 Vent Pipe Connection to Blower

CAUTION:

•  Do Not Overtighten The Top And Bottom 

Gear Clamps Of The Rubber Coupling.

•  Do Not Apply Solvent Cement Or Silicone 

To The Rubber Coupling Connection.

The plastic vent piping connects into the rubber coupling 
located on the top of the blower assembly. This cou-
pling includes gear clamps to connect the venting to the 
blower. These connections must be properly seated and 
tightened to prevent the leakage of flue gases into the 
area. See Figures 21-25.
The 40, 50 and 60-gallon heaters with rated inputs of 
50,000 Btu/hr or less are designed and supplied with a 
51mm (2 in.) rubber coupling to accept the vent pipe.
The 50 and 75-gallon models with rated inputs of 60,000 
Btu/hr or more are supplied with a 76mm (3 in.) rubber 
coupling to accept the vent pipe.
Before installing clean and lightly sand the end of the 
plastic vent piping that will connect into the rubber cou-
pling.
Loosen the upper clamp on the rubber coupling and 
insert the sanded end of the vent piping a full 32mm (1-
1/4 in.). Do not use glue or sealant in the rubber coupling. 
Check that there is no stress on the connection or the 
vent piping that may be caused by twisting or bending.
Tighten the upper clamp so that the vent piping is firmly 
secured in the coupling and is gas tight. Do not over 
tighten or cause distortion of any of the parts. Ensure 
the bottom of the rubber coupling is firmly seated on 
the blower outlet and that the lower gear clamp is also 
secure. Check to ensure there is no distortion or move-
ment of the clamped assembly once it is completed.

BLOWER

2” VENT 

PIPE

2” RUBBER 

COUPLING 

(SUPPLIED)

CONFIGURATION 
FOR 40, 50 AND 
60-GALLON (LO-
INPUT) HEATERS 
CONNECTED TO 
2" VENTING.

Figure 21

1.

2.

3.

4.

5.

6.

2” RUBBER 

COUPLING 

(SUPPLIED)

BLOWER

3” VENT 

PIPE

2”-3” 

ADAPTER* 

(FIELD 

SUPPLIED)

2” VENT PIPE, 

75mm (3 in.) 

MAX LENGTH

CONFIGURATION 
FOR 40, 50 AND 
60-GALLON (LO-
INPUT) HEATERS 
CONNECTED TO 
3” VENTING.

* FOR 3” DIRECT 
CONNECTION TO 
THE BLOWER, 
ORDER 
COUPLING Kit # 
9008311005 
(SEE ALSO 
FIGURE 24).

Figure 22

4” VENT 

PIPE

3” RUBBER 

COUPLING

(ORDER COUPLING 

Kit # 9008311005 

TO REPLACE 2” 

RUBBER COUPLING 

SUPPLIED.)

3” VENT PIPE, 

75mm (3 in.) 

MAX LENGTH

3”-4” 

ADAPTER 

(FIELD 

SUPPLIED)

BLOWER

CONFIGURATION  
FOR LO-INPUT 
HEATERS 
CONNECTED TO  
4” VENTING.

LOW-INPUT 
HEATERS ARE 
SUPPLIED WITH  
A 2” RUBBER 
COUPLING.

Figure 23

3” VENT 

PIPE

3” RUBBER 

COUPLING 

(SUPPLIED)

BLOWER

CONFIGURATION  
FOR HI-INPUT 
HEATERS 
CONNECTED TO 
TO 3” VENTING.

(OPTIONAL 
CONFIGURATION  
FOR LO-INPUT 
HEATERS 
CONNECTED TO 
TO 3” VENTING.)

Figure 24

4” VENT 

PIPE

3” RUBBER 

COUPLING 

(SUPPLIED)

3” VENT PIPE, 

75mm (3 in.) 

MAX LENGTH

3”-4” 

ADAPTER 

(FIELD 

SUPPLIED)

BLOWER

CONFIGURATION  
FOR HI-INPUT 
HEATER 
CONNECTED TO 
4” VENTING.

Figure 25

 

– 16 – 

Содержание 40 gal.

Страница 1: ...n in these instructions is not followed exactly a fire or explosion may result causing property damage per sonal injury or death Do not try to light any appliance Do not touch any electrical switch do...

Страница 2: ...Relief Valve The Discharge Line Relief Drain Tube Temperature Pressure Relief Valve and Pipe Insulation Electrical Supply 19 SAFETY LOCKOUTS 21 High Limit Controls 21 Thermostat Water Temperature Blow...

Страница 3: ...combination with space heating applications User Responsibilities This manual has been prepared to acquaint you with the installation operation and maintenance of your gas fired water heater and provi...

Страница 4: ...able liquids or vapours have spilled or leaked in the area of the water heater leave the area immediately and call the fire department from a neighbor s home Do not attempt to clean the spill until al...

Страница 5: ...r and your safety Since we cannot put everything on the first few pages READ ENTIRE MANUAL BEFORE ATTEMPTING TO INSTALL OR OPERATE THE WATER HEATER After installation dispose of packaging material in...

Страница 6: ...if in an alcove or closet installation the entire floor must be covered by the panel Clearances and Accessibility DO NOT BLOCK AIR INTAKE OR SENSOR ACCESS ENSURE ADEQUATE CLEARANCE FOR AIR SUPPLY FRON...

Страница 7: ...s than 14 in w c 3 5 kPa the water heater must be isolated from the gas supply piping system by closing its manual shut off valve 1 2 3 4 WARNING Exposure to a higher gas supply pressure may cause dam...

Страница 8: ...r Tubing see Figure 9 26 Rubber Coupling 27 Gear Clamp 28 Flue Collector 29 Hot Water Outlet Nipple 30 Anode under cap 31 Cold Water Inlet Nipple 32 Flexible Manifold Tube see Figures 6 7 33 Viewport...

Страница 9: ...d as the primary water inlet and outlet connections For your convenience plugs are installed in these fittings at the factory Remove these plugs if needed for your specific installation Otherwise as w...

Страница 10: ...ETAL DRAlN PAN 150mm 6 MAX AIR GAP TO SUITABLE DRAIN NOTE THE T P VALVE CAN BE PIPED DIRECTLY TO THE DRAIN Figure 12 Mixing Valves Water heaters are intended to produce hot water Water heated to a tem...

Страница 11: ...can experience high ambient environments include closets alcoves areas under staircases attics especially in metal roofed buildings areas with restricted air movement rooms with large solar gains meta...

Страница 12: ...less VENT LENGTH LESS THAN OR EQUAL TO 20 EQUIVALENT FT 6 1 METRES USE THIS SCREEN SUPPLIED VENT LENGTH GREATER THAN 20 EQUIVALENT FT 6 1 METRES USE THIS SCREEN SUPPLIED Figure 14 Rodent Screens A ve...

Страница 13: ...ene Vent Pipe Size Elbow Type Short Sweep Short Radius Long Sweep Long Radius Notes 1 Use long radius elbows where possible Minimum distance between 90 elbows should be 6 150mm wherever possible 2 Ven...

Страница 14: ...nt piping to ensure adequate drainage Horizontal vent pip ing must not sag to form valleys where condensate may collect Vertical venting shall be supported every 1 5m 5 ft CAUTION Use of Solvent Cemen...

Страница 15: ...sure the plastic tubing is not folded anywhere between the pressure switch and the blower housing 5 This water heater is a polarity sensitive appliance and will not operate if the power supply polari...

Страница 16: ...iping is firmly secured in the coupling and is gas tight Do not over tighten or cause distortion of any of the parts Ensure the bottom of the rubber coupling is firmly seated on the blower outlet and...

Страница 17: ...S 200mm 8 in LOOP TO DRAIN BLOWER ASSEMBLY Figure 26 Water Supply Piping Installation Piping fittings and valves should be installed according to the installation drawing Figure 27 Water supply pressu...

Страница 18: ...ING VALVE SET TO 49 C 120 F FOLLOW THE TEMPERING VALVE MANUFACTURER S INSTRUCTIONS T P VALVE AND DISCHARGE LINE COLD WATER TEMPERED WATER TO FIXTURE Figure 28 Closed System Thermal Expansion Water sup...

Страница 19: ...ely close the cold water inlet to the water heater follow the draining instructions in this manual and replace the temperature pressure relief valve with a properly rated sized new one Temperature Pre...

Страница 20: ...Verify proper opera tion after servicing Note Always reference the wiring diagram for the correct electrical connections WARNING When the unit is plugged in 120VAC is pres ent at the electric connecti...

Страница 21: ...ontrol will flash the gas lockout code Refer to the System Error Codes section of this manual for an explanation of the codes applicable to the control installed on your water heater If this error occ...

Страница 22: ...possible gas leaks Vent Pipe System 1 Vent pipe and fittings of approved material 2 Acceptable size length and number of elbows on exhaust vent system 3 Installed in accordance with the latest edition...

Страница 23: ...eel water before bathing or showering Temperature limiting valves are available Mixing Valves Hot water can scald Water heaters are intended to produce hot water Water heated to a temperature that wil...

Страница 24: ...ition 9 Turn thermostat to desired setting DANGER Hotter water increases the risk of scald injury Consult the instruction manual before changing temperature 10 If the appliance will not operate follow...

Страница 25: ...e water heater Mixing valves are available at plumbing supply or hardware stores see Figure 11 12 Follow manufacturer s instructions for installation of the valves Before changing the factory setting...

Страница 26: ...should be considered normal Sediment buildup in the tank bottom will create varying amounts of noise and may cause premature tank failure Drain and flush the tank as directed under Draining and Flush...

Страница 27: ...Presence of flammable or corrosive materials in the installation area Presence of combustible materials near the water heat er Verify proper operation after any service is performed on this water hea...

Страница 28: ...supply proper clearances from the water heater must be maintained See Locating the New Water Heater section Combustible materials such as clothing cleaning materials or flammable liquids etc must not...

Страница 29: ...so you can access to the anode head Figure 39 Keep in a safe place for reinstallation later Remove the anode rod by using a ratchet and a 1 1 16 socket turning counter clockwise Figure 39 1 2 3 4 5 6...

Страница 30: ...blower wheel This can be problematic especially where condensation is present as particles may adhere to the venting sur faces These conditions can result in nuisance failures In areas that have a hig...

Страница 31: ...venter in the cold water line an expansion tank of adequate size must be installed Combo Heating Systems require higher water tem peratures than other applications When the system is used to supply wa...

Страница 32: ...y air Low gas pressure Orifice too small Thermostat set too low Heater too small Wrong piping connection Wasted hot water Flue clogged Air inlets blocked 1 2 3 4 5 6 7 8 9 Provide ventilation to water...

Страница 33: ...treatment if needed Refer to Condensate section 1 2 WATER LEAKAGE Condensation Dripping Temperature Pressure Relief Valve Thermostat does not shut off Drain valve dripping leaking Tank Leak 1 2 3 4 5...

Страница 34: ...p requires manual intervention and can not be reset by cycling power to the control A manual reset requires turning the temperature setting dial to the lowest coldest position for a minimum of 10 seco...

Страница 35: ...ht dim Call For Heat no fault conditions One Flash three second pause Low Flame Signal control continues to operate Two Flash three second pause Pressure Switch Failed Closed Three Flash three second...

Страница 36: ...System Return Inlet Optional 19 Air Inlet Snorkel 20 Combo Heating System Supply Outlet Optional 21 Blower with Power Cord see Figure 49 22 Air Switch inside box see Figure 49 23 Junction Box see Fig...

Страница 37: ...5 40 41 Natural gas and Propane main burner with igniter assembly for 60k to 75k Btu hr models Flare Nut Figure 47 17 Figure 48 25 23 24 22 5 26 27 Figure 49 Notes Natural gas models have Right hand t...

Страница 38: ...e water heater s Model Number SKU Serial Number date of purchase and date of installation c THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF THIS EXPRESS WARRANTY IS WHER...

Страница 39: ...cy beyond the control of the Manufacturer or s The water heater is installed in a closed system without adequate provision for thermal expansion 3 Except when speci cally prohibited by the applicable...

Отзывы: