JX2-PROFI1
5 The Communication Module JX2-PROFI
Jetter AG
30
Register 1m101: Command Register
Various actions can be triggered via the command register. A read access provides
the command processed last.
15
1
An error has occurred. Register 1m134
holds the reason for the error.
Value range:
23-bit signed integer
Value after reset:
1
Command
No.
Comment
5
Reset the module.
The module will be reset into its initial state. After having issued
this command, the module must not be accessed before bit 13
in the status register has been reset.
6
The error bit in the status register and the error number register
is cleared.
With the help of this command, errors can be acknowledged.
Resetting the module by issuing command 5 will not clear an
error report.
7
A status diagnose telegram will be sent (see 6.3).
8
An extended diagnose telegram will be sent. The data written in
the diagnose data registers are being transmitted to the
PROFIBUS master as a diagnose telegram (see 6.3).
9
The module is set into the state of static diagnosis.
10
The latest transmitting of a diagnose telegram will be cancelled
(see 6.3).
11
The "read data block" request of the master is confirmed by OK.
12
The "read data block" request of the master is confirmed by
NOT OK.
13
The "write data block" request of the master is confirmed by OK.
14
The "write data block" request of the master is confirmed by
NOT OK.
Value range:
0 .. 255
Value after
reset:
0
Содержание JetWeb JX2-PR0FI1
Страница 1: ...Article 608 641 01 November 2002 Printed in Germany ...
Страница 4: ...JX2 PROFI1 Table of Contents Jetter AG 4 ...
Страница 13: ...1 Safety Instructions JetWeb 13 Jetter AG ...
Страница 14: ...JX2 PROFI1 2 Physical Dimensions Jetter AG 14 2 Physical Dimensions Fig 2 Front View JX2 PROFI1 ...
Страница 15: ...JetWeb 15 Jetter AG Fig 3 Side View JX2 PROFI1 Fig 4 Top View JX2 PROFI1 ...
Страница 19: ...JetWeb 19 Jetter AG ...
Страница 21: ...JetWeb 21 Jetter AG ...
Страница 23: ...JetWeb 23 Jetter AG 5 3 Features ...
Страница 43: ...JetWeb 43 Jetter AG ...
Страница 45: ...JetWeb Jetter AG 45 ...
Страница 61: ...JetWeb Jetter AG 61 43 rPB_DiagData1 12146 44 rPB_DiagData2 12147 45 46 rPB_DataIn 12300 47 rPB_DataOut 12400 ...
Страница 62: ...JX2 PROFI1 8 Sample Programs 62 Jetter AG ...
Страница 63: ...JX2 PROFI1 Appendices Jetter AG 63 Appendices ...