14

113242-3

The input ratings shown on the dryer data label are for
elevations up to 2,000 feet (610 meters), unless elevation
requirements of over 2,000 feet (610 meters) were specified
at the time the dryer order was placed with the factory.  The
adjustment or conversion of dryers in the field for elevations
over 2,000 feet (610 meters) is made by changing each burner
orifice.  If this conversion is necessary, contact the reseller
who sold the dryer or contact the factory.

Important

This gas dryer is not provided with an internal gas
supply shutoff and an external gas supply shutoff

must be provided.

Technical Gas Data

Gas Specifications

Shaded areas are stated in metric equivalents

*Measured at outlet side of gas valve pressure tap when gas valve is on.

Gas Connections

Inlet connection ............ 1/2” N.P.T.
Inlet supply size ........... 1/2” Diameter Pipe (minimum)
Heat input (per dryer) .. 95,000 Btu/hr (23,940 kcal/hr)

Natural Gas

Regulation is controlled by the dryer’s gas valve’s internal
regulator.  Incoming supply pressure must be consistent
between a minimum of 6.0 inches (14.92 mb) and a maximum
of 12.0 inches (29.9 mb) water column (W.C.) pressure.

Liquid Propane (L.P.) Gas

Dryers made for use with L.P. gas have the gas valve’s internal
pressure regulator blocked open so that the gas pressure
must be regulated upstream of the dryer.  The pressure
measured at each gas valve pressure tap must be a
consistent 10.5 inches (26.1 mb) water column.  There is no
regulator or regulation provided in an L.P. dryer.  The pressure
must be regulated at the source (L.P. tank) or an external
regulator must be added to each dryer.

Shaded area is stated in metric equivalent

* Drill Measurement Size (D.M.S.) equivalents are as follows:

Natural Gas ........................... #29 = 0.1360” (3.4540 mm).
Liquid Propane Gas ............... #46 = 0.0810” (2.0574 mm).

!

Type of Gas

Manifold Pressure*

In-Line Pressure

Natural

3.5 inches W.C.

6.0-12.0 inches W.C.

8.7 mb

14.92 - 29.9 mb

Liquid

Propane

10.5 inches W.C.

11.0 inches W.C.

26.1 mb

27.4 mb

TYPE OF GAS

Btu/hr

Rating

kcal/hr

Rating

Natural

Liquid Propane

Qty.

D.M.S.*

Part No.

Qty.

D.M.S.*

Part No.

95,000

23,940

2

#29

140820

2

#46

140806

LIQUID PROPANE CONVERSION KIT PART NUMBER 883306

!

!

!

!

!

Gas Information______________________

It is your responsibility to have all plumbing connections made
by a qualified professional to ensure that the gas plumbing
installation is adequate and conforms to local and state
regulations or codes.  In the absence of such codes, all
plumbing connections, materials, and workmanship must
conform to the applicable requirements of the National Fuel
Gas Code ANSI Z223.1-LATEST EDITION, or in Canada, the
Canadian Installation Codes CAN/CGA-B149.1-M91 (Natural
Gas) or CAN/CGA-B149.2-M91 (Liquid Propane [L.P.] Gas) or
LATEST EDITION.

Important

Failure to comply with codes or ordinances,
and/or requirements in this manual, can result in

personal injury and improper operation of the dryer.

The dryer and its individual shutoff valves must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess
of 1/2 psig (3.5 kPa).  The dryer must be isolated from the
gas supply piping system by closing its individual manual
shutoff valve during any pressure test of the gas supply piping
system at test pressures equal to or less than 1/2 psig (3.5
kPa).

Important

Failure to isolate or disconnect the dryer from
supply as noted can cause irreparable damage

to the gas valve, which will

 

void the warranty.

Warning

Fire or explosion could result due to failure of
isolating or disconnecting the gas supply as

noted.

Gas Supply

The gas dryer installation must meet the American National
Standard...National Fuel Gas Code ANSI Z223.1-LATEST
EDITION, or in Canada, the Canadian Installation Codes CAN/
CGA-B149.1 M91 (Natural Gas) or CAN/CGA-B149.2-M91 (L.P.
Gas) or LATEST EDITION, as well as local codes and
ordinances and must be done by a qualified professional.

Note

Undersized gas piping will result in ignition
problems, slow drying, increased use of energy,

and can create a safety hazard.

The dryer must be connected to the type of heat/gas indicated
on the data label.   If this information does not agree with the
type of gas available, do not operate the dryer.  Contact the
reseller who sold the dryer or contact the factory.

Important

Any burner changes or conversions must be
made by a qualified professional.

Содержание D40

Страница 1: ... Installation and service must be performed by a qualified installer service agency or the gas supplier AVERTISSEMENT Assurez vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d incendie ou d explosion ou pour éviter tout dommage matériel toute blessure ou la mort Ne pas entreposer ni utiliser d essence ni d autres vapeurs ou liquides inflammables à p...

Страница 2: ...______________________________________________________________ Serial Number s ________________________________________________________________________________________ ______________________________________________________________________________________________________ ______________________________________________________________________________________________________ Replacement parts can be o...

Страница 3: ...ck guards outer tops or service panels removed Personal injury or fire could result The dryer must never be operated without the lint filter screen in place even if an external lint collection system is used FOR YOUR SAFETY Do not dry mop heads in the dryer Do not use dryer in the presence of dry cleaning fumes Dryers must not be installed or stored in an area where it will be exposed to water and...

Страница 4: ... articles that contain plastic foam sponge rubber or similarly textured rubber materials Drying in a heated basket tumbler may damage plastics or rubber and also may be a fire hazard A program should be established for the inspection and cleaning of lint in the burner area exhaust ductwork and area around the back of the dryer The frequency of inspection and cleaning can best be determined from ex...

Страница 5: ...61 cm AIRFLOW 60 HZ 460 cfm 13 cmm AIRFLOW 50 HZ 382 cfm 11 cmm EXHAUST CONNECTION DIAMETER 8 20 32 cm WATER CONNECTION 3 4 M N P T DRYERS PER 20 40 CONTAINER 12 24 DRYERS PER 48 53 TRUCK 30 32 VOLTAGE AVAILABLE 120 480v 1 3 ø 2 3 4 w 50 60 Hz APPROX NET WEIGHT 517 lbs 234 5 kg APPROX SHIPPING WEIGHT 552 lbs 250 38 kg HEAT INPUT 95 000 Btu hr kcal hr INLET PIPE CONNECTION 1 2 F B S P T VOLTAGE AVA...

Страница 6: ...6 113242 3 Specifications _______________________ ...

Страница 7: ...supporting its weight Carpeting must be removed from the floor area that the dryer is to rest on Important The dryer must be installed on noncombustible floors only The dryer must not be installed or stored in an area where it will be exposed to water and or weather The dryer is for use in noncombustible locations Provisions for adequate air supply must be provided as noted in this manual refer to...

Страница 8: ...otect the outside end of the horizontal ductwork from the weather a 90 elbow bent downward should be installed where the exhaust exits the building If the ductwork travels vertically up through the roof it should be protected from the weather by using a 180 turn to point the opening downward In either case allow at least twice the diameter of the duct between the duct opening and the nearest obstr...

Страница 9: ...work Exhaust back pressure measured by a manometer at the dryer exhaust duct area must be no less than 0 and must not exceed 0 3 inches 0 74 mb of water column W C For extended ductwork runs the cross section area of the duct can only be increased to an extent For extended ductwork runs a professional heating ventilating and air conditioning HVAC firm should be consulted for proper venting informa...

Страница 10: ...diameter increasing before each individual 8 inch 20 32 cm duct is added refer to Illus C for horizontal venting and Illus D for vertical venting Important No more than four 4 dryers maximum should be connected to one 1 main common duct with a vertical run Note Distance between dryer single ducts being connected to the main common duct must be a minimum width of 34 1 4 87 cm Ductwork should be lai...

Страница 11: ...ns Important Figures shown are for non reversing models only For reversing models contact the factory Electric Models Only All electrically heated dryers must be connected to the electric service shown on the dryer s data label The connecting wires must be properly sized to handle the rated current ELECTRICAL SERVICE SPECIFICATIONS PER DRYER IMPORTANT NOTES A B C 208 VAC AND 240 VAC ARE NOT THE SA...

Страница 12: ...he way to the electrical ground If there are any nonmetallic interruptions such as a meter pump plastic rubber or other insulating connectors they must be jumped out with no 4 copper wire and securely clamped to bare metal at both ends Important For personal safety and proper operation the dryer must be grounded Provisions are made for ground connection in each dryer at the electrical service conn...

Страница 13: ...dryer s data label The electrical input connections are made at the electric oven contactor located inside the assembly at the rear center upper section of the dryer The ground connection is made to a copper lug also provided in this area To gain access remove oven rear service cover Important A strain relief must be used where the input wiring enters the oven assembly For 208 240V Applications A ...

Страница 14: ...2 29 140820 2 46 140806 LIQUID PROPANE CONVERSION KIT PART NUMBER 883306 Gas Information______________________ It is your responsibility to have all plumbing connections made by a qualified professional to ensure that the gas plumbing installation is adequate and conforms to local and state regulations or codes In the absence of such codes all plumbing connections materials and workmanship must co...

Страница 15: ...m at test pressures equal to or less than 1 2 psig 3 5 kPa Piping Connections All components materials must conform to National Fuel Gas Code Specifications ANSI Z223 1 LATEST EDITION or in Canada CAN CGA B149 1 M91 Natural Gas or CAN CGA B149 2 M91 Liquid Propane L P Gas or LATEST EDITION for General Installation and Gas Plumbing as well as local codes and ordinances and must be done by a qualifi...

Страница 16: ...7 kg hr Steam Information ___________________ It is your responsibility to have all plumbing connections made by a qualified professional to ensure that the steam plumbing installation is adequate and conforms with local and state regulations or codes Care must be exercised when leveling steam dryers into final position After leveling the dryer check the downward pitch of the heat exchanger from f...

Страница 17: ...eam coil damage All horizontal runs of steam supply piping should be pitched 1 4 inch for every 1 foot 0 30 meters back towards the steam supply header causing the condensate in the line to drain to the header Install a bypass trap in any low point to eliminate wet steam Important Flexible hoses couplings must be used Coil failure due to hard plumbing connections will void the warranty Steam Dampe...

Страница 18: ...____________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ ___________________________...

Страница 19: ...made by a qualified professional to ensure that the plumbing installation is adequate and conforms to local state and federal regulations or codes It is the installation or owner s responsibility to see that the necessary or required water water pressure pipe size or connections are provided The manufacturer assumes no responsibility if the fire suppression system is not connected installed or mai...

Страница 20: ...he water solenoid valve The use and connections of this manual bypass are at the option or discretion of the owner The water connection for the manual bypass is made to the T or four way fitting which has a 3 8 F P T and a coupling must be used to provide the minimum 1 2 supply feed line If the rear area of the dryer or the water supply is located in an area where it will be exposed to cold freezi...

Страница 21: ...d in place Rotate the basket tumbler drum by hand to be sure it moves freely Steam Models check to ensure that a clean dry regulated air supply 80 psi 5 51 bar is on the dryer with air operated damper system only Steam Models check to ensure all steam shutoff valves are open Steam Models check steam damper operation Check basket tumbler bearing setscrews to ensure that they are all tight Check ven...

Страница 22: ...that no further adjustments are necessary and that all components are functioning properly Basket Coating The basket tumbler is treated with a protective coating We suggest dampening old garments or cloth material with a solution of water and nonflammable mild detergent and tumbling them in the basket tumbler to remove this coating Check the electric service phase sequence 3 phase 3ø models only W...

Страница 23: ...TEMP ___ ___ MINUTES REMAINING At the end of the heat cycle the dryer will shut off the heat and continue the fan and basket tumbler until the Cool Down Time or temperature is reached Important For more detailed information regarding the microprocessor controller computer on your dryer refer to the microprocessor user s manual included with the dryer Dual Timer Dryers Turn drying timer knob for a ...

Страница 24: ...enever contacting JLA for warranty information be sure to have the dryer s model number and serial number available so that your inquiry can be handled in an expeditious manner Routine Maintenance ________________ Cleaning A program and or schedule should be established for periodic inspection cleaning and removal of lint from various areas of the dryer as well as throughout the ductwork system Th...

Страница 25: ...stick Note A back draft damper that is sticking partially closed can result in slow drying and shutdown of heat circuit safety switches or thermostats When cleaning the dryer cabinet s avoid using harsh abrasives A product intended for the cleaning of appliances is recommended Adjustments _________________________ 7 Days After Installation and Every 6 Months Thereafter Inspect bolts nuts screws se...

Страница 26: ...f the preset cycles in letters A F Verify that the applicable indicator lights on the microprocessor controller computer board are lit Refer to the illustration below For Models with Johnson Direct Spark Ignition DSI Controller G760 Theory of Operation Start the drying cycle When the gas burner ignites within the chosen trial for ignition time 6 seconds the flame sensor detects gas burner flame an...

Страница 27: ...set manually This hi temperature condition may be caused due to a restricted exhaust poor airflow or improper burner operation The location of the burner hi limit is on the right side of the burner box looking at the burner from the back of the dryer Warning Discontinue power to dryer before attempting to reset hi limit light emitting diode L E D diagnostic indicator flashes A steady light emittin...