12. COMMISSIONING

12.1 

Ensure the heater is correctly fitted with water and all air vented from the flow and return circuits.

12.2 

Switch on electrical supply.

12.3 

Setting maximum speed.

12.3.1  Make a short across thermista-stat connections, if fitted, and adjust the fan speed as required, 

remove the short.

12.4 

Setting minimum fan speed.

12.4.1  Make a short across the pipe sensor and adjusted the fan speed as required, remove short.

12.5 

WITH THERMISTA-STAT FITTED

12.5.1  Turn up thermista-stat to call for heat.
12.5.2   Check for 230V on switch live out.
12.5.3  With the water at the required temperature ensure fan starts
12.5.4   Allow the system to warm up and check temperature rise across unit is 40

°

C.

12.5.5   Set water differential to 20

°

C using lockshield valve or equivalent.

12.5.6  Turn off thermista-stat and check there is NO 230V on switch live out.
12.5.7  Check fan stops when water cools to required temperature.

12.6 

WITH NO THERMISTA-STAT FITTED

12.6.3  With the water at the required temperature ensure fan starts
12.6.4   Allow the system to warm up and check temperature rise across unit is 40

°

C.

12.6.5   Set water differential to 20

°

C using lockshield valve or equivalent.

11.6.6  Check fan stops when water cools to required temperature.

13. 

SERVICING & MAINTENANCE

13.1 ROUTINE 

MAINTENANCE

 

IMPORTANT: Before carrying out any work on the unit, ALWAYS ENSURE THAT IT IS ISOLATED FROM 
THE MAINS ELECTRICAL SUPPLY.

 

Remove the filter and unscrew the two retaining screws holding the front cover on the unit, gently pull it 
forward.

 

Maintenance should be carried out at least once per year. 

13.1.1   Check that the heat exchanger airways are free from obstructions. If necessary, clean with a  

  vacuum cleaner from the air inspection panel, taking care to not damage the airways.

CAUTION: THE ELEMENTS OF THE HEAT EXCHANGER ARE VERY FRAGILE.

 

13.1.2  Check the condition of the external strainer, cleaning as necessary.

 

13.1.3  Check that the air filter is being regularly cleaned in accordance with the User’s Instructions.

13.2 PCB 

REPLACEMENT

 

13.2.1  Ensure that the electrical supply is switched off and isolated.

13.3 PCB 

REMOVAL

1

3.3.1    Disconnect the wiring at the PCB terminal block.

13.3.2    Release the 4 clips securing the PCB  and withdraw the panel, disconnecting the fan supply lead 

at the fan tray terminal block.

13.3.3    Reassembly or replacement is in reverse order.

13.4 FAN 

REMOVAL

 

13.4.1  Ensure that the electrical supply is switched off and isolated.

 

13.4.2  Disconnect the 2 inline connectors on the fan assembly.

 

13.4.3  Release the screws securing the fan and withdraw if from the location runners.

 

13.4.4  Refitment or replacement is in reverse order.

13.5 

HEAT EXCHANGER REMOVAL

13.5.1    Ensure that the electrical supply is switched off and isolated.
13.5.2    Close the isolating valves and drain down the unit.
13.5.3    Release the clip and remove the heat exchanger and its associated pipework from the unit.
13.5.4   Refitment or replacement is in reverse order. Ensure that all air locks are expelled, and check for 

water soundness.

13.6 

AIR FILTER REMOVAL

 

13.6.1  The air filter is removed by sliding it out from the front of the unit.

Содержание Aquair S-10

Страница 1: ...ON COMMISSIONING SERVICING INSTRUCTIONS AQUAIR S SERIES of Water to Air Space Heaters These instructions are to be left with the User Publication No ZZ 1416 4 October 2014 COMMISSIONING S sustainable...

Страница 2: ...turn Air System 5 9 Electrical 6 10 Fan Performance Graph 6 11 Operating Mode 6 12 Commissioning 7 13 Servicing Maintenance 7 14 Circuit Diagram 11 15 Notes 9 16 Dimensions 10 17 Spares List 11 18 Exp...

Страница 3: ...ature of 60 C Water connections are left or right handed through knockouts in the sides of the cabinet 2 2 The air is drawn in through the air filter or air cleaner if fitted and the heat exchanger by...

Страница 4: ...t 5 1 2 All wiring must be in accordance with the appropriate standards 5 1 3 Ensure safety regulations and practices are adhered to when installing and using this equipment 5 2 DUCTING INFORMATION 5...

Страница 5: ...o 1000 0302300 MUST be fitted to the top of the unit Call Johnson Starley Ltd for details Tel 01604 762881 7 7 4 Swivel the disc cap by breaking the paint seal tap the disc and swivel Remove the cap i...

Страница 6: ...thermista stat demand 11 1 3 With no thermista stat connected the fan will run when a water temperature of 44 C is reached the fan speed is controlled by the water temperature The maximum fan speed re...

Страница 7: ...ter and unscrew the two retaining screws holding the front cover on the unit gently pull it forward Maintenance should be carried out at least once per year 13 1 1 Check that the heat exchanger airway...

Страница 8: ...voltage terminal 4 Ensure all connections are sound Check clock is on measure output Check for live supply into clock Repace clock if live is present Is 230 250VAC present Check harness connections to...

Страница 9: ...ter then 28K YES YES NO In there 230 250 VAC across high voltage terminals 1 2 If there 230 250 VAC across High Voltage terminals 1 2 Make sure mains is present across High Voltage terminals 2 3 Is th...

Страница 10: ...02 631 402 42 22 53 97 463 44 331 169 365 61 445 787 22 53 97 517 48 296 336 60 325 52 341 350 44 42 362 300 768 48 362 402 53 97 22 384 217 44 42 550 205 365 55 48 FIGURE 7 AQUAIR S 20 DIMENSIONS FIG...

Страница 11: ...FROM HEAT SOURCE FIGURE 8 AQUAIR S EXPLODED DIAGRAM ITEM DESCRIPTION QTY 10S 16S 20S 1 Air filter 1 AQ10 0182005 AQ16 0182005 AQ20 0182005 2 Air circulation fan with EC technology 1 AQ10 0126005 AQ16...

Страница 12: ...ndstarley co uk Reception 01604 762881 Fax 01604 767408 Johnson Starley Dravo Division Industrial H V Sales 01604 707022 sales johnsonandstarley co uk www dravo co uk Anniversary 1922 2012 In the inte...

Отзывы: