background image

6

19

6.3

IGNITION OF PILOT AND MAIN BURNERS:
WARNING:  

If the pilot burner is extinguished either intentionally or unintentionally, no attempt should be made to

relight the gas for a minimum of 3 minutes. Ensure that the Electrical supply, time control and Selector switches  are set
to 

‘OFF’.

6.3.1

Set the Thermista-stat/room thermostat to lowest or 

OFF

 setting.

6.3.2

On the Multifunctional control, remove the Outlet Pressure test point cover, and fit a pressure test gauge (refer
Fig. 4).

6.3.3

Turn the heater Gas supply 

ON

, test for gas soundness and purge the whole gas pipe as described in BS6891.

6.3.4

Referring to Fig. 4,  partially depress the OPERATING CONTROL and set the control 

1

/

4

 turn anti-clockwise  to

the ‘SPARK’ symbol. Press and hold the OPERATING CONTROL, and whilst observing the Pilot Burner,
repeatedly press the Piezo igniter button until the Pilot burner ignites.

6.3.5

After 20 seconds release the OPERATING CONTROL and let it spring out; ensure that the Pilot burner remains
alight. If the Pilot burner extinguishes, rotate the OPERATING CONTROL clockwise to the ‘

’ position and

ensure that the OPERATING CONTROL is fully reset. Wait three minutes and repeat steps 6.3.4 and 6.3.5,
holding the OPERATING CONTROL depressed for a longer period, until the Pilot burner remains alight.

6.3.6

Ensure that the pilot flame envelops thermocouple tip, if not, check that the pilot orifices is free from
obstruction. The pilot is factory set and is non-adjustable.

6.3.7

With the Pilot burner lit, depress the OPERATING CONTROL and turn it to the position indicated by the flame
symbol.

6.3.8

Set the air heater Electricity supply 

ON

.

6.3.9

Set the Time control to required Heating On periods.

6.3.9

Set the Selector switch to ‘TIMED’.

6.3.10 Set the Thermista-stat or room thermostat to MAXIMUM.

6.3.11 Ensure that the main burner has now ignited.

6.3.12 Test for gas leakage at the supply, Multifunctional control, Pilot and Main burners using proprietary detection

fluid and sealing any leaks found.

6.3.13 Allow the heater to operate for a minimum of 15 minutes to ensure stability.

6.4

MAIN BURNER PRESSURE TEST:

NOTE: AIR HEATER BURNERS ARE FACTORY SET TO PROVIDE A NOMINAL HIGH PRESSURE OUTPUT AS
DETAILED IN SUB PARA 1.2

6.4.1

Referring to Table 2 and Fig. 4 below, ensure that the pressure test gauge indicates the correct burner pressure,
resetting if required as follows:
a.

At the Multifunctional control:
i.

Remove the Burner Pressure Adjuster cover.

ii.

Set the Burner Pressure Adjuster to provide a pressure test gauge indication for the correct burner
pressure as detailed in Table 2.

iii.

Refit the Burner Pressure Adjuster cover.

6.4.2

Apply the pressure set arrow to indicate the appropriate burner pressure on the data badge.

6.5

EXTINGUISHING OF PILOT AND MAIN BURNERS:

6.5.1

On the Multifunctional control, rotate the OPERATING CONTROL clockwise  to the ‘

’  position and ensure that

the OPERATING CONTROL fully resets, and both the Pilot and Main Burners are extinguished.

6.5.2

On the Multifunctional control, remove the pressure test gauge and refit the Outlet Pressure test point cover.

6.6

TEMPERATURE RISE CHECKS:

6.6.1

Ignite the Pilot and Main burners and allow 15 minutes for stability before continuing.

6.6.2

Check that the temperature rise across the heater is between 45

o

C - 55

o

C, setting the fan speed as follows:

i.

SYSTEM E-T heaters:  System E-T provides a fan speed corresponding to the above temperature rise, if

the appliance is to be set to operate at the minimum rate and the ducting has been sized accordingly, set

the ‘RATE SWITCH’ to ‘

MIN

’, thus reducing the fan speed.

ii

BASIC Control heaters, the fan speed is adjusted by selecting the fan speed at control panel
(decrease voltage selection to decrease fan speed).

Fig. 6a, SYSTEM E-T FUNCTIONAL DIAGRAM

r

Содержание HI-SPEC J25SC Series

Страница 1: ...PARES HI SPECJ25SC KEY G CNo MFR SNo DESCRIPTION QTY 1 BOS02064SP Fan Assembly 1 2 T193 0145000 FilterAssembly 1 3 378466 BOS02031 Time Control 1 4 381627 1000 0701140 Multifunctional Control 1 5 2329...

Страница 2: ...ent must be not less than 75mm 3 in However if clearances are less than 75mm the internal surface of the compartment must be lined with non combustible material The compartment must be of a fixed rigi...

Страница 3: ...he air filter front cover and the air circulation fan 5 1 2 Cut a hole in the chosen side of the fan compartment The knock outs will determine the size and position 5 1 3 Remove and the filter frame r...

Страница 4: ...5 4 4 Apply a suitable mastic not provided to the spigot flanges and insert them into their respective apertures and seal them to the face of the SE duct wall 5 4 5 Position the larger rope ring seal...

Страница 5: ...door or windows or on an outside wall iii Where affected by warm air ducts diffusers waste pipes or the heater itself iv Where subject to vibration c Connect Thermista stat Room thermostat wires to c...

Страница 6: ...MAXIMUM 6 3 11 Ensure that the main burner has now ignited 6 3 12 Test for gas leakage at the supply Multifunctional control Pilot and Main burners using proprietary detection fluid and sealing any le...

Страница 7: ...ch OFF the electrical supply to the air heater 6 8 3 Release the securing screw and hinge down the fan chamber door 6 8 4 Disconnect the air circulation fan as follows a System E T models disconnect t...

Страница 8: ...s etc Outlet faces may require partial blanking in order to achieve this 6 9 3 Set the SUMMERAIRFLOW switch to O 6 9 4 Ignite the Pilot and Main burners as detailed in sub paras 6 3 4 to 6 3 7 6 9 5 S...

Страница 9: ...arry out a complete functional test of the appliance in accordance with Commissioning Instructions at Sect 6 1 to 6 8 inclusive Replace any sealing gasket or insulation that is damaged before re commi...

Страница 10: ...Thermocouple lock nut from the Pilot Burner Assembly and Multifunctional Control and withdraw the Thermocouple taking care to avoid damage to the capillary 8 5 3 Release the Igniter electrode lock nut...

Страница 11: ...0 3 Disconnect terminals 21 to 33 from the Electronic module 8 10 4 Release the 2 x screws and nuts securing Electronic module to Electrical assembly and remove module 8 10 5 Refitting or replacement...

Страница 12: ...YSTEM E T models a When carrying out any electrical testing a test meter MUST be used since low resistance test devices can cause damage to the Electronics module b Before commencing defect diagnosis...

Страница 13: ...YSTEM E T models a When carrying out any electrical testing a test meter MUST be used since low resistance test devices can cause damage to the Electronics module b Before commencing defect diagnosis...

Страница 14: ...0 3 Disconnect terminals 21 to 33 from the Electronic module 8 10 4 Release the 2 x screws and nuts securing Electronic module to Electrical assembly and remove module 8 10 5 Refitting or replacement...

Страница 15: ...Thermocouple lock nut from the Pilot Burner Assembly and Multifunctional Control and withdraw the Thermocouple taking care to avoid damage to the capillary 8 5 3 Release the Igniter electrode lock nut...

Страница 16: ...arry out a complete functional test of the appliance in accordance with Commissioning Instructions at Sect 6 1 to 6 8 inclusive Replace any sealing gasket or insulation that is damaged before re commi...

Страница 17: ...s etc Outlet faces may require partial blanking in order to achieve this 6 9 3 Set the SUMMERAIRFLOW switch to O 6 9 4 Ignite the Pilot and Main burners as detailed in sub paras 6 3 4 to 6 3 7 6 9 5 S...

Страница 18: ...ch OFF the electrical supply to the air heater 6 8 3 Release the securing screw and hinge down the fan chamber door 6 8 4 Disconnect the air circulation fan as follows a System E T models disconnect t...

Страница 19: ...MAXIMUM 6 3 11 Ensure that the main burner has now ignited 6 3 12 Test for gas leakage at the supply Multifunctional control Pilot and Main burners using proprietary detection fluid and sealing any le...

Страница 20: ...door or windows or on an outside wall iii Where affected by warm air ducts diffusers waste pipes or the heater itself iv Where subject to vibration c Connect Thermista stat Room thermostat wires to c...

Страница 21: ...5 4 4 Apply a suitable mastic not provided to the spigot flanges and insert them into their respective apertures and seal them to the face of the SE duct wall 5 4 5 Position the larger rope ring seal...

Страница 22: ...he air filter front cover and the air circulation fan 5 1 2 Cut a hole in the chosen side of the fan compartment The knock outs will determine the size and position 5 1 3 Remove and the filter frame r...

Страница 23: ...ent must be not less than 75mm 3 in However if clearances are less than 75mm the internal surface of the compartment must be lined with non combustible material The compartment must be of a fixed rigi...

Страница 24: ...PARES HI SPECJ25SC KEY G CNo MFR SNo DESCRIPTION QTY 1 BOS02064SP Fan Assembly 1 2 T193 0145000 FilterAssembly 1 3 378466 BOS02031 Time Control 1 4 381627 1000 0701140 Multifunctional Control 1 5 2329...

Отзывы: