Compact Zero Clearance 

Cabinet Installation 

ZCC Part No. 225333

Installation notes:

The Gason Zero Clearance Cabinet

 

 is an approved cabinet that allows for Eureka/Jindara Insert woodheaters as stated above to be installed within

replace in accordance with AS2918:2001.

This can be achieved by following the installation guidelines listed below. 
• Select the position that you wish to to install your ZCC , car

roof cavity (The outer

 being 255mm requires a 25mm clearance on either side to combustibles, making overall clearance 305mm).

. Note: Line up centre holes with corresponding holes depending on model. Refer to diagram on sheet 2.

• Fit the 

 to the upstands and terminate at the required height above the roof line.

• Fit 300mm x 100mm vermin proof vent directly behind where the 

 will be located, as near as practicable to the 

r. This vent will

allow air access to the zero box either from another room or external air. Note, if installed on 

r, an additional two vents are

required. i.e. Either thr

r, one each side of the zero box, or alternatively, through the side wall(s), if applicable.

• Build your frame around the 

 mantaining the clearances listed above.


• Cover the rest of the frame to suit your requirments with plaster, timber, MDF etc.

• Install the mantel if required. Note if mantle is made out of a combustible material the following dimensions must be adhered to.

All dimensions are minimum and must under no circumstances be reduced. 

Gason Pty Ltd accepts no liability whatsoever for their

interpretation of AS2918:2001.

Sheet 1 NEXT 2 GPN

 231080 Rev.A

Sheet 1 NEXT 2 GPN

 231080 Rev.A

545

763

Zero

Clearance

Box

To suit Insert models: Opal SRS4, Riverina SRS3,

D

A min. 

60mm

 gap for

Opal SRS4/Riverina SRS3

and 

120mm 

gap for 

Stockade SRS5/Barossa SRS3

timber stud.

The timber stud may need

to be notched out to allow

for the minimum required

Stockade SRS5, Barossa SRS3, Kimberley Mk2, Hamersley Mk2 

Federation Mk2 & Victorian Insert

NOTE:

F

Tripleskin

Flue

690

660

836

30

E

MODEL

A            B           C            D           E           F            G             H            I           J          

Opal

Riverina

Stockade

Barossa

Kimberley

Hamersley

Federation

Victorian

A

C

Hearth Width

12        570       890        810        40        20       1040       1100      50       250            530

12        550       950        810        40        20       1340       1390      50       250            510

18        615    

18        705     1000       

All dimensions in millimetres, images not to scale

Clearance to combustibles

Insert your chosen appliance into the zero cabinet. Note: x2 galvanized c-section brackets supplied are required to centralise 

Opal/Riverina, Stockade/Barossa.  For installation of Kimberley, Hamersley, Federation and Victorian, appliances must sit on c-section 

to ensure correct installation height is achieved. Fit active flue and cowl once appliance is in position. 

See oversheet for dimensions.

(non-combustible cement sheet, villaboard or similar) in the position desired for the ZCC, ensuring hearth will 

1140      25       250            550

  940      1063      100       50       1050 

B

12        570       890        810        40        20       1040       1100      50       250            530

12        550       950        810        40        20       1340       1390      50       250            510

18        705     1000       

18        705     1000       

1063      100       50         975       1225     150      250            600

1063      100       50         975       1225     150      250            600    
1063      100       50         975       1225     150      250            600

Cover the front face of framing with a minimum 4mm cement sheet or non-combustible material.

A. F.

mm in front 

of unit

Hearth depth

the ZCC

ZCC

ZCC

extend fully underneath ZCC as shown above for relevent model. Place the ZCC into position.