10 Pulse stretching
JetWeb
78
Jetter AG
The input state of the JX2-IO16 module is normally read out through the input
numbers of the controller.
When using manual pulse stretching on the JX2-IO16 module, register 3xx3 has to
be used for reading the present input state.
Register 3xx3: Present input state
Function
Description
Read
Present input state at the input terminal
Write
Illegal
Value range
Bit-coded, 8 bits
Value after reset
0b 00000000
Meaning of values:
0
:
Input is not active (0 V state)
1
:
Input is active (24 V state)
Meaning of the individual bits:
Bit 0:
Input # 1
Bit 1:
Input # 2
Bit 2:
Input # 3
Bit 3:
Input # 4
Bit 4:
Input # 5
Bit 5:
Input # 6
Bit 6:
Input # 7
Bit 7:
Input # 8