Johnson & Starley HI-SPEC J40 Скачать руководство пользователя страница 1

1

Air Filter

2

Air circulating fan

3

Heat exchanger access cover

4

Data plate

5

Time Control

6

Multifunctional Control

7

Fan Delay Control /Limit Switch

8

Pilot Burner

9

Burner Assembly

10

Gas connection

11

Heat shield

12

Piezo igniter unit

13

Spillage monitoring Device (TTB)

This appliance has been tested and certified by B G Technology for use with natural gas G20.

Note:

If an ELJAN 6 circulator is fitted, the relevant Installation, Commissioning and Servicing instructions provided with that

appliance must also be observed.

1.

BRIEF DESCRIPTION

HI-SPEC J40 WARM AIR HEATER

SYSTEM E-T and Conventional Control

INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS

G.C. No 42 451 09

Publication No. ZZ 815/9.

October 2006

1

2

1

Fig. 1

1.1

HI-SPEC J40 is an open-flued, fan assisted downflow, ducted warm air heater, which may be supplied with SYSTEM E-T
or BASIC control. An ELJAN 6 circulator is available as an option. A Spillage Monitoring Device (TTB) is fitted
which senses the temperature in the draught diverter, and shuts down the appliance when this temperature rises due to the
presence of flue gases.

1.2

The Air heater output can be adjusted between 8.8kW (31.65MJ/h, 30,000Btu/h) and 11.2kW (42.2MJ/h, 40,000Btu/h) .
“Summer air circulation” of unheated air is available by manual selection (see User’s Instructions). ELJAN 6 output is
3.32kW (11.5MJ/h, 11,340Btu/h).

THIS APPLIANCE CONFORMS TO BS EN 45014

3

5

7

13

6

9

8

11

4

10

12

Johnson and Starley prides itself on its ability to supply spare parts quickly and efficiently. If you have a problem in
obtaining a spare part, please contact Johnson and Starley Spares Department at the address below.

JOHNSON & STARLEY LTD.

Telephone:

(01604) 762881

Rhosili Road,

Brackmills,

 Fax:

(01604)  767408

    Northampton NN4 7LZ

Содержание HI-SPEC J40

Страница 1: ...ssisted downflow ducted warm air heater which may be supplied with SYSTEM E T or BASIC control An ELJAN 6 circulator is available as an option ASpillage Monitoring Device TTB is fitted which senses th...

Страница 2: ...lication 3 VENTILATIONAND COMBUSTIONAIR 3 1 The room or internal space in which the heater is installed requires a permanent air vent of minimum effective area 62cm2 9in2 The air vent should be either...

Страница 3: ...iser ducts should be fully insulated with 50mm 2in fibreglass or similar If short extended duct runs are taken below floor level these should be similarly insulated and in addition wrapped with a soun...

Страница 4: ...m equivalent vertical height is 1 metre The installer must make a judgement based on his knowledge and experience and the examination and testing described above as to whether an existing flue system...

Страница 5: ...ance Inlet Flue Outlet Resistance Ki Resistance Ko 100 mm dia spigot 2 5 100 mm flue 2 5 125 mm dia spigot 1 0 125 mm flue 1 0 150 mm dia spigot 0 48 150 mm flue 0 48 Table 3 Inlet and outlet resistan...

Страница 6: ...rminal is specifically recommended The latter should be positioned in a free air space where it is not shielded by any structure A minimum of 1m 3ft from any vertical or inclined roof structure must b...

Страница 7: ...at d BASIC MODELS A24V room thermostat not supplied that complies with BS 800 BS 3955 and BS4201 is essential to ensure close control of comfort conditions An anticipator is located within the thermos...

Страница 8: ...ATING CONTROL is fully reset Wait three minutes and repeat steps 6 3 4 and 6 3 5 holding the OPERATING CONTROL depressed for a longer period until the Pilot burner remains alight 6 3 6 With the Pilot...

Страница 9: ...and allow 15 minutes for stability before continuing 6 6 2 Check the temperature rise across heater is between 45o C 55o C setting the fan speed as follows i SYSTEM E T heaters System E T provides a...

Страница 10: ...t exchanger b Extinguish the Main and Pilot burners c Ensure that there is no spillage evident by visually observing the draught diverter location on the air heater d If spillage is evident further in...

Страница 11: ...ow to operate the Thermista stat room thermostat time and heater ON OFF switch and summer air circulation switch and that the time control must be reset following a power failure 7 2 3 How to extingui...

Страница 12: ...and with the main burner lit ensure that the operation of Air Circulation fan does not affect the main burner flame profile 8 2 BURNERAND CONTROLASSEMBLYREMOVAL 8 2 1 Ensure that the Gas and Electric...

Страница 13: ...minals 16 N and 15 L g Water heater from connection block terminals 10 L and 9 N h Water Pump from connection block terminals 12 L and 11 N i Cleanflow from connection block terminals 19 24V and 20 0V...

Страница 14: ...8 13 6 Refitting or replacement is in reverse order 8 14 SPILLAGE MONITORING DEVICE TTB REMOVAL 8 14 1 Ensure that the electrical supply is isolated 8 14 2 Remove the appliance louvre door release th...

Страница 15: ...8 13 6 Refitting or replacement is in reverse order 8 14 SPILLAGE MONITORING DEVICE TTB REMOVAL 8 14 1 Ensure that the electrical supply is isolated 8 14 2 Remove the appliance louvre door release th...

Страница 16: ...minals 16 N and 15 L g Water heater from connection block terminals 10 L and 9 N h Water Pump from connection block terminals 12 L and 11 N i Cleanflow from connection block terminals 19 24V and 20 0V...

Страница 17: ...and with the main burner lit ensure that the operation of Air Circulation fan does not affect the main burner flame profile 8 2 BURNERAND CONTROLASSEMBLYREMOVAL 8 2 1 Ensure that the Gas and Electric...

Страница 18: ...ow to operate the Thermista stat room thermostat time and heater ON OFF switch and summer air circulation switch and that the time control must be reset following a power failure 7 2 3 How to extingui...

Страница 19: ...t exchanger b Extinguish the Main and Pilot burners c Ensure that there is no spillage evident by visually observing the draught diverter location on the air heater d If spillage is evident further in...

Страница 20: ...and allow 15 minutes for stability before continuing 6 6 2 Check the temperature rise across heater is between 45o C 55o C setting the fan speed as follows i SYSTEM E T heaters System E T provides a...

Страница 21: ...ATING CONTROL is fully reset Wait three minutes and repeat steps 6 3 4 and 6 3 5 holding the OPERATING CONTROL depressed for a longer period until the Pilot burner remains alight 6 3 6 With the Pilot...

Страница 22: ...at d BASIC MODELS A24V room thermostat not supplied that complies with BS 800 BS 3955 and BS4201 is essential to ensure close control of comfort conditions An anticipator is located within the thermos...

Страница 23: ...rminal is specifically recommended The latter should be positioned in a free air space where it is not shielded by any structure A minimum of 1m 3ft from any vertical or inclined roof structure must b...

Страница 24: ...ance Inlet Flue Outlet Resistance Ki Resistance Ko 100 mm dia spigot 2 5 100 mm flue 2 5 125 mm dia spigot 1 0 125 mm flue 1 0 150 mm dia spigot 0 48 150 mm flue 0 48 Table 3 Inlet and outlet resistan...

Страница 25: ...m equivalent vertical height is 1 metre The installer must make a judgement based on his knowledge and experience and the examination and testing described above as to whether an existing flue system...

Страница 26: ...iser ducts should be fully insulated with 50mm 2in fibreglass or similar If short extended duct runs are taken below floor level these should be similarly insulated and in addition wrapped with a soun...

Страница 27: ...lication 3 VENTILATIONAND COMBUSTIONAIR 3 1 The room or internal space in which the heater is installed requires a permanent air vent of minimum effective area 62cm2 9in2 The air vent should be either...

Страница 28: ...ssisted downflow ducted warm air heater which may be supplied with SYSTEM E T or BASIC control An ELJAN 6 circulator is available as an option ASpillage Monitoring Device TTB is fitted which senses th...

Отзывы: