Jetter AG
Technical specifications | 4
JX3-BN-EC User Manual
13 / 92
4.4 Environmental conditions
Category
Description
Standards
Operating temperature
0 … +50 °C
DIN EN 61131-2
Storage temperature
-40 … +70 °C
DIN EN 60068-2-1
Air humidity
10 ... 95 %,
non-condensing
DIN EN 60068-2-2
Max. operating altitude:
2,000 m above sea level
Corrosion immunity and
chemical resistance
No special protection against corrosion. Ambient air
must be free from higher concentrations of acids, al-
caline solutions, corrosive agents, salts, metal va-
pors, and other corrosive or electroconductive con-
taminants.
Degree of pollution - Elec-
tronics
Degree of pollution 2
DIN EN 61131-2
Usually, the pollution is non-conductive. However,
temporary conductivity due to condensation may oc-
cur.
Tab. 5:
Environmental conditions
4.5 EMI values
4.5.1 Housing
Emitted interfer-
ence
Parameter
Values
Standards
Frequency band
30 … 230 MHz
DIN EN 61000-6-3
DIN EN 61131-2
DIN EN 55011
Limit value
30 dB (µV/m) at 10 m dis-
tance
Frequency band
230 … 1,000 MHz
Limit value
37 dB (µV/m) at 10 m dis-
tance
Class B
Tab. 6:
Emitted interference
Immunity to inter-
ference
Parameter
Values
Standards
Magnetic field with mains frequency
Frequency
50 Hz
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-8
Magnetic field
30 A/m
RF field, amplitude-modulated
Frequency band
80 MHz … 2 GHz
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-3
Test field strength
10 V/m
AM 80 % with 1 kHz
Criterion A
ESD
Discharge through air:
Test peak voltage 8 kV
8 kV
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-2
Discharge through air
Test peak voltage
4 kV
Criterion A
Tab. 7:
Immunity to interference