JOHNSON CONTROLS
17
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
2
APPROVALS
Designed certified by ETL, CETL as follows:
1. For use as a forced air furnace with cooling unit
(gas heat models).
2. For outdoor installation only.
3. For installation on combustible material and may
be installed directly on combustible flooring or
Class A, Class B or Class C roof covering materi-
als.
4. For use with natural gas or LP.
5. When used with LP propane gas one of the fol-
lowing conversion kits must be installed before
the gas heat section is fired:
375,000 BTU Input - 385-01866-001
750,000 BTU Input - 385-01866-002
1,125,000 BTU Input - 385-01866-003
Not suitable for use with conventional venting systems.
LIMITATIONS
The installation of this unit must conform to local
building codes, or in the absence of local codes, with
ANSI 223.1 Natural Fuel Gas Code and /or CAN/CGA
B149 installation codes.
In U.S.A.:
1. National Electrical Code ANSI/NFPA No. 70 -
Latest Edition.
2. National Fuel Gas Code Z223.1 - Latest Edition.
3. Gas-Fired Central Furnace Standard ANSI Z21.47
- Latest Edition.
4. Local gas utility requirements.
Refer to Table 16 on page 37 for airflow and enter-
ing air/ambient conditions limitations, and Table 1 on
page 17 for voltage limitations.
TABLE 1 -
VOLTAGE LIMITATIONS
UNIT POWER
SUPPLY
VOLTAGE VARIATIONS
MIN. VOLTS
MAX. VOLTS
575-3-60
518
632
480-3-60
415
506
230-3-60
207
253
200-3-60
187
228
If the VAV boxes in the conditioned space
have hydronic heating coils installed, it is
the responsibility of the installing contrac-
tor to take appropriate measures to protect
the hydronic coils against low unit supply
air temperatures that could result in the
freeze up and rupture of the coils.
UNIT INSPECTION
Immediately upon receiving the unit, it should be in-
spected for possible damage, which may have occurred
during transit. If damage is evident, it should be noted
in the carrier’s freight bill. A written request for inspec-
tion by the carrier’s agent should be made at once.
See
“Instruction” manual, Form 50.15-NM for more infor-
mation and details.
To ensure warranty coverage, this equip-
ment must be commissioned and serviced
by an authorized Johnson Controls service
mechanic or a qualified service person
experienced in packaged rooftop instal-
lation. Installation must comply with all
applicable codes, particularly in regard to
electrical wiring and other safety elements
such as relief valves, HP cut-out settings,
design working pressures, and ventilation
requirements consistent with the amount
and type of refrigerant charge.
Lethal voltages exist within the control
panels. Before servicing, open and tag all
disconnect switches.
LOCATIONS AND CLEARANCES
General
The YORK YPAL air conditioning units are designed
for outdoor installation. When selecting a site for in-
stallation, be guided by the following conditions:
1. Unit must be installed on a level surface.
2. For the outdoor location of the unit, select a place
having a minimum sun exposure and an adequate
supply of fresh air for the condenser.
3. Also avoid locations beneath windows or between
structures.
4. Optional condenser coil protection should be used
for seashore locations or other harsh environments.
SECTION 2 – INSTALLATION
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...