JOHNSON CONTROLS
141
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
7
SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS
TABLE 36 -
DEFINITIONS
MENU ITEM
DEFINITION
ACCUMULATED UNOCCUPIED OVERRIDE TIME
This parameter gives the accumulated time the unit has placed in
unoccupied override mode.
ACTIVE ALARM
This identifies the number of active alarms present.
ADDRESS
This parameter is used to set the communication address for the unit
when connected to a network.
APS DATA
This parameter gives the status of the supply fan air proving switch.
0 = switch open, 1 = switch closed
BUILDING PRESSURE SETPOINT
This parameter establishes the building pressure setpoint for the
control of building exhaust operation.
BUILDING STATIC PRESSURE
This parameter gives the current value of the Building Static Pressure
input.
BUILDING STATIC PRESSURE SENSOR
INSTALLED
This parameter must be turned ON to enable the use of building
pressure in the operation of the exhaust function.
COMFORT VENTILATION FOR COOLING
ENABLED
This parameter must be turned ON to enabled COMFORT
VENTILATION during cooling mode operation on a Constant Volume
unit.
COMFORT VENTILATION FOR HEATING
ENABLED
This parameter must be turned ON to enable COMFORT
VENTILATION during heating mode operation on a Constant Volume
unit.
COMFORT VENTILATION LOWER SETPOINT
This parameter is the lower setpoint used by the Unit Controller to
determine when to switch the unit in COMFORT VENTILATION mode.
COMFORT VENTILATION UPPER SETPOINT
This parameter is the upper setpoint used by the Unit Controller to
determine when to switch the unit in COMFORT VENTILATION mode.
COMP 1 ASCD ACTIVE
This is used to determine the status of the off cycle timer. ON means
the compressor 1 is in this mode.
COMP 1 ASCD TIMER
This gives the actual time of the off cycle timer for compressor 1 in
seconds.
COMP 1 MIN RUN TIME
This gives the actual time of the minimum run time for compressor 1 in
seconds.
COMP 1 OUTPUT
This gives the status of the binary output from the Unit Controller to
compressor circuit 1.
COMP 1 OVERLOAD SWITCH
This is the status of the binary input from the compressor overload for
compressor system 1 to the Unit Controller. ON - okay, OFF - faulted.
COMP 2 ASCD ACTIVE
This is used to determine the status of the off cycle timer. ON means
the compressor 2 is in this mode.
COMP 2 ASCD TIMER
This gives the actual time of the off cycle timer for compressor 2 in
seconds.
COMP 2 MIN RUN TIME
This gives the actual time of the minimum run time for compressor 2 in
seconds.
COMP 2 OUTPUT
This gives the status of the binary output from the Unit Controller to
compressor circuit 2.
COMP 2 OVERLOAD SWITCH
This is the status of the binary input from the compressor overload for
compressor system 2 to the Unit Controller. ON - okay, OFF - faulted.
COMP 3 ASCD ACTIVE
This is used to determine the status of the off cycle timer. ON means
the compressor 3 is in this mode
COMP 3 ASCD TIMER
This gives the actual time of the off cycle timer for compressor 3 in
seconds.
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...