3 Operating Parameters

Jetter AG

15

Operating Parameters (EMC) - Immunity to 

Interference of Signal Ports

Parameter

Value

Reference

Asymmetric RF, am-
plitude-modulated

Frequency band 0.15 -80 MHz
Test voltage 10 V
AM 80 % with 1 kHz
Source impedance 150 Ohm
Criterion A

DIN EN 61000-6-2
DIN EN 61000-4-6

Burst

Test voltage 1 kV
tr/tn 5/50 ns
Repetition rate 5 kHz
Criterion A

DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-4

Operating Parameters (EMC) - Immunity to 

Interference of DC Power Supply In- and Outputs

Parameter

Value

Reference

Asymmetric RF, am-
plitude-modulated

Frequency band 0.15 -80 MHz
Test voltage 10 V
AM 80 % with 1 kHz
Source impedance 150 Ohm
Criterion A

DIN EN 61000-6-2
DIN EN 61000-4-6

Burst

Test voltage 2 kV
tr/tn 5/50 ns
Repetition rate 5 kHz
Criterion A

DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-4

Содержание JetWeb JX2-SIM8

Страница 1: ...Article 608 633 26 April 2002 Printed in Germany JetWeb JX2 SIM8 Operator s Manual...

Страница 2: ...need not be documented in every single case This manual and the information contained herein have been compiled with due diligence However Jetter AG assumes no liability for printing errors or damages...

Страница 3: ...ine 49 7141 2550 444 Telefax 49 7141 2550 425 E Mail Sales sales jetter de E Mail Technical Hotline hotline jetter de Internet Address http www jetter de This Operator s Manual is an Integral Part of...

Страница 4: ...s to produce manuals that are more user friendly and to address your wishes and requirements From this JX2 SIM8 module may result unavoidable residual risks to persons and property For this reason any...

Страница 5: ...structions 7 1 1 Ensure Your Own Safety 9 1 2 Instructions on EMI 10 2 Physical Dimensions 11 3 Operating Parameters 13 4 Technical Data 17 5 Digital Input Module JX2 SIM8 19 5 1 Description of Connec...

Страница 6: ...Table of Contents JetWeb 6 Jetter AG...

Страница 7: ...Safety Extra Low Voltage The JX2 SIM8 module is therefore not subject to the EU Low Voltage Directive The JX2 SIM8 module may only be operated within the limits of the stated data Usage Other Than Ag...

Страница 8: ...material damage Important This sign is to indicate a possible impending situation which might bring damage to the product or to its surroundings Note You will be informed of various possible applicat...

Страница 9: ...original parts and equipment any claims with respect to liability of Jetter AG are excluded Malfunctions Information Signs and Labels Disconnect the JX2 SIM8 module from the mains to carry out mainten...

Страница 10: ...sures for increasing immunity to interference On principle physical separation should be maintained between signal and voltage lines Shield both sides of the cable The entire shield must be drawn behi...

Страница 11: ...JX2 SIM8 2 Physical Dimensions Jetter AG 11 2 Physical Dimensions Fig 2 Front View JX2 SIM8 Fig 3 Side View JX2 SIM8...

Страница 12: ...JetWeb 12 Jetter AG Fig 4 Top View JX2 SIM8...

Страница 13: ...roconductive contaminants Operating Altitude Up to 2000 m above sea level DIN EN 61131 2 Mechanical Operating Parameters Parameter Value Reference Free Falls Withstand ing Test Height of fall units wi...

Страница 14: ...MHz limit 37 dB V m at 10 m distance class B DIN EN 50081 1 DIN EN 55011 DIN EN 50081 2 Operating Parameters EMC Immunity to Interference of Housing Parameter Value Reference Magnetic Field with Main...

Страница 15: ...est voltage 1 kV tr tn 5 50 ns Repetition rate 5 kHz Criterion A DIN EN 61131 2 DIN EN 61000 6 2 DIN EN 61000 4 4 Operating Parameters EMC Immunity to Interference of DC Power Supply In and Outputs Pa...

Страница 16: ...JetWeb 16 Jetter AG...

Страница 17: ...ed signal Enclosure Aluminium painted Dimensions H x W x D in mm 115 x 45 x 69 Weight 350 g Mounting DIN Rail Heat loss of logic circuit 0 3 Watt Rated Input Voltage DC 24 V 15 20 Voltage Range DC 0 3...

Страница 18: ...on If a line with reverse polarity is connected to a digital input the input will be destroyed Note A digital output may directly without additional load be connected to a digital input 0 State 2 2 11...

Страница 19: ...SIM8 module is for simulating digital inputs 5 1 Description of Connections This module is equipped with 4 pushbuttons inputs 1 to 4 and 4 switches inputs 5 to 8 for simulating digital inputs 5 2 Des...

Страница 20: ...ule arranged as follows Note Digital input or output modules are taken into account when assigning module numbers Intelligent modules such as SV SM PID etc located among the digital input and output m...

Страница 21: ...e JX2 ID8 and one digital output module JX2 OD8 Basic Controller JX2 OD8 Output Module JX2 SV1 Servo Module JX2 ID8 Input Module Module 1 Module 2 Module 3 Module 4 Inputs and Outputs 101 108 Output 2...

Отзывы: