JJM Boiler Works JM-2 Скачать руководство пользователя страница 3

Installation

Figure 1

  JM-series condensate neutralizing tubes – features and dimensions

JM

series Condensate Neutralizing Tubes –– Installation/Operation & Maintenance

3

RATINGS & DIMENSIONS 

(in inches)

Model MBH GPH

A

B

C

D

E

F

JM-2

150

2

10.5 2.75 1.375 3.5 1.875 6.5

JM-3

300

3

19.5 2.75 1.375 3.5 1.875, 9.5

1

PVC tubing filled with 

3

/

8

” limestone and 97% MgO Pellets

2

Clamp-on support brackets

3

Condensate outlet hose barb 

fitting

¾” hose barb x ½” NPT  — or — 

¾” PVC x ½” NPT  (both supplied)

4

Condensate inlet hose barb 

fitting

Figure 2

  JM-series tube with floor drain, typical

Figure 3

  JM-series tube with condensate pump, typical

Condensing boiler or furnace

Condensate neutralizing tube (or multiple tubes piped in parallel)

Boiler/furnace condensate trap connection

Boiler/furnace vent

Vent condensate trap, when used — Install a trap as shown. Connect 

the tubing to a separate JM tube if appliances are common vented. For 

individually-vented appliances, the vent condensate drain can be con-

nected to the appliance condensate drain line.

Drain or sump

G     

Condensate pump

Bottom of boiler/furnace condensate outlet — MUST be ABOVE 

condensate pump inlet connection

Bottom of JM tube condensate outlet

Mounting pad or structural platform, when required to elevate boiler 

condensate drain as needed

Mounting clamps

Mounting clamps must be secured to the mounting surface

Plastic tubing or PVC pipe — When using PVC pipe, remove the JM 

inlet and outlet hose barb fittings and replace with threaded PVC fit-

tings. Include unions in the piping to allow removal of the JM tube for 

inspection and service. — Secure pipe or tubing in place. — Protect 

with a shield if necessary if routed through traffic areas.

Use hose clamps at all connections when using plastic tubing.

Condensate drain termination at floor drain (or condensate pump 

reservoir inlet) — secure in place with clamps. — Follow instructions 

for condensate pump.

Elevate the JM tube on a structural base if necessary for the outlet to be 

raised.

Route condensate discharge line from to appropriate drain location.