JOHNSON CONTROLS
154
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
SECTION 8 – SERVICE
TABLE 43 -
HUMIDITY SENSOR OUTPUTS
%
RELATIVE
HUMIDITY
OUTPUT
VOLTAGE
VDC
%
RELATIVE
HUMIDITY
OUTPUT
VOLTAGE
VDC
5
0.25
55
2.75
10
0.50
60
3.00
15
0.75
65
3.25
20
1.00
70
3.50
25
1.25
75
3.75
30
1.50
80
4.00
35
1.75
85
4.25
40
2.00
90
4.50
45
2.25
95
4.75
50
2.50
100
5.00
CO
2
Sensor
Two CO
2
sensors are used in conjunction with the
“DE-
MAND VENTILATION”
option. In
“DEMAND VEN-
TILATION”
the Unit Control monitors the CO
2
level
of the outdoor air and the CO
2
level in the conditioned
space and varies the amount of ventilation air based on
the relationship between these two values.
gives the VDC output for a given CO
2
level.
Furnace Status Input
The Unit Controller monitors the operation of the
Staged Gas Heat section and displays the status through
the STATUS screen of the User Interface. The opera-
tion of each of the gas heat sections is monitored by a
multiplexer installed in the gas heat section. When a
gas heat section is energized, it sends a 24-volt signal
to the multiplexer. The multiplexer takes the five ON /
OFF inputs and converts them into a 0 to 5VDC signal
that is sent to the Unit Controller. The Unit Control-
ler then decodes this analog input and displays the fur-
nace section status.
shows the
relationship between the DC voltage and the furnace
operation status.
TABLE 41 -
PRESSURE TRANSDUCERS
SUCTION TRANSDUCER
DISCHARGE
TRANSDUCER
PRESSURE
PSIG
VOLTAGE
VDC
PRESSURE
PSIG
VOLTAGE
VDC
0
0.5
0
0.5
25
0.75
32.5
0.7
50
1
65
0.9
75
1.25
97.5
1.1
100
1.5
130
1.3
125
1.75
162.5
1.5
150
2
195
1.7
175
2.25
227.5
1.9
200
2.5
260
2.1
225
2.75
292.5
2.3
250
3
325
2.5
275
3.25
357.5
2.7
300
3.5
390
2.9
325
3.75
422.5
3.1
350
4
455
3.3
375
4.25
487.5
3.5
400
4.5
520
3.7
552.5
3.9
585
4.1
617.5
4.3
650
4.5
Humidity Sensors
The humidity sensor outputs a 0 to 5VDC in response to
the relative humidity sensed. An outdoor air humidity
sensor is used whenever the economizer is configured
for single or dual enthalpy. A return air humidity sensor
is used whenever the economizer is configured for dual
enthalpy. A humidity sensor is also used to monitor the
humidity in the space between the slab and raised floor
system used for FlexSys applications.
gives the relationship between the voltage output
of the humidity sensor and the % relative humidity.
TABLE 42 -
FURNACE STATUS INPUT STAGED GAS HEAT
MIN VOLTS DC
MAX VOLTS DC
FURNACE 1 STATUS FURNACE 2 STATUS FURNACE 3 STATUS
0.086
0.166
OFF
OFF
OFF
0.224
0.313
ON
OFF
OFF
0.361
0.461
OFF
ON
OFF
0.499
0.609
ON
ON
OFF
0.637
0.756
OFF
OFF
ON
0.774
0.904
ON
OFF
ON
0.912
1.051
OFF
ON
ON
1.050
1.199
ON
ON
ON
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...