5020803-UIM-C-0715
Johnson Controls Unitary Products
15
1. Airflow tested with dry coil conditions, without air filters, at 230 volts
2. Applications above 0.8" w.c. external static pressure are not recommended.
3. Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
4. Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
5. Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
Table 10:
Airflow - Bottom Duct Application
Model
Motor Speed
External Static Pressure (Inches WC)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
24
Low (1)
791
755
745
686
632
585
537
455
Low/Medium (2)
851
813
801
743
692
648
603
524
Medium (3)
938
905
890
836
788
745
702
623
Medium/High (4)
1069
978
969
921
872
830
787
713
High (5)
1207
1182
1185
1122
1106
1066
1023
952
30
Low (1)
768
730
720
659
604
555
508
424
Low/Medium (2)
943
911
900
847
800
759
716
641
Medium (3)
1039
1013
998
949
905
865
825
748
Medium/High (4)
1190
1099
1090
1048
1002
963
923
853
High (5)
1207
1182
1185
1122
1106
1066
1023
952
36
Low (1)
1127
1082
1021
952
889
825
759
689
Low/Medium (2)
1306
1265
1205
1154
1094
1029
963
892
Medium (3)
1354
1315
1259
1212
1153
1093
1024
990
Medium/High (4)
1397
1348
1297
1256
1195
1135
1077
1014
High (5)
1634
1591
1548
1497
1446
1382
1309
1250
42
Low (1)
1455
1414
1379
1335
1294
1254
1212
1160
Low/Medium (2)
1566
1532
1492
1455
1416
1372
1333
1280
Medium (3)
1565
1530
1491
1458
1419
1381
1336
1290
Medium/High (4)
1675
1641
1606
1578
1535
1495
1455
1412
High (5)
1946
1909
1863
1815
1771
1721
1654
1595
48
Low (1)
1598
1548
1502
1454
1410
1362
1307
1251
Low/Medium (2)
1663
1612
1568
1522
1476
1422
1370
1297
Medium (3)
1789
1733
1670
1650
1596
1578
1535
1483
Medium/High (4)
1931
1814
1808
1736
1673
1650
1597
1519
High (5)
2131
2058
1998
1949
1892
1840
1788
1728
60
Low (1)
1655
1612
1596
1531
1461
1462
1429
1391
Low/Medium (2)
1766
1720
1667
1629
1632
1539
1537
1498
Medium (3)
1987
1933
1861
1817
1820
1715
1725
1651
Medium/High (4)
2114
2050
2047
1974
1899
1889
1920
1866
High (5)
2369
2308
2249
2183
2126
2088
2034
1990
Table 11:
Electric Heat Minimum Supply Air
Model
Voltage
Minimum Blower Speed for Electric Heat
Heater kW
2
5
8
10
13
15
18
20
25
A24
208/230-1-60
Low #1 Low #1 Med. Low #2
Med. #3
Med. Hi #4
--
--
--
--
A30
208/230-1-60
Low #1 Low #1
Low #1
Med. Low #2
Med #3
High #5
--
--
--
B36
208/230-1-60
Low #1 Low #1
Low #1
Low #1
Med. Low #2
High #5
--
--
--
B42
208/230-1-60
--
Low #1
Low #1
Low #1
Low #1
Med. Low #2 Med. Hi #4
High #5
--
B48
208/230-1-60
--
Low #1
Low #1
Low #1
Low #1
Low #1
Med. Low #2 Med. High #4
--
B60
208/230-1-60
--
Low #1
Low #1
Low #1
Low #1
Low #1
Low #1
Med. Low #2 Med. High #4
Table 12:
Electric Heat Multipliers
Voltage
kW Capacity Multipliers
1
Nominal
Applied
240
208
0.75
230
0.92
1. Electric heaters are rated at nominal voltage. Use this table to determine
the electric heat capacity for heaters applied at lower voltages.