background image

5165699-BIM-C-0516

Johnson Controls Unitary Products

3

SECTION III: UNIT INSTALLATION

LOCATION

Access for servicing is an important factor in the location of any furnace.

Provide a minimum of 24” (61 cm) in front of the furnace for access to
the heating elements and controls. This access may be provided by a
closet door or by locating the furnace 24” (61 cm) from a facing wall or
partition.

FURNACE CLEARANCE

Electric furnace is approved for zero (0) in. clearance to combustible
material on all or any part of the furnace exterior and the inlet or outlet
duct work. For furnaces installed in upflow application, there must be
1” (2.54 cm) clearance from the outlet duct work for a distance of 3 feet
(91.4 cm) from the supply air opening.

RETURN AIR

In order for the furnace to work properly, a closet or alcove must have a
certain total free area opening for return air.

For Heating Only Furnace

Minimum 200 sq. in (1290 sq. cm) free area opening. Use any return
Grille with minimum 200 sq. in free opening.

For up to 4 Ton AC and 3.5 Ton HP Applications (Standard 
Blower)

Minimum 250 sq. in (1613 sq. cm) free area opening. The standard
blower assembly supplied with the furnace is capable of handling up 4
Ton AC and 3.5 Ton HP applications. Use any return grille with mini-
mum 250 sq. in (1613 sq. cm) free area opening.

For 5 Ton AC and 4 Ton HP Applications (Accessory 
Blower)

Minimum 350 sq. in (2129 sq. cm) free area opening. Use 5 Ton AC/4
Ton HP blower accessory 3500-7901/A. Use accessory louvered door
3501-9311 or any return grille with a minimum 350 sq. in (2129 sq. cm)
free area opening.

The return air opening can be located in a closet front door or a sidewall
above the furnace casing, or in a louvered door on the furnace. If open-
ing for the return air is located in the floor, side walls or closet door any-
where below furnace casing height, 6” (15.2 cm) minimum clearance
must be provided on the furnace side where return is located to provide
for proper air flow. See Figure 2. The 6” (15.2 cm) minimum clearance
is not required if there is a return grille installed above the furnace
height. This return grille cannot start more than three feet above the fur-
nace height.

For Upflow installations, a closet 32” (81.3 cm) wide by 30” (76.2 cm)
deep with a 30” (76.2 cm) wide door is necessary. See Figure 3. 

When installing furnace in a separate closet or room which is accessi-

ble only through an outside door, a minimum of 200 in

2

 (1290 cm

2

) free

opening for return air must be provided. The supply and return air must
be ducted, securely attached and be sealed to the furnace casing if
there are grilles in the outside door to the closet. Openings where ducts
pass through walls, the floor or the ceiling must be sealed to prevent air

leakage into or from closet and the living area.

Provisions shall be made to permit the return of circulating air from all
rooms and living spaces, except the bathroom(s) to the circulating air
supply inlet of the furnace. Failure to comply may cause improper heat-
ing and may cause the furnace to cycle on the limit.

DUCT SYSTEM DESIGN

Electric furnace is designed to operate at a given static pressure.

In order to assure proper air flow through the furnace, the distribution
system must be designed so that the static pressure external to the fur-
nace does not exceed the static pressure rating shown on the furnace
rating plate.

The number, size and placement of registers should be such that even
distribution of heat is provided throughout the home.

SECTION IV: DOWNFLOW FURNACE 

INSTALLATION 

7900 SERIES DUCT CONNECTOR

We have designed our duct connector to eliminate a sub-base require-
ment. Table 1 will help you in deciding the part number of the duct con-
nector you need.

Provide adequate clearance for servicing.

1.

Locate furnace conveniently away from wall facing or partitions to
permit easy removal of components.

2.

A six (6) inch space minimum should be maintained between the

furnace and closet door when door is used for return air.

3.

Two (2) feet of space must be available in front of furnace for
future servicing (blower, element or furnace removal, etc.).

 FIGURE 2:  

Upflow Closet Clearances

30”

32”

30”

Wide Door

Closet

25-1/2””

Return Air
Pass Through
Frame Width

1-5/8” Min., 2-3/8 Max.

Содержание EB10F

Страница 1: ...mance 7 Electrical Data 7 SECTION I GENERAL The following list includes important facts and information regarding the EB furnace and its packaging inclusions 1 Furnace is rated at 240 volts 60 Hz single phase 2 Filters are furnished with each model and are the same for all models 16 x 20 x 1 in top and 20 x 20 x 1 in the louvered door 3 Furnace size is the same for all models See Figure 1 4 Four w...

Страница 2: ...stalling and servicing heating cooling equipment can be hazard ous due to the electrical components Only trained and qualified personnel should install repair or service heating cooling equip ment Untrained service personnel can perform basic maintenance functions such as cleaning and replacing the air filters When working on heating cooling equipment observe precautions in the manuals and on the ...

Страница 3: ...s not required if there is a return grille installed above the furnace height This return grille cannot start more than three feet above the fur nace height For Upflow installations a closet 32 81 3 cm wide by 30 76 2 cm deep with a 30 76 2 cm wide door is necessary See Figure 3 When installing furnace in a separate closet or room which is accessi ble only through an outside door a minimum of 200 ...

Страница 4: ... floor opening See Figure 6 TABLE 1 Duct Connector for Electric Furnaces FLOOR TO DUCT DIMENSIONS FINGERED STYLE SCREW TAB STYLE 1 2 54 cm 7990 6211 7990 6011 2 5 1 cm 7990 6221 7990 6021 3 7 6 cm 4 10 2 cm 7990 6241 7990 6041 5 12 7 cm 6 15 2 cm 7990 6261 7990 6061 7 17 8 cm 7990 6271 7990 6071 8 20 3 cm 7990 6281 7990 6081 9 22 8 cm 10 25 4 cm 7990 6301 7990 6101 11 282 cm 12 30 5 cm 7990 6321 7...

Страница 5: ...width ducts there will not be suf ficient clearance to bend the tabs on two sides of the duct connector In such cases the tabs may be attached to the sides of the duct by using sheet metal screws or other suitable fasteners Holes for sheet metal screws are provided in three 3 tabs on each side of the duct connector If more than 3 tabs need to be used to provide a more secure and air tight connecti...

Страница 6: ...hed under the casing flange and screws provided can be used to capture the other end of duct con nector Secure collar to top of furnace 10 The flange plate shipped with kit 3500 7211 is mounted to the fur nace using eight 8 screws supplied with kit 3500 8961A Two blunt screws should be used to secure the front edge of flange plate to furnace See Figure 11 11 Secure the top of the furnace to a stru...

Страница 7: ... 50 0 59 2 58 4 Minimum Wire Size 90ºC 8 10 6 10 8 8 6 6 Minimum Wire Size 75ºC 6 10 6 10 6 8 6 6 Minimum Wire Size 60ºC 6 10 4 10 6 6 4 4 Ground Wire Size 4 4 Refer to National Electrical Code Table 250 122 for Non Sheathed Conductor Ground Wire 10 10 10 10 10 10 10 10 Max Fuse or C B Amps 60 30 60 30 60 50 60 60 TABLE 3 EB Series Blower Performance Static Pressure inches of w c 0 0 0 1 0 2 0 3 0...

Страница 8: ...FORMER LIMIT SWITCHES GROUND LUGS 3500 378P JUMPER BARS FOR SINGLE BRANCH CIRCUIT SERVICE THERMOSTAT WIRES CIRCUIT BREAKERS SEQUENCERS NOTE As Shipped the jumper bar assembly is set up for bottom entry For side entry the top lug can be removed and re positioned as shown to provide proper wire bending clearances A0345 001 0 6 F F O N O N O F F O 0 6 WARNING For personal safety be sure to turn the e...

Страница 9: ...tallation instructions packed with the accessory package for more information FIGURE 15 Thermostat Wiring DELUXE BLEND AIR II FRESH AIR FRESH AIR OFF AUTO ALARM RED RED WHITE WHITE GREEN GREEN BLACK B L A C K BLACK RED WHITE GREEN Y E LL O W WIRES FROM FURNACE NOT FACTORY INSTALLED STANDARD OR DELUXE BLEND AIR CONTROL BOX THERMOSTAT WIRING SCHEMATIC FOR BLEND AIR AND FURNACE The EB Furnaces are A ...

Страница 10: ...F L REPLACE FILTER WITH SAME SIZE 240 VAC 60 Hz 1 PHASE NOTE 4 SPEED BLOWER EB SERIES FURNACES GRN WHT M4 H1 YEL L L YEL YEL SINGLE BRANCH CIRCUIT SERVICE 240 VAC 60Hz 1 PHASE GND LUG DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT OFF AT HOUSEHOLD SERVICE BOX CHECK WITH A VOLTMETER OR OTHER PROPER INSTRUMENT HAZARD OF ELECTRICAL SHOCK SERVICE CONNECTION COVER MUST BE INSTALLED IF FILTERS AR...

Страница 11: ... F L REPLACE FILTER WITH SAME SIZE 240 VAC 60 Hz 1 PHASE NOTE 4 SPEED BLOWER EB SERIES FURNACES GRN WHT M4 H1 YEL L L YEL YEL SINGLE BRANCH CIRCUIT SERVICE 240 VAC 60Hz 1 PHASE GND LUG THIS FURNACE MAY BE CONNECTED TO MORE THAN ONE POWER SUPPLY TURN OFF ALL POWER TO THE FURNACE AT THE WALL BOX AND LOCK IT OUT DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT OFF AT HOUSEHOLD SERVICE BOX CHECK ...

Страница 12: ...LL BOX AND LOCK IT OUT DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT OFF AT HOUSEHOLD SERVICE BOX CHECK WITH A VOLTMETER OR OTHER PROPER INSTRUMENT HAZARD OF ELECTRICAL SHOCK SERVICE CONNECTION COVER MUST BE INSTALLED IF FILTERS ARE USED CLEAN REPLACE EACH SEASON OR MORE OFTEN IF NEEDED CAUTION IMPORTANT HIGH VOLTAGE WARNING IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLA...

Страница 13: ... POWER TO THE FURNACE AT THE WALL BOX AND LOCK IT OUT DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT OFF AT HOUSEHOLD SERVICE BOX CHECK WITH A VOLTMETER OR OTHER PROPER INSTRUMENT HAZARD OF ELECTRICAL SHOCK SERVICE CONNECTION COVER MUST BE INSTALLED IF FILTERS ARE USED CLEAN REPLACE EACH SEASON OR MORE OFTEN IF NEEDED CAUTION IMPORTANT HIGH VOLTAGE WARNING IF ANY OF THE ORIGINAL WIRE SUPPLI...

Страница 14: ...LL POWER TO THE FURNACE AT THE WALL BOX AND LOCK IT OUT DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT OFF AT HOUSEHOLD SERVICE BOX CHECK WITH A VOLTMETER OR OTHER PROPER INSTRUMENT HAZARD OF ELECTRICAL SHOCK SERVICE CONNECTION COVER MUST BE INSTALLED IF FILTERS ARE USED CLEAN REPLACE EACH SEASON OR MORE OFTEN IF NEEDED CAUTION IMPORTANT HIGH VOLTAGE WARNING IF ANY OF THE ORIGINAL WIRE SUPP...

Страница 15: ...ARS P N 3500 378 NOTE 4 SPEED BLOWER EB SERIES FURNACES GRN WHT M4 H1 M7 M8 RED R L SHOCK HAZARD THIS FURNACE MAY BE CONNECTED TO MORE THAN ONE POWER SUPPLY TURN OFF ALL POWER TO THE FURNACE AT THE WALL BOX AND LOCK IT OUT DO NOT OPEN THIS PANEL UNTIL ELECTRICAL POWER IS SHUT OFF AT HOUSEHOLD SERVICE BOX CHECK WITH A VOLTMETER OR OTHER PROPER INSTRUMENT HAZARD OF ELECTRICAL SHOCK SERVICE CONNECTIO...

Страница 16: ... change without notice Published in U S A 5165699 BIM C 0516 Copyright 2016 by Johnson Controls Inc All rights reserved Supersedes 5165699 BIM B 0316 York International Corp 5005 York Drive Norman OK 73069 NOTES ...

Отзывы: