6

6.

COMMISSIONING

6.1

PREPARATION:

6.1.1

Ensure that:

a.

Gas and Electrical supplies are 

OFF.

b.

Filter, fan and fan compartments are free from obstructions.

c.

All registers or grilles are open and conform to design specifications.

d.

Return, relief and ventilation air installations are adequate.

6.2

SETTING OF FAN SPEED:

6.2.1

Remove the air filter and fan chamber door.

SYSTEM E-T MODELS:  

On the electronic control module, set:

6.2.2

Rate Switch to ‘

MAX

’,

6.2.3

Cleanflow switch to ‘

1

’ if a Cleanflow electronic air cleaner is fitted, otherwise set to ‘

0

’.

6.2.4

Refit the fan chamber door and air filter.

6.3

IGNITION OF PILOT AND MAIN BURNERS:
WARNING:  

If the pilot light is extinguished either intentionally or unintentionally, no attempt should be made to

relight the gas for a minimum of 3 minutes. Ensure that the Electrical supply, time control and Selector switches  are set
to 

‘OFF’

.

6.3.1

Set the Thermista-stat/room thermostat to lowest or 

OFF

 setting.

6.3.2

On the Multifunctional control, remove the Outlet Pressure test point cover, and fit a pressure test gauge (refer
Fig. 4).

6.3.3

Turn the heater Gas supply 

ON

, test for gas soundness and purge the whole gas pipe as described in BS6891.

6.3.4

Referring to Fig. 4,  partially depress the OPERATING CONTROL and set the control 

1

/

4

 turn anti-clockwise to

the ‘SPARK’ symbol. Press and hold the OPERATING CONTROL, and whilst observing the Pilot Burner,
repeatedly press the Piezo igniter button until the Pilot burner ignites.

6.3.5

After 20 seconds release the Multifunctional control OPERATING CONTROL and let it spring out; ensure that
the Pilot burner remains alight. If the Pilot burner extinguishes, rotate the Multifunctional control OPERATING
CONTROL clockwise to the ‘

l

 ’ position and ensure that the OPERATING CONTROL is fully reset. Wait three

minutes and repeat steps 6.3.4 and 6.3.5, holding the OPERATING CONTROL depressed for a longer period, until
the Pilot burner remains alight.

6.3.6

Ensure that the pilot flame envelops thermocouple tip, if not, check that the pilot orifices is free from
obstruction. The pilot is factory set and is non-adjustable.

6.3.7

With the Pilot burner lit, depress the OPERATING CONTROL and turn it to the position indicated by the flame
symbol.

6.3.8

Set the air heater Electricity supply 

ON.

6.3.9

Set the Time control to required Heating On periods.

6.3.9

Set the Selector switch to ‘TIMED’.

6.3.10 Set the Thermista-stat or room thermostat to MAXIMUM.

6.3.11 Ensure that the main burner has now ignited.

6.3.12 Test for gas leakage at supply, Multifunctional control, Pilot and Main burners using proprietary detection fluid,

sealing any leaks found.

6.3.13 Allow heater to operate for a minimum of 15 minutes to ensure stability.

19

Fig. 6a, SYSTEM E-T FUNCTIONAL DIAGRAM

r

Содержание HI-SPEC J25RS Series

Страница 1: ...be left with the User or adjacent to the Gas Meter 1 24 1 2 3 4 5 6 7 8 9 10 11 12 10 SHORT LIST OF SPARES HI SPECJ25RS KEY G CNo MFR SNo DESCRIPTION QTY 1 232961 BOS02064 Fan Assembly 1 2 245508 R25...

Страница 2: ...ctrical supplies 2 3 For service access a minimum of 300mm 12 ins is required at the front of the heater Space must also be allowed in a compartment installation to permit the removal of the heater Th...

Страница 3: ...screws previously removed 5 1 7 Refit the air circulation fan front cover and air filter 5 1 8 Using suitable material manufacture a plate to cover the original return air opening in the top of the ai...

Страница 4: ...screw provided Note The orifice cup must NOT be used in balanced flue applications 4 21 Fig 3 Fitting of orifice cup Fig 7a SYSTEM E T CIRCUIT DIAGRAM FRONT SIDE 1234 1234 1234 1234 1234 1234 1234 12...

Страница 5: ...as a room thermostat c BASIC CONTROL MODELS A 24V room thermostat not supplied that complies with BS800 BS3955 and BS4201 is essential to ensure close control of comfort conditions An anticipator is l...

Страница 6: ...n anti clockwise to the SPARK symbol Press and hold the OPERATING CONTROL and whilst observing the Pilot Burner repeatedly press the Piezo igniter button until the Pilot burner ignites 6 3 5 After 20...

Страница 7: ...lly resets and both the Pilot and Main Burners are extinguished 6 5 2 On the Multifunctional control remove the pressure test gauge and refit the Outlet Pressure test point cover 6 6 TEMPERATURE RISE...

Страница 8: ...witch OFF the electrical supply to the air heater 6 8 8 Reconnect the air circulation fan at the terminal block 6 8 9 Hinge up the fan chamber door taking care to avoid causing damage to wiring and se...

Страница 9: ...system by opening and closing warm air outlets 7 2 6 How to obtain summer air circulation 7 2 7 That the air grilles on the heater or heater compartment grilles and ventilators in the walls windows o...

Страница 10: ...nstructions applicable to the appliance 8 2 BURNER AND CONTROL ASSEMBLY REMOVAL 8 2 1 Ensure that the Gas and Electrical supplies are switched OFF 8 2 2 Remove the appliance door 8 2 3 Disconnect igni...

Страница 11: ...from the capacitor b 230V mains L N and E from connection block terminals 1 and 2 and Earth stud respectively c Thermista stat connections from connection block terminals 7 and 8 d Limit switch from c...

Страница 12: ...n earth stud 8 13 4 Release the 2 x 4mm screws securing the Limit switch mounting plate and withdraw the control from the appliance by drawing the conductors through the grommet in the fan chamber flo...

Страница 13: ...n earth stud 8 13 4 Release the 2 x 4mm screws securing the Limit switch mounting plate and withdraw the control from the appliance by drawing the conductors through the grommet in the fan chamber flo...

Страница 14: ...from the capacitor b 230V mains L N and E from connection block terminals 1 and 2 and Earth stud respectively c Thermista stat connections from connection block terminals 7 and 8 d Limit switch from c...

Страница 15: ...nstructions applicable to the appliance 8 2 BURNER AND CONTROL ASSEMBLY REMOVAL 8 2 1 Ensure that the Gas and Electrical supplies are switched OFF 8 2 2 Remove the appliance door 8 2 3 Disconnect igni...

Страница 16: ...system by opening and closing warm air outlets 7 2 6 How to obtain summer air circulation 7 2 7 That the air grilles on the heater or heater compartment grilles and ventilators in the walls windows o...

Страница 17: ...witch OFF the electrical supply to the air heater 6 8 8 Reconnect the air circulation fan at the terminal block 6 8 9 Hinge up the fan chamber door taking care to avoid causing damage to wiring and se...

Страница 18: ...lly resets and both the Pilot and Main Burners are extinguished 6 5 2 On the Multifunctional control remove the pressure test gauge and refit the Outlet Pressure test point cover 6 6 TEMPERATURE RISE...

Страница 19: ...n anti clockwise to the SPARK symbol Press and hold the OPERATING CONTROL and whilst observing the Pilot Burner repeatedly press the Piezo igniter button until the Pilot burner ignites 6 3 5 After 20...

Страница 20: ...as a room thermostat c BASIC CONTROL MODELS A 24V room thermostat not supplied that complies with BS800 BS3955 and BS4201 is essential to ensure close control of comfort conditions An anticipator is l...

Страница 21: ...screw provided Note The orifice cup must NOT be used in balanced flue applications 4 21 Fig 3 Fitting of orifice cup Fig 7a SYSTEM E T CIRCUIT DIAGRAM FRONT SIDE 1234 1234 1234 1234 1234 1234 1234 12...

Страница 22: ...screws previously removed 5 1 7 Refit the air circulation fan front cover and air filter 5 1 8 Using suitable material manufacture a plate to cover the original return air opening in the top of the ai...

Страница 23: ...ctrical supplies 2 3 For service access a minimum of 300mm 12 ins is required at the front of the heater Space must also be allowed in a compartment installation to permit the removal of the heater Th...

Страница 24: ...be left with the User or adjacent to the Gas Meter 1 24 1 2 3 4 5 6 7 8 9 10 11 12 10 SHORT LIST OF SPARES HI SPECJ25RS KEY G CNo MFR SNo DESCRIPTION QTY 1 232961 BOS02064 Fan Assembly 1 2 245508 R25...

Отзывы: