Multiple Sidewall Terminations
An exhaust termination must be at least
1 ft (305mm) away from another exhaust
termination. An exhaust termination must
also be at least 2 ft (610 mm) away from
an inside corner. (If the adjacent wall is less
than 2 ft (610 mm) of length, the minimum
required distance away from the inside
corner will be equal to the length of that
adjacent wall.)
Multiple DV Sidewall Terminations
A direct vent (DV) termination must be
at least 1 ft (305 mm) away from other
direct vent terminations.
A direct vent termination must also be at
least 2 ft (610 mm) away from an inside
corner. (If the adjacent wall is less than
2 ft (610 mm) of length, the minimum
required distance away from the inside
corner will be equal to the length of that
adjacent wall.)
ŶƟĐŝƉĂ
ƚĞĚ^ŶŽǁůĞǀ
Ğů
džŚĂƵƐƚ
dĞƌŵŝŶĂƟŽŶ
ϮŌ
;ϲϭϬŵŵͿ
ŵŝŶ͘
ϭŌ
;ϯϬϱŵŵͿ
ŵŝŶ͘
ϭŌ
;ϯϬϱŵŵͿ
ŵŝŶ͘
/ŶƐŝĚĞ
ĐŽƌŶĞƌ
Inside
corner
ŶƟĐŝƉĂ
ƚĞĚ^ŶŽǁůĞǀ
Ğů
ϮŌ
(610 mm)
min.
ϭŌ
(305 mm)
min.
ϭŌ
(305 mm)
min.
Combined
ŝŶƚĂŬĞĂŶĚ
ĞdžŚĂƵƐƚ
ƚĞƌŵŝŶĂƟŽŶ
For direct vent sidewall
terminations that use two
separate penetrations for
the intake and exhaust,
keep the termination
clearances shown in the
diagrams on the right.
Improper installation can result in carbon monoxide poisoning or death. Follow all local
and national codes in regards to proper termination clearances. In the absence of such
codes, the clearances below can be used as guidelines. Local codes supersede these
guidelines.
WARNING
1 ft (305 mm) min.
0.5 ft
(159 mm) min.
Exhaust
Intake
Exhaust
Intake
фĂƐĞϮх
1 ft (305 mm)
min.
0.5 ft
(159 mm) min.
0.5 ft
(159 mm)
min.
Exhaust
Intake
Exhaust
Intake
фĂƐĞϭх
Exhaust
termination
2 ft
(610 mm)
min.
Exhaust and/or direct
vent sidewall terminations
should be at least 2 ft (610
mm) away from an opposite
surface/wall. Do not place
the termination directly in
front of an opening into a
building
.