4
Isolation voltage
Between contact and coil:
2000 VAC / min
Action time
10 ms max
Release time
5 ms max
Mechanical service life
10
6
times
Energy pulse output
Pulse width
80ms±20%
Max. terminal voltage
35V
Max. terminal current
10mA
Pulse frequency
≤10Hz
Digital input
Sensitivity
ON:140
~
270V AC, OFF: <110 V AC
Isolation voltage
5000 VAC (1 min)
Scanning time
1 ms
Wave filtering time
30 ms
Communication interface
Physical interface
RS-485
Communication speed
Up to 115.2 kbps
Communication protocol
Modbus-RTU
Isolation voltage
2000 VAC (1 min)
Real-time clock
Error
≤0.5s/day
Electromagnetic compatibility
Electrostatic discharge immunity: IEC 61000-4-2-III
Radiated, radio-frequency, electromagnetic field immunity: IEC 61000-4-3-III
Electrical fast transient/burst immunity: IEC 61000-4-4-IV
Surge immunity: IEC 61000-4-5-IV
Immunity to conducted disturbances, induced by radio-frequency fields: IEC 61000-4-6-III
Power frequency magnetic field immunity: IEC 61000-4-8-III
Voltage dips, short interruptions and voltage variations immunity: IEC 61000-4-11-III