Johnson Controls Unitary Products S1-CD065T01 Скачать руководство пользователя страница 5

KNOB  A

COVER  B

BASE PLATE  D

DEHUMIDISTAT  C

ANCHOR  F (x2)

SCREW  E (x2)

BASE PLATE  D

CUT WIRES

4”-6” LENGTH

ONBOARD DEHUMIDISTAT WALL MOUNT INSTALLATION 
(FIGURE 12)

1.   Gently pull knob (A) from the dehumidistat cover (B). The cover is 

held in place by snap clips. Remove the cover by pulling carefully. 

Do not touch the sensing element on the dehumidistat (C).

2.   Remove 4 screws in base plate (D) and save for attaching the 

provided cover plate in place of the dehumidistat.

3.   Pull dehumidistat off unit until 4”- 6” of wire is outside of unit.
4.   Cut wires and use metal tape to secure leads to inside of unit, 

preventing contact with blower.

5.   Remove the gasket from the base plate. This will be used with the 

insulated cover plate installed in the next step. 

6.   Using the screws removed in Step 2, install the provided insulated 

cover plate with gasket over the dehumidistat opening on the unit.

7.   Remove the wiring access panel on unit outlet panel.
8.   Unplug the REMOTE terminals from the circuit board, remove the 

two wires and cut off bare leads. Once cut, the wires may remain 

in the unit.

9.   Run a 2-wire cable (18-22AWG) from the dehumidifier to the wall 

mount location. 

10.  Connect cable at the dehumidifier to the REMOTE terminals. Plug 

terminals into the circuit board and replace wiring access panel. 

See 

Figure 13

11.  Use the dehumidistat base as a template to mark mounting holes 

and wire access location on the wall.

12.  Drill two 3/16” holes at mounting locations and a 3/8” hole at 

desired wire access location.

13.  Pull 2-wire cable from the dehumidifier through the wire access 

opening in the wall.

14.  Strip wire ends coming from the dehumidistat and dehumidifier 

and connect with small, field supplied wire nuts.

15.  Push excess wire and wire nuts through the access hole in the 

wall. Use the supplied screws (E) and wall anchors (F) to attach 

the base plate (with dehumidistat) to the wall using the top 

centered hole and bottom centered slot.

16.  Reassemble dehumidistat cover by snapping in place on base 

plate and press on knob.

FIGURE 12 – Wall Mount

90-1466

FIGURE 13 – Dehumidistat to Unit Wiring

90-1465

5

Содержание S1-CD065T01

Страница 1: ...ION 1 Do not use in pool applications 2 If unit has been shipped or stored on its side wait 24 hours before running 3 Do not use solvents or cleaners on or near the circuit board P w c Airflow cfm 0 2...

Страница 2: ...inside wall of the living space Do not locate dehumidistat in the direct path of drafts from open doors and windows Do not install where operation might be affected by lamps outside sources of humidit...

Страница 3: ...ION OFF A COIL AIR IS PULLED FROM MAIN RETURN DUCT DEHUMIDISTAT WITH SET POINT KNOB CONDENSATE HOSE TO COMMON DRAIN OR OUTSIDE NOTE DO NOT BLOCK FURNACE ACCESS Figure 5 Basement Installation 90 1423 M...

Страница 4: ...f the unit is not wired to the HVAC system air is pulled through the unit dehumidified and circulated solely by the dehumidifier blower Wiring To HVAC System DEHUMIDIFIER CIRCUIT BOARD TERMINALS HVAC...

Страница 5: ...EMOTE terminals from the circuit board remove the two wires and cut off bare leads Once cut the wires may remain in the unit 9 Run a 2 wire cable 18 22AWG from the dehumidifier to the wall mount locat...

Страница 6: ...h the wiring access panel in the back of the dehumidifier see Figure 15 Remove the wiring access panel and pull the FLOAT SWITCH terminal block off the circuit board Remove the float switch jumper wir...

Страница 7: ...ressor do not activate 6 Check LED indicators Green should remain on If Red LED is on refer to the TROUBLESHOOTING GUIDE The red LED turns on when a fault condition is active Possible fault conditions...

Страница 8: ...t is not ducted to HVAC return install approximately 2 of 8 flex duct on inlet collar Vibration Install vibration isolators under dehumidifier feet Dehumidifier is producing hot air This is normal ope...

Отзывы: