL
HANGER

INSULATED
VAPOR LINE

 FIGURE 3:  

Underground Installation

 Dry nitrogen should always be supplied through the tubing while it
is being brazed, because the temperature is high enough to cause
oxidation of the copper unless an inert atmosphere is provided. The
flow of dry nitrogen should continue until the joint has cooled.
Always use a pressure regulator and safety valve to insure that only
low pressure dry nitrogen is introduced into the tubing. Only a small
flow is necessary to displace air and prevent oxidation.

This is not a backseating valve. The service access port has a
valve core. Opening or closing valve does not close service access
port.
 If the valve stem is backed out past the chamfered retaining wall,
the O-ring can be damaged causing leakage or system pressure
could force the valve stem out of the valve body possibly causing
personal injury.

Do not leave the system open to the atmosphere.  Unit damage
could occur due to moisture being absorbed by the POE oil in the
system.  This type of oil is highly susceptible to moisture absorp-
tion.

TO INDOOR

COIL

TO OUTDOOR

COIL

CAP

INSULATED
VAPOR LINE

LIQUID
LINE

PVC
CONDUIT

Содержание 16 Seer-AC6B Series

Страница 1: ...ing Diagram 24 LIST OF TABLES R 410A Saturation Properties 18 TEST Input Functionality 19 Operational Mode Display 19 Status Code Display 19 Status Code Display 19 Operational Fault Codes 20 Sensor or Switch Fault Codes 20 Wiring Related Fault Codes 20 SECTION I GENERAL The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines Sweat connect units are factory...

Страница 2: ...d layer of hot air into the outdoor unit Provide an adequate structural support ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 22 unit it is required that the outdoor unit indoor coil and metering device all be replaced Line set change out is also recommended The following steps should be performed in order to insure proper system operation and performance 1 Cha...

Страница 3: ...hraeder cap seal 3 Loosen and remove distributor cap seal 4 Install the thermal expansion valve to the orifice distributor assembly with supplied fittings Hand tighten and turn an additional 1 4 turn to seal Do not overtighten fittings 5 Install the liquid line to the top of the thermal expansion valve with fit ting supplied with the liquid line Hand modify the liquid line to align with casing ope...

Страница 4: ...tions The total system refrigerant charge is retained within the outdoor unit during shipping and installation The reusable service valves are pro vided to evacuate and charge per this instruction Serious service problems can be avoided by taking adequate precau tions to ensure an internally clean and dry system PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat d...

Страница 5: ...e the nitrogen source from the liquid fitting service port 9 Replace the Schrader core in the liquid and vapor valves 10 Leak test all refrigerant piping connections SECTION IV EVACUATION 1 It will be necessary to evacuate the system to 500 microns or less If a leak is suspected leak test with dry nitrogen to locate the leak Repair the leak and test again To verify that the system has no leaks sim...

Страница 6: ...cating Control 2 Route low voltage four conductor shielded thermostat communica tions harness into junction box and connect to communications port on control board See Figure 6 Communications Harness Connec tion 3 Route low voltage wiring into bottom of control box Make low volt age wiring connections inside the junction box per Figures 7 8 4 The complete connection diagram and schematic wiring la...

Страница 7: ...FM must be set properly Refer to the Technical Guide for the outdoor unit for the recommended air flow settings for each size condensing unit and matching indoor unit Set the cooling speed per the instructions for the air handler or furnace Verify the airflow If installed as a communicating system outdoor indoor and thermo stat the system will automatically adjust to the optimal airflow settings T...

Страница 8: ...PSHU PXVW EH VHW WR 6 1 67 5 21 7 21 5 9ROW RPPRQ 5 9ROW RW LUVW 6WDJH RPSUHVVRU 6HFRQG 6WDJH RPSUHVVRU 6 1 67 5 21 7 21 5 3DUW 1XPEHU 6 3 WHUQDO XPLGLVWDW 2SWLRQDO 2SHQ RQ XPLGLW 5LVH 3DUW 1XPEHU 6 8 LUVW 6WDJH RPSUHVVRU 20 9ROW RPPRQ 5 9ROW RW DQ 6HFRQG 6WDJH HDW 2 5HYHUVLQJ 9DOYH QHUJL HG LQ RRO 0DOIXQFWLRQ LJKW 80 XPLGLW 6ZLWFK 2SHQ RQ XPLGLW 5LVH 36 5 1 5 21752 6HFRQG RU XOO 6WDJH RPSUHVVRU L...

Страница 9: ...RPSUHVVRU 6 1 67 5 21 7 21 5 3DUW 1XPEHU 6 3 WHUQDO XPLGLVWDW 2SWLRQDO 2SHQ RQ XPLGLW 5LVH 3DUW 1XPEHU 6 8 9 XPLGLILHU 2SWLRQDO 9 OHFWURQLF LU OHDQHU 2SWLRQDO LUVW 6WDJH RPSUHVVRU 20 9ROW RPPRQ 5 9ROW RW DQ 6HFRQG 6WDJH HDW 2 5HYHUVLQJ 9DOYH QHUJL HG LQ RRO 0DOIXQFWLRQ LJKW 80 XPLGLW 6ZLWFK 2SHQ RQ XPLGLW 5LVH 9 5 63 5 1 5 21752 6HFRQG RU XOO 6WDJH RPSUHVVRU LUVW 6WDJH HDW 9 RXW OHFWURQLF LU OHDQH...

Страница 10: ... 6 6 1 67 5 21 7 21 5 9ROW RPPRQ 5 9ROW RW LUVW 6WDJH RPSUHVVRU 6HFRQG 6WDJH RPSUHVVRU 6 1 67 5 21 7 21 5 3DUW 1XPEHU 6 3 WHUQDO XPLGLVWDW 2SWLRQDO 2SHQ RQ XPLGLW 5LVH 3DUW 1XPEHU 6 8 9ROW RPPRQ 5 9ROW RW LUVW 6WDJH RPSUHVVRU 02 8 7 1 851 21752 DQ 02 8 7 1 851 6HFRQG RU XOO 6WDJH RPSUHVVRU 80 HKXPLGLILFDWLRQ 2SHQ RQ XPLGLW 5LVH 0RGXODWLQJ HDW 0RYH 80 67 7 MXPSHU WR 6 LI KXPLGLVWDW LV WR EH XVHG 2 ...

Страница 11: ...ise 2 Connection of the C terminal 24 Volt common is optional when used with batteries Thermostat Installer Setup 0170 System Type must be set to 8 2 Heat 2 Cool Multistage Conventional Connection of the C terminal 24 volt common is optional when used with batteries Thermostat Installer Setup 1 System Type must be set to 6 2 Heat 2 Cool Multistage Conventional Thermostat Installer Setup 15 Compres...

Страница 12: ... DHUM jumper to YES if humidistat is to be used G L 8 9 V F L 8 9 V PV 8 9 ID MODELS TWO STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor External Humidistat Optional Open on Humidity Rise 24VAC Humidifier Optional External Humidistat Optional Open on Humidity Rise 2 2 Part Number S1 2HU16700124 2 C 24 Volt Common R 24 Volt Hot Y First Stage...

Страница 13: ... Stage Compressor VARIABLE SPEED MODULATING FURNACE CONTROL G Fan VARIABLE SPEED MODULATING FURNACE Y Y2 Second or Full Stage Compressor HUM Dehumidification Open on Humidity Rise W Modulating Heat Part Numbers SAP Legacy 171334 031 09153 1 1 Move HUMIDISTAT jumper to YES if humidistat is to be used FL9C FC9C PC9 ID MODELS External Humidistat Optional Open on Humidity Rise 24VAC Humidifier Optiona...

Страница 14: ... 1 Move HUMIDISTAT jumper to YES if humidistat is to be used FL9C FC9C PC9 ID MODELS External Humidistat Optional Open on Humidity Rise 24VAC Humidifier Optional External Humidistat Optional Open on Humidity Rise 2 2 Part Number S1 2HU16700124 2 C 24 Volt Common R 24 Volt Hot Y First Stage Compressor Y2 Second Stage Compressor G Fan DN22C00124 THERMOSTAT W2 Second Stage Heat C 24 Volt Common R 24 ...

Страница 15: ...with batteries Thermostat Installer Setup 1 System Type must be set to 6 2 Heat 2 Cool Multistage Conventional COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in Cool X L Malfunction Light HUM Humidity Switch Open on Humidity Rise VARIABLE SPEED AIR HANDLER CONTROL G Fan VARIABLE S...

Страница 16: ...t Common is optional when used with batteries COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in Cool X L Malfunction Light HUM Humidity Switch Open on Humidity Rise VARIABLE SPEED AIR HANDLER CONTROL G Fan VARIABLE SPEED AIR HANDLER 1 AV ID MODELS SV MV EAC 24VAC out Electronic Ai...

Страница 17: ...on Properties 6 Subcooling temperature TC Saturated Temperature ST Liquid Temp T Add charge if the calculated subcooling temperature TC in Step 6 is lower than the recommended level Remove and recover the refrigerant if the subcooling TC is higher than the recommended level See Table 1 for R 410A saturation temperatures After disconnecting manifold gauge set check flare caps on service ports to be...

Страница 18: ... control includes a TEST input connector that can be used for vari ous testing functions during installation and service Table 2 summa rizes the behavior of the control when the two TEST pins are connected On 5 Ton unit the outdoor fan motor is a permanent magnet DC brushless type The motor requires a separate Electronic Control to operate Do not attempt to replace this motor with a typical PSC ty...

Страница 19: ...aster signals present Control behavior with system master signals present 2 No response No response 2 Display compressor type TS Ultratech or single stage compressor Ignore LPS Bypass ASCD Reduce timer to zero immediately If Y1 thermostat or communication is present and the high pressure switch is closed contactors will be energized Clear soft lockout Clear soft lockout Clear hard lockout Clear ha...

Страница 20: ...to be reset when the thermostat is satisfied or when the thermostat is set to SYSTEM OFF and back to HEAT or COOL mode 2 The TEST terminals are shorted for more than two seconds When the soft lockout condition is reset the control will stop displaying the fault code and will respond to thermostat inputs normally Hard Lockout If four soft lockouts occur within a twelve hour period the control will ...

Страница 21: ...is started following a high pressure switch fault the control will start a six hour timer based on accumulated compressor run time If the control senses another opening of the high pressure switch before the timer expires it will cause a soft lockout condition The second opening of the high pressure switch must be greater than 160 milliseconds for the lockout to occur If the second opening is betw...

Страница 22: ...835965 UIM B 0413 22 Johnson Controls Unitary Products SECTION IX WIRING DIAGRAM FIGURE 18 Single Stage Wiring Diagram 2 4 Ton ...

Страница 23: ...835965 UIM B 0413 Johnson Controls Unitary Products 23 FIGURE 19 Single Stage Wiring Diagram 5 Ton ...

Страница 24: ...835965 UIM B 0413 24 Johnson Controls Unitary Products NOTES ...

Страница 25: ...if applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas piping is connected if applicable Supply plenum and return ducts are connected and sealed Filter Size Vent system is connected if applicable Thermostat wiring complete Heat anticipator is set to the recommended va...

Страница 26: ...ner with the owner s manual Explain thermostat use and programming if applicable to owner Cycle Test Operate the unit through several heating cycles if applicable from the thermostat noting and correcting any problems Operate the unit through continuous fan cycles from the thermostat noting and correcting any problems Operate the unit through a cooling cycles noting and correcting any problems COO...

Отзывы: